Setting Touch Switches
Reference: Specification of notify bits and input of I/O comments is possible by using either the
S Noti Bit:
S No.:
S Lamp Bit:
S Comment:
S Act Type:
input notification window or the touch switch setting screen.
Specify the PC bit that is notified that the touch switch
has been pressed here (only when direct connection is
used).
Specify the number used to notify that a touch switch
has been pressed, or to control the touch switch on/off
(flashing) status (used only when direct connection is
not used).
Specify the bit in the PC that controls the on/off (flash-
ing) status of the touch switch (used only when direct
connection is used).
Input a memo here, for example one that indicates the
purpose of use.
Specify the effect of pressing the touch switch here.
When using an NT20M or NT600M, or an NT20S or
600S with Ver.5 direct connection, or using an NT612G
or NT610C and not using direct connection, or using
Ver.1 direct connection, setting is not possible and the
setting is fixed as "Moment".
Moment:
The PC bit comes ON when the touch
switch is pressed and goes OFF when it is
released.
Altnat:
Each time the touch switch is pressed the
status of the PC bit (ON/OFF) is changed
to the opposite status.
Set:
The PC bit is switched ON when the touch
switch is pressed.
Rset:
The PC bit is switched OFF when the
touch switch is pressed.
Section 4-7