Input /
Terminal
output
symbol
Multifunction programmable analog output. Factory
default setting: Operation frequency command.
FM
Output
Connect
7.5Vdc(10Vdc)-1mA full-scale voltmeter.
Multifunction programmable analog output. Factory
default setting: Output current. Connect a 1mAdc
AM
Output
full-scale ammeter or a 7.5Vdc(10Vdc)-1mA full-
scale voltmeter.
Multifunction open collector output. This terminal
FP
outputs pulses at 1.00 kHz to 43.20 kHz. Factory
Output
default setting: 3.84kHz.
Common
CC
Common terminal of the control circuit.
to I/O
24Vdc power output (power for control of the
P24
Output
inverter).
Multifunction programmable open collector output.
OUT1
The terminal has been set by default so as to detect
and output low-speed signal output frequencies.
Output Multifunction programmable open collector output.
The terminal has been set by default so as to detect
OUT2
and outputs signals indicating the completion of
acceleration/ deceleration.
Relay contact output.
A (cosφ= 1), 30 Vdc-1 A and 250 Vac-1A (cosφ =
FLA
0.4).
Used to detect the activation of the inverter's
FLB
Output
protective function. If the protective function is
FLC
activated, FLA-FLC circuit is closed, while FLB-FLC
circuit is opened .
Function
a
1mAdc
full-scale
Contact rating: 250 Vac = -2
Electrical
specification
1mA full-scale dc
ammeter or
ammeter
or
a
7.5Vdc-1mA full-
scale dc voltmeter
1mA full-scale dc
ammeter or
7.5Vdc-1mA full-
scale dc voltmeter
Max. 50 mA
24Vdc-100mA
Open
output:
24Vdc-50mA
*Sink logic/
source logic
switchable
250Vac-2A
30Vdc-1A
:resistor load
250Vac-1A
:cosφ=0.4
B-9
Inverter internal
circuit
0.01μ
100k 18k
4.7k
0.01μ
0.1μ
33k
15k
P24
P5
3 . 9
10k
F U S E
0.1μ
68k
collector
F U S E
10 10
FL
 10k
470p
P24
P5
1 50
10k
7k

Hide quick links: