1. DESCRIPTION
Viking Early Suppression Fast Response (ESFR) Pendent Sprinkler VK510
incorporates the capability to suppress specific high-challenge fires. The larger
K-Factor allows protection of higher hazard commodities at greater ceiling heights
with lower end-head pressures. K25.2 sprinklers can:
• Provide flexibility of fire protection designs.
• Reduce or eliminate the need for a system fire pump.
• Eliminate the use of in-rack sprinklers when protecting high piled storage of
certain specified materials up to:
UL (Refer to Table 4): 40 ft. (12,2 m) with ceilings up to 45 ft. (13,7 m)*
FM (Refer to Table 5): 45 ft. (13,7 m) with ceilings up to 50 ft. (15,2 m)*
NFPA 13 (Refer to Table 6): The VK510 is a Special Sprinkler as defined by
the National Fire Protection Association (NFPA 13, 2022 Ed.-Section 15.2).
Viking ESFR Pendent Sprinklers VK510 are primarily intended to protect the
following types of storage, which tend to produce severe-challenge fires: palletized
and solid pile storage as well as single, double, multiple, and portable open rack
storage (no open-top containers or solid shelves). The VK510 is listed to utilize a
minimum aisle width of 6'-0" (UL - 40' storage or FM - 45' storage).
Viking ESFR Pendent Sprinklers VK510 provide protection of most common
storage materials, including:
• Encapsulated or unencapsulated Class I, II, III, and IV commodities*.
• cULus Listed for protection of cartoned nonexpanded** Group A plastic
commodities*.
• FM Approved for protection of cartoned unexpanded** plastic commodities.*
* Refer the Approval Chart and Commodity Selection and Design Criteria Overview for Listing
and Approval requirements that must be followed.
** The terms nonexpanded and unexpanded are equivalent.
2. LISTINGS AND APPROVALS*
cULus Listed: Category VNWH (Listed as a Specific Application ESFR
Sprinkler)
FM Approved: Class 2026
VdS Approved: Certificate G4040015
LPCB Approved: Ref. No. 096g/01
China Approval: Approved according to China GB Standard
* Refer the Approval Chart and Commodity Selection and Design Criteria Overview for Listing and Approval requirements that must be followed.
3. TECHNICAL DATA
Specifications:
Maximum Working Pressure: 175 psi (12 bar). Factory tested hydrostatically to 500 psi (34.5 bar).
Thread size: 1" NPT or 25 mm BSPT (Refer to Table 2)
Nominal K-factor: 25.2 U.S. (363 metric*)
* Metric K-factor measurement shown is in bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
Overall Length: 3-3/16" (81 mm)
Deflector Diameter: 1-3/4" (45 mm)
Material Standards:
Frame Casting: Brass UNS-C84400
Deflector: Phosphor Bronze UNS-C51000
Seat: Copper UNS-C11000 and Stainless Steel UNS-S30400
Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape
Form No. F_121022
Rev 01
TECHNICAL BULLETIN
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
December 2022
ESFR PENDENT SPRINKLER
UL: SPECIFIC APPLICATION ESFR SPRINKLER
FM: STORAGE SPRINKLER
NFPA: SPECIAL SPRINKLER
VK510 (K25.2)
TABLE 1
SPRINKLER GENERAL INFORMATION
Item
Sprinkler Identification
Number (SIN)
K-factor, gpm/psi
(lpm/bar
)
½
½
Thread Size
Sprinkler Orientation
Maximum Working Pressure
Page 1 of 7
Description
VK510
25.2 (363)
1" NPT (25 mm)
Pendent
175 psi (12 bar)

Advertisement

loading

Summary of Contents for Viking 12080

  • Page 1 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Pendent Sprinkler VK510 incorporates the capability to suppress specific high-challenge fires.
  • Page 2 4. INSTALLATION NOTICE Viking sprinklers are manufactured and tested to meet rigid requirements of the approving agencies. The sprinklers are designed to be installed in accordance with recognized installation standards or FM Global Loss Prevention Data Sheets. System design must be based on guidelines described in the latest edition of the applicable FM Global Loss Prevention Data Sheets indicated for Storage sprinklers, the latest NFPA Standards indicated for ESFR sprinklers, the Authority Having Jurisdiction, and also with the provisions of government codes, ordinances, and standