5.4 Setting and calibrating meters

 : FM Terminal meter selection
: FM Terminal meter adjustment

 : AM Terminal meter selection
 : AM Terminal meter adjustment
・Function
The terminals AM and FM send out analog voltage signals. (Absolute value output)
Use a full-scale 0~1 mAdc ammeter or a full-scale 0~7.5 Vdc (10 Vdc) voltmeter.
To calibrate the meter connected to the terminal FM or AM, use the FM Terminal meter adjustment
 or the AM Terminal meter adjustment  respectively.
Connect meters as shown below.
<Connection to terminal FM>        <Connection to terminal AM>
FM
VF−P7
CC
☆An frequency meter QS60T is optionally available.
  [Terminal FM-related parameters]
Title
FM Terminal meter

selection
FM Terminal meter

adjustment
Meter : Frequency meter
(Default setting)
The reading of the
frequency meter fluctuates
during calibration.
Function
: Running frequency
: Frequency command
: Current
: DC voltage
: Output voltage
: After-compensation frequency
: Speed feedback (real-time value)
: Speed feedback (1 second filter)
: Torque
: Torque reference
: Internal torque reference
: Torque current
: Exciting current
: PID feedback value
: Motor overload factor (OL2 data)
: Inverter overload factor (OL1 data)
: PBr overload factor (PBrOL data)
: PBr load factor (pulse duty)
: Input power
: Output power
: Peak output current
: Peak DC voltage
: Motor counter dummy PG
: Position pulse
: RR input
: VI/II input
: RX input
: RX2 input
: FM output
: AM output
: Fixed output for meters
: Analog output for communication
: Acc/dec torque removal
E-10
AM
VF−P7
CC
  ☆
Use an ammeter capable of measuring up to a current
1.5 times larger than the rated current of the inverter.
Adjustment range
Meter: Ammeter
(Default setting)
The reading of the
ammeter fluctuates during
calibration.
Default setting
Adjustment level
(a)
(a)
(b)
(b)
(b)
(a)
(a)
(a)
(b)
(b)
(b)
(b)
(b)
(a)
(c)
(c)
(c)
(c)
(e)
(e)
(b)
(b)
(d)
(d)
(c)
(c)
(c)
(c)
(c)
(c)
(c)
(b)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents