Grounding For Ac Power; Supplying Power To The Unit; Total Access 900 Series - ADTRAN Total Access 916 Hardware Installation Manual

Total access 900 series
Hide thumbs Also See for Total Access 916:
Table of Contents

Advertisement

Unit Installation

Grounding for AC Power

The attachment-plug receptacles in the vicinity of the product or system are all to be of a grounding type,
and the equipment grounding conductors serving these receptacles are to be connected to earth ground at
the service equipment.

Supplying Power to the Unit

As shipped, each Total Access 900 Series product is set to factory default conditions. After installing the
unit, the Total Access 900 Series product is ready for power-up. To power the unit, ensure that the unit is
properly connected to an appropriate power source (as outlined in the sections below).

Total Access 900 Series

The Total Access 900 Series comes equipped with a 90 -120 VAC, 60 Hz power supply. The maximum
power consumption is 50 W. A grounded, three-plug detachable cable is included with the shipment.
Use only copper conductors when making power connections.
Install unit in accordance with Article 400 and 364.8 of the NEC NFPA 70.
A readily accessible disconnect device, that is suitably approved and rated, shall be
incorporated in the field wiring.
Maximum recommended ambient operating temperature is 50
28
Total Access 900 Series Hardware Installation Guide
Copyright © 2005 ADTRAN, Inc.
°
C.
61210916L1-34A

Advertisement

Table of Contents
loading

This manual is also suitable for:

Total access 912Total access 924

Table of Contents