Delta Electronics PLC DVP Series DVP-SX Instruction Sheet

Delta electronics plc dvp series instruction manual

Advertisement

Quick Links

Warning
This Instruction Sheet only provides descriptions for electrical specifications, general specifications, installation &
wiring, troubleshooting and peripherals. Other detail information about programming and commands is compatible
with SA/SC/SX series; please see PLC Application Manual. For more information about the optional peripheral,
please see individual product manual.
This is an OPEN TYPE PLC. The PLC should be kept in an enclosure away from airborne dust, humidity, electric
shock risk and vibration. Also, it is equipped with protective methods such as some special tools or keys to open the
enclosure, so as to avoid the hazard to users and the damage to the PLC.
Never connect the AC main circuit power supply to any of the input/output terminals, as it will damage the PLC.
Check all the wiring prior to power up. To avoid any electromagnetic noise, make sure the PLC is properly
grounded
. DO NOT touch terminals when power on.
Introduction
Thank you for choosing DELTA's PLC DVP series. The DVP-SX series is a 10-point (4DI+2DO+2AI+2AO)
special main processing unit. Besides the same commands and functions as DVP-SA/SX/SC series, 2-CH
12-bit analog voltage/current input and 2-CH 12-bit analog voltage/current output are all bipolar. There is
built-in 2-digit 7-segment display corresponds to internal register directly to display PLC station or
user-defined code.
Product Profile and Outline
Status indicator: POWER, RUN,
1
ERROR, BAT.LOW
2
RUN/STOP switch
3
2-digital 7-segment display
4
Digital I/O terminal
5
DIN rail clip
6
Analog I/O terminals
7
I/O point indicators
8
COM1 (RS-232) (Rx) indicator
9
COM2 (RS-485) (Tx) indicator
COM1 (RS-232)
10
Communication port (Slave)
Units: mm
11
Nameplate
12
Expansion port
Mounting hold of the expansion
13
unit
Battery replacement: Please change the battery within 3 minutes, or the
14
DIN rail (35mm)
internal data of the PLC (including the program area, RTC and latched
15
Expansion unit clip
registers) could be lost or destroyed.
COM2 (RS-485)
16
Communication port
17
DC Power input
2 pin removable terminal
18
(standard accessory)
Power input cable
19
(standard accessory)
20
Battery Cover
21
Battery socket connection
22
Battery mount
Electrical Specifications
Electrical Specifications
Model
DVP10SX11R/T
DVP08SM11N
DVP08SN11R/T
Item
MPU: 24V DC (-15% ~ 20%) (with DC input reverse polarity protection),
Power supply voltage
Expansion Unit: supplied by the MPU
Fuse
2A / 250V AC
Power Consumption
5W
1W
1.5W
> 5 M
at 500 V DC (Between all inputs / outputs and earth)
Insulation Resistance
Ω
ESD: 8KV Air Discharge
EFT: Power Line: 2KV, Digital I/O: 1KV, Analog & Communication I/O: 250V
Noise Immunity
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV
RS: 26MHz~1GHz, 10V/m
The diameter of grounding wire cannot be smaller than the wire diameter of terminals L and N
Grounding
(All DVP units should be grounded directly to the ground pole).
Operation: 0°C ~ 55°C (temperature), 50 ~ 95% (humidity), Pollution degree 2;
Environment
Storage: -25° C ~ 70°C (temperature), 5 ~ 95% (humidity); D/A output operation: 0°C ~ 50°C
(temperature)
Vibration / Shock
Standard: IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea)
Resistance
Weight (approx.) (g)
138 / 133
64
88 / 68
Approvals
Electrical Specification of Input Point
Electrical Specification of Output Point
Input Type
DC (SINK or SOURCE)
Output Type
Relay-R
Current
1.5A/1 point
Input Current
24V DC 5mA
Specification
(5A/COM)
Off
On,
Voltage
Below 250V
X0,X1: above 18.5V DC
Specification
AC, 30V DC
X2,X3: above 16.5V DC
Active Level
On
O ff,
75VA
(Inductive)
X0~X3 below 8V DC
Maximum
Loading
90 W
About 10ms (An
(Resistive)
Responding
adjustment range of 0 ~ 20
Time
ms could be selected
Responding
About 10 ms
through D1020 and D1021)
Time
Model Name & I/O Configuration
Input
Model
Power
Point
Type
Point
DI AI
DI
AI
DO AO
24V
-20 ~ 20mA
DVP10SX11R
4
2
2
DC
DC24V/5 mA
range(-1,000 ~ +1,000)
+20%
Sink or Source
-10 ~ +10V
DVP10SX11T
4
2
range(-2,000 ~ +2,000) 2
-15%
Installation & Wiring
ENGLISH
3.1 PLC Mounting Arrangements and Wiring Notes
Installation of the DIN rail:
The DVP-PLC can be secured to a cabinet by using the
DIN rail that is 35mm high with a depth of 7.5mm. When
mounting the PLC on the DIN rail, be sure to use the
end bracket to stop any side-to-side motion of the PLC,
thus to reduce the chance of the wires being pulled
loose. At the bottom of the PLC is a small retaining clip.
To secure the PLC to the DIN rail, place it onto the rail
and gently push up the clip. To remove it, pull down the
retaining clip and gently pull the PLC away from the DIN
rail. As shown on the right:
Wiring:
1. Please use 22-16AWG (1.5mm) wiring (either single or multiple core) for
22-16AWG
I/O wiring terminals. The specification for the terminals is as shown on
the left. PLC terminal screws should be tightened to between 1.95
kg-cm (1.7 in-lbs). Use 60/75° C copper conductor only.
2. I/O signal wires or power supply should not run through the same
< 1.5mm
multi-wire cable or conduit.
3.2 Wiring Notes
Power Input Wiring
DVP-SX series input power supply is DC input. Please take a note of listed items when operating DVP-SX.
Series.
1. Please make sure the power is at terminals 24V DC and 0V (power range is 20.4V DC ~ 28.8V DC). When
voltage is lower than 20.4V DC, PLC will stop operating, all outputs will turn Off and ERROR LED will flash
continuously.
2. If the power-off time is less than 10ms, the PLC still operates unaffectedly. If the power-off time is too long or
the power voltage drops, the PLC will stop operating and all the outputs will be Off. Once the power is
restored, the PLC will return to operate automatically. (There are latched auxiliary relays and registers
inside of the PLC, please be aware when programming.)
20.4V~28.8V
24VDC
OV
DC Input Type
2A
Safety Wiring
Since the PLC is in control of numerous devices, motion of either one device could affect the motion of other
devices, therefore the breakdown of either one device would consequently be detrimental to the whole auto
control system, and danger will thus be resulted. Please use the recommended wiring below for the power
input:
5
MC
DVP08SP11R/T
DVP16SP11R/T
4
8
2
-
G uard
Limit
1.5W
2W
MC
3
MC
L
N
7
6
Input Point Wiring
The input signal of the input point is the DC power DC input. There are two modes of DC type wiring: SINK and
SOURCE, defined as follows:
90 / 70
96 / 76
Sink = Current flows into the common terminal S/S
S/S
Sinkin g
Transistor-T
0.3A/1 point @ 40°C; When the output of Y0
X0
and Y1 is high-speed pulse, Y0 and Y1 =
30mA
30V DC
Loop Equivalent Circuit of Input Point
+24V
When the output of Y0 and
24G
Y1 is high-speed pulse, Y0
DC Type
9W/1 point
and Y1 = 0.9W (Y0 = 32kHz,
(DC Signal IN)
Y1 = 10kHz)
S/S
Off
O n 20us
Y0 and Y1 are specified
points for high-speed pulse
X0
On
O ff 30us
SINK Mode
Loop Equivalent Circuit of Input Point
Output
Type
+24 V
DC Type
DO
AO
24 G
(DC Signal IN)
-20 ~ 20mA
2
Relay
(range:-2,000 ~ +2,000)
S/ S
-10 ~ +10V
2
Resistor
(range:-2,000 ~ +2,000)
X0
SOURCE Mode
Output Point Wiring
DVP-**-**-11-R
L O AD
Y0
LED
When installing the DVP series
RY
C0
PLC, make sure that it is
installed in an enclosure with
R E LAY O UT P U T
sufficient space (as shown
below) to its surroundings so as
to allow heat dissipation.
DVP-**-**-11-T
Y0
T
D
LED
R
G
D
D
C0
DV P
M P
D
TRANSISTOR OUTPUT
D > 50 mm
Analog Input/Output Point Wiring
Voltage input
CH0
-10V~+10V
V+
250
*3
I+
COM
Shielded*1
Current input
CH1
-20mA~+20mA
V+
*2
250
I+
COM
Shielded*1
voltage output
-10V~+10V
*5
CH0
V+
I+
COM
AC drive, recorder,
shielding cable *1
scale valve...
current output
CH1
-20mA~20mA
V+
I+
COM
AC drive, recorder,
shielding cable *4
scale valve...
S/ S X0
X1
X2
terminal of
power module
24+
DC /DC
5V
DC24V
24-
class 3 grounding
(100
or less)
Power supply for AC loads
Power Circuit Protection Fuse (3A)
1
Power On pilot indicator
Emergency stop
