Omron SYSDRIVE 3G3MV SERIES User Manual page 213

Sysdrive 3g3mv series multi-function compact inverter
Hide thumbs Also See for SYSDRIVE 3G3MV SERIES:
Table of Contents

Advertisement

Communications
Register No.
(Hex)
0023
Frequency reference
0024
Output frequency
0025 to 0026
Not used.
0027
Output current
0028
Output voltage
0029
Fault status 2 (See note.)
002A
Warning status (See note.)
002B
Input terminal status
002C
Inverter status 1
002D
Output terminal status
002E
Inverter status 2 (See note.)
002F to 0030
Not used.
0031
Main circuit DC voltage
0032
Torque reference
0033 to 0034
Not used.
0035
Accumulated operating time
(See note.)
0036
Not used.
0037
Output power
0038
PID feedback
0039
PID input
003A
PID output
003B to 003C
Not used.
003D
Communications error
003E to 00FF
Not used.
Note The fault status 2, warning status, Inverter status 2, and accumulated operating time functions are
provided for 5.5- and 7.5-kW Inverters only.
D Status Signal (Register 0020 Hex)
Bit No.
0
1
2
3
4
5
6
7
8 to 15
Function
During RUN (1: During RUN)
Forward/reverse operation (1: Reverse operation)
Inverter ready (1: Ready)
Fault (1: Fault)
Data setting error (1: Error)
Multi-function output 1 (1: ON)
Multi-function output 2 (1: ON)
Multi-function output 3 (1: ON)
Not used.
Description
According to the set value in n152.
According to the set value in n152.
---
Read based on 1 A as 10.
Read based on 1 V as 1.
Refer to the following corresponding table.
Refer to the following corresponding table.
Refer to the following corresponding table.
Refer to the following corresponding table.
Refer to the following corresponding table.
Refer to the following corresponding table.
---
Read based on 1 V as 1.
Read based on ±1% as ±1 and the rated motor
torque is 100%.
---
Read based on 1 [h] as 1.
---
Read based on ±1 W as ±1. Cannot be monitored in
vector control mode.
Read based on 1% as 10 and a value equivalent to
the maximum frequency as 100%.
Read based on ±1% as ±10 and a value equivalent
to the maximum frequency as 100%.
Read based on ±1% as ±10 and a value equivalent
to the maximum frequency as 100%.
---
Refer to the following corresponding table.
---
Function
Chapter 7
7-23