Utility power condition

The utility input voltage is outside the operating range.
Action:
Check the input voltage and reconfigure the UPS
1.
Contact a qualified electrician to verify that the utility power is suitable for the UPS.
2.

Internal UPS fault condition

Action:
Power down the UPS
1.
If the condition persists, contact an HP authorized service representative.
2.

REPO condition

Action:
If the remote switch is closed, then open the switch to enable power to the output receptacles.
If the condition occurred while reconnecting a disconnected REPO port, then verify the polarity of the
REPO connector pins.
For more information about REPO ports, see "Connecting the REPO port (on page 20)."

Site wiring condition

Action: Contact a qualified electrician to be sure that:
The utility power receptacle is grounded.
There is a ground wire in the UPS power cord.
The line and neutral wires are not reversed in the wall outlet.

Overload condition

All the load LEDs are illuminated.
Action:
Power down the UPS
1.
Remove one or more load devices to reduce the power requirements.
2.
Wait at least 5 seconds and restart the UPS.
3.
If the condition persists, verify that the load devices are not defective.
4.

UPS does not start

Action:
("Powering down the
UPS" on page 31).
("Powering down the
UPS" on page 31).
("Configuring the
UPS" on page 28).
Troubleshooting 44