Troubleshooting A Fan; Troubleshooting System Memory - Dell PowerEdge R410 Hardware Owner's Manual

Dell server hardware owner's manual
Hide thumbs Also See for PowerEdge R410:
Table of Contents

Advertisement

Troubleshooting a Fan

WARNING:
cover and access any of the components inside the system. Before you begin this
procedure, review the safety instructions that came with the system.
1 Locate the faulty fan indicated by the LCD panel or the diagnostic
software.
2 Turn off the system and all attached peripherals.
3 Open the system. See "Opening the System" on page 82.
4 Reseat the fan's power cable.
5 Restart the system.
If the fan functions properly, close the system. See "Closing the System" on
page 83.
6 If the fan does not function, turn off the system and install a new fan.
See "Replacing a Cooling Fan" on page 114.
7 Restart the system.
If the problem is resolved, close the system. See "Closing the System" on
page 83.
If the replacement fan does not operate, see "Getting Help" on page 167.

Troubleshooting System Memory

WARNING:
cover and access any of the components inside the system. Before you begin this
procedure, review the safety instructions that came with the system.
1 If the system is operational, run the appropriate online diagnostic test.
See "Running the System Diagnostics" on page 163.
If diagnostics indicates a fault, follow the corrective actions provided by
the diagnostic program.
2 Turn off the system and attached peripherals, and unplug the system from
the power source. Press the power button with the system unplugged, and
then reconnect the system to power.
152
Troubleshooting Your System
Only trained service technicians are authorized to remove the system
Only trained service technicians are authorized to remove the system