Omron H5S Datasheet page 4

Digital time switch
Hide thumbs Also See for H5S:
Table of Contents

Advertisement

■ Characteristics
Item
± 0.01% ± 0.05 s max. (See note 1.)
Accuracy of operating
The ± 0.01% value applies to the set time interval.
time
Setting error
Influence of voltage
Influence of temperature
± 15 s per month (at 25 ° C)
Cyclic error
Continuous use: 5 years min. (at 25 ° C) (See note 2.)
Memory protection
100 M Ω min. (between current-carrying terminals and exposed non-current carrying metal parts, between operation
Insulation resistance
circuit and control output circuit, between control output circuits, and between non-continuous contacts.)
Dielectric strength
2,950 VAC, 50/60 Hz for 1 min (between current-carrying terminals and exposed non-current carrying metal parts)
2,000 VAC, 50/60 Hz for 1 min (between operation circuit and control output circuit, and between control output
circuits)
1,000 VAC, 50/60 Hz for 1 min (between non-continuous contacts)
± 1,500 V (between power terminals, for AC power models), ± 500 V (between power terminals, for DC power models)
Noise immunity
Square-wave noise by noise simulator (pulse width: 100 ns, for 1 µ s, 1-ns rise time)
Vibration
Destruction 10 to 55 Hz with 0.375-mm single amplitude in 3 directions for 2 hours each
resistance
Malfunction 10 to 55 Hz with 0.25-mm single amplitude in 3 directions for 10 minutes each
Shock
Destruction 300 m/s
resistance
Malfunction 100 m/s
Life
Mechanical
100,000 operations min.
expectancy
Electrical
50,000 operations min. (15 A at 250 VAC, resistive load)
50,000 operations min. (10 A at 30 VDC, resistive load)
50,000 operations min. (10 A at 250 VAC, inductive load (cos φ = 0.7))
50,000 operations min. (1 HP at 250 VAC, motor load)
50,000 operations min. (100 W at 100 VAC, lamp load)
10,000 operations min. (300 W at 100 VAC, lamp load)
Approved standards
cURus: UL 508/CSA C22.2 No.14,
Conforms to EN 60730-2-7(Pollution degree 2/overvoltage category II),
Conforms to VDE 0106/part100.
Conforms to Electrical Appliance and Material Safety Law (for Japan)
EMC
(EMI)
EMI Radiated:
EMI Conducted (Continuous):
EMI Conducted (Non-continuous):
Harmonic Current:
Voltage fluctuation/flicker:
(EMS)
ESD Immunity:
Radiated Electromagnetic Field Immunity: EN 60730-2-7 (IEC 61000-4-3): 10-V/m AM modulation
Conducted Disturbance Immunity:
Burst Immunity:
Surge Immunity:
line)
Voltage Dip/Interrupting Immunity:
Weight
Approx. 200 g
Note: 1. The total error including the repeat accuracy, setting error, variation due to voltage change, and variation due to temperature change is
± 0.01% ± 0.05 s max.
2. The total time when power is not being supplied.
4
Digital Time Switch
Weekly 2-circuit Models
(H5S-W@2)
2
3 times each in x, y, and z axes, 6 directions
2
3 times each in x, y, and z axes, 6 directions
H5S
Yearly 2-circuit Models
(H5S-Y@2)
± 15 s per month (at − 10 to 45 ° C), ± 20 s per month (at 45 to 55 ° C)
EN 60730-2-7
EN 60730-2-7 (CISPR 22 Class B)
EN 60730-2-7 (CISPR 22 Class B)
EN 60730-2-7 (CISPR 14-1)
EN 60730-2-7 (IEC 61000-3-2 Class A)
EN 60730-2-7 (IEC 61000-3-3)
EN 60730-2-7
EN 60730-2-7 (IEC 61000-4-2): 6 kV contact discharge
EN 60730-2-7 (IEC 61000-4-6): 10 V (0.15 to 80 MHz)
EN 60730-2-7 (IEC 61000-4-4): 2 kV power line
EN 60730-2-7 (IEC 61000-4-5): 1 kV line to line (power line, output line)
EN 60730-2-7 (IEC 61000-4-11): 0.5-s cycle, 100% (rated voltage)
Yearly 4-circuit Models
(H5S-Y@4)
50,000 operations min. (3 A at 250
VAC, resistive load)
50,000 operations min. (3 A at 30
VDC, resistive load)
8 kV air discharge
(80 MHz to 1 GHz, 1.4 GHz to 2 GHz)
10-V/m pulse modulation (900 MHz)
1 kV control line
2 kV line to ground (power line, output
0.5 kV line to line (input line)
1 kV line to ground (input line)