Toshiba TOSVERT VF-P7 Instruction Manual page 171

Inverter for fan and pump applications
Hide thumbs Also See for TOSVERT VF-P7:
Table of Contents

Advertisement

■Table of contact input terminal function settings
Parameter setting
Positive
Negative
logic
logic
0
1
No assignment function
2
3
F: Forward operation command
4
5
R: Reverse operation command
6
7
ST: Standby (Inverse)
8
9
RES: Reset
10
11
S1: Preset-speed #1
12
13
S2: Preset-speed #2
14
15
S3: Preset-speed #3
16
17
S4: Preset-speed #4
18
19
Jog run
20
21
Emergency stop
22
23
DC injection breaking
Acceleration/deceleration
24
25
switching #1(*2)
Acceleration/deceleration
26
27
switching #2(*2)
28
29
V/f switching #1(*2)
30
31
V/f switching #2(*2)
32
33
Torque limit switching #1(*2)
34
35
Torque limit switching #2(*2)
36
37
PID control OFF selection
38
39
Pattern group #1
40
41
Pattern group #2
42
43
Pattern group #3
44
45
Pattern group #4
46
47
Pattern run continuation signal
48
49
Pattern run trigger signal
50
51
Forced Jog forward operation
52
53
Forced Jog reverse operation
54
55
Reservation area(*3)
56
57
Reservation area(*3)
58
59
Reservation area(*3)
60
61
Reservation area(*3)
62
63
Reservation area(*3)
64
65
Reservation area(*3)
66
67
Reservation area(*3)
68
69
Reservation area(*3)
(*1): Valid when (Speed setting mode selection) is set at (Up-down frequency).
The frequency setting range is between 0.0 to (Upper limit frequency).
In this case, acceleration time is (Acceleration time #2), and deceleration time is
(Deceleration time #2).
(*2): To switch acceleration/deceleration pattern, V/f pattern, torque limit #1∼#4, give the
following signals to switching functions. (in case of positive logic)
Acc/dec, V/f, torque limit #1
Acc/dec, V/f, torque limit #2
Acc/dec, V/f, torque limit #3
Acc/dec, V/f, torque limit #4
(*3): Reservation area. Do not set at these functions.
■Sink logic/source logic
Switching between sink logic and source logic (input/output terminal logic) is possible.
For details, refer to the section 2.3.2.
Parameter setting
Function
Positive
logic
70
72
74
76
78
80
82
84
86
88
90
92
94
96
98
100
102
104
106
108
110
112
114
116
118
120
122
124
126
128
130
132
134
switching #1
OFF
ON
OFF
ON
G-4
Function
Negative
logic
71
Reservation area(*3)
73
Reservation area(*3)
75
Reservation area(*3)
77
Reservation area(*3)
79
Reservation area(*3)
81
Reservation area(*3)
83
Reservation area(*3)
85
Reservation area(*3)
87
Binary data write
89
Up/down frequency (up) (*1)
91
Up/down frequency (down) (*1)
93
Up/down frequency (clear)
95
PUSH-type run command
97
PUSH-type stop command
99
Forward/reverse selection
101
Run/stop command
103
Commercial power/INV switching
Frequency reference priority
105
switching
107
VI/II terminal priority
109
Command terminal board priority
111
Parameter editing enabling
Control switching (torque,
113
position)
115
Deviation counter clear
117
Position control forward limit LS
119
Position control reverse limit LS
Light load high-speed operation
121
enabling
123
Reservation area(*3)
125
Preliminary excitation
System consistent sequence
127
(BC: Braking command)
System-supporting sequence
129
(B: Brake release)
System-supporting sequence
131
(BA: Brake answer)
System-supporting sequence
133
(BT: Brake test)
135
Reservation area(*3)
switching #2
OFF
OFF
ON
ON