The machinery must provide a quick manual method
disconnecting all system power.
Circuit isolation device (System Power Disconnect)
Utilize the electromagnetic contactor and the relay to be the
isolation unit of the power circuit to prevent the possible
1
instability of the system when the power is supplied on and off.
DVP PLC MPU (main processing unit)
Grounding
Power supply:
AC: 100 ~ 240V AC, 50/60Hz
DC: 24V DC
產 品 外 觀 及 各 部 介 紹
Source = Current flows out of common terminal S/S
X0
S/S
So urcing
Wiring Loop
24VDC
SINK
+5V
+24V
OV
S/S
X0
X1
X2
24VDC
Sink Type
電 池 安 裝
電 池 安 裝 : : : :
電 池 安 裝
電 池 安 裝
Wiring Loop
24VDC
SOUR CE
+5V
+24V
OV
S/S
X0
X1
X2
24VD C
Source Type
電 氣 規 格
1. There are two kinds of DVP-SX Series PLC output
modules: Relay and Transistor. For relevant electrical
P OW E R
specification, please refer to the function specification.
2. Be careful with the connection of the common
terminals when wiring outputs. For example, when
wiring DVP12SX11R, output terminal Y0 uses one
common terminal C0, Y1 uses C1, as shown below:
LOAD
C0 Y0 C1 Y1
<0.3A
Action indication: When the output point is active, the
corresponding indicator at the front will be on.
3. Isolated circuit: The optical coupler is used to isolate
/
signals between PLC internal circuits and input
modules.
Note 1:
Please isolate analog input and other power
100K
wiring.
CH0
100K
Note 2:
If input signal is in current, please short out
AG
between V+ and I+ terminals.
100K
CH1
Note 3:
100K
If the noise interference from loaded input wiring
terminal is significant, please connect a
AG
capacitor with 0.1 ~ 0.47µF 25V for noise
filtering.
Note 4:
Please isolate analog output and other power
CH0
wiring.
Note 5:
機 種 型 號 與
If the noise interference from loaded input wiring
terminal is significant, please connect a
CH1
capacitor with 0.1 ~ 0.47µF 25V for noise
filtering.
Note 6:
DVP10SX11R
Please connect
power module terminal and
analog output module terminal to system
+15V
DC/DC
DVP10SX11T
AG
earth point and make system earth point be
converter
-15V
grounded or connects to machine cover.
Warning:
DO NOT wire to the No function terminal
注 意 事 項
SA/SX/SC
PLC
OPEN TYPE
:
/
產 品 簡 介
DVP
DVP-SX
10
4DI+2DO+2AI+2AO
SA/SX/SC
2CH
12-bit
/
2CH
12-bit
/
2
1
2
RUN/STOP
2
3
4
I/O
5
DIN
6
I/O
7
/
COM1 (RS-232)
8
(Rx)
COM2 (RS-485)
9
(Tx)
mm
COM1 (RS-232)
10
(Slave)
11
12
13
3
PLC
14
DIN
(35mm)
15
COM2 (RS-485)
16
(Master/Slave)
17
18
2 pin
19
20
21
22
產 品 規 格
DVP10SX11R/T
DVP08SM11N
DVP08SN11R/T
DVP08SP11R/T
DVP16SP11R/T
24V DC -15% ~ 20%
2A/250V AC
-
5W
1W
1.5W
1.5W
2W
5M
/
500V DC
ESD: 8KV Air Discharge
EFT: Power Line: 2KV, Digital I/O: 1KV, Analog & Communication I/O: 250V
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV
RS: 26MHz ~ 1GHz, 10V/m
L,N
PLC
0°C ~ 55°C
50 ~ 95%
2
-25°C ~ 70°C
5 ~ 95%
D/A
0°C ~ 50°C
/
IEC61131-2, IEC68-2-6 (TEST Fc)/IEC61131-2 & IEC68-2-27 (TEST Ea)
, g
138 / 133
64
88 / 68
90 / 70
96 / 76
SINK
SOURCE
-R
-T
0.3A/1
@ 40°C
24V DC 5mA
1.5A/1
5A/COM
, Y0 Y1
30mA
Off → On,
X0 X1
18.5V DC
250V AC,30V DC
30V DC
X2 X3
16.5V DC
On → Off,
75VA
X0~X3
8V DC
9W/1
Y0 Y1
0.9W
90W
Y0 50KHz Y1 10KHz
10ms
D1020
D1021
0 ~ 20ms
Off → On 20us
Y0 Y1
10 ms
On → Off 30us
配 置
I/O
DI AI
DI
AI
DO AO
DO
AO
-20 ~ 20mA
-20 ~ 20mA
4
2
2
2
24VDC
DC24V/5 mA
(
-1,000 ~ +1,000)
(
-2,000 ~ +2,000)
+20%
Sink
Source
-10 ~ +10V
-10 ~ +10V
-15%
4
2
2
2
(
-2,000 ~ +2,000)
(
-2,000 ~ +2,000)
繁 體 中 文
繁 體 中 文
繁 體 中 文
繁 體 中 文
/
/

Advertisement

loading

Summary of Contents for Delta Electronics PLC DVP Series DVP-SX

  • Page 1 Electrical Specifications Item Power supply voltage Fuse Power Consumption Insulation Resistance Noise Immunity Grounding Environment Vibration / Shock Resistance Weight (approx.) (g) Approvals Electrical Specification of Input Point Input Type Input Current Active Level Responding Time Model Name & I/O Configuration DVP10SX11R DVP10SX11T Warning...
  • Page 2 輸 出 點 之 配 線 安 裝 及 配 線 盤 內 安 裝 及 配 線 鋁 軌 之 安 裝 方 法 : : : : 鋁 軌 之 安 裝 方 法 鋁 軌 之 安 裝 方 法 鋁...

This manual is also suitable for:

Dvp-sx