Multi-Function Output - Omron SYSDRIVE 3G3MV SERIES User Manual

Sysdrive 3g3mv series multi-function compact inverter
Hide thumbs Also See for SYSDRIVE 3G3MV SERIES:
Table of Contents

Advertisement

Basic Operation
• For n101, set the origin search deceleration time to the time required to go from 100% to 0% of the
maximum frequency.
• If 0 is set for the origin search deceleration time, operation will be carried out at the default setting of 2.0
seconds.
• For n102, set the operating level as a percentage, with the Inverter's rated input taken as 100%. If the
Inverter's output current drops below the level of the Inverter's output current, the speed search will be
completed and acceleration will be resumed.

5-10-2 Multi-function Output

The 3G3MV incorporates four multi-function output terminals: two multi-function contact
outputs (MA and MB) and two multi-function photocoupler outputs (P1 and P2).
Output from these terminals has a variety of functions according to the application.
H Selecting the Multi-function Output (n050 through n056)
n057
Multi-function Output 1 (MA/MB
and MC)
Setting
0 to 7, 10 to 21 (See note.)
range
n058
Multi-function Output 2 (P1 and
PC)
Setting
0 to 7, 10 to 21 (see note.)
range
n059
Multi-function Output 3 (P2 and
PC)
Setting
0 to 7, 10 to 21 (See note.)
range
Note Set values 20 and 21 are available for 5.5- and 7.5-kW Inverters only.
Set Values
Value
Function
0
Fault output
1
Operation in progress
2
Frequency agree
3
Idling
4
Frequency detection 1
5
Frequency detection 2
6
Overtorque being
monitored (NO-contact
output)
7
Overtorque being
monitored (NC-contact
output)
5-36
Register
0139 Hex
Unit of
1
setting
Register
013A Hex
Unit of
1
setting
Register
013B Hex
Unit of
1
setting
ON: Fault output (with protective function working)
ON: During RUN (with RUN command input or inverter output)
ON: Frequency agree (output frequency agrees with frequency
reference)
ON: Zero speed (at less than min. output frequency)
ON: Output frequency y frequency detection level (n095)
ON: Output frequency x frequency detection level (n095)
Output if any of the following parameter conditions is satisfied.
• Overtorque detection function selection 1 (n096)
• Overtorque detection function selection 2 (n097)
• Overtorque detection level (n098)
O
t
d t
ti
l
• Overtorque detection time (n099)
Note NO contact: ON with overtorque being detected; NC contact:
OFF with overtorque being detected
Changes during
operation
Default setting
Changes during
operation
Default setting
Changes during
operation
Default setting
Description
l ( 098)
Chapter 5
No
0
No
1
No
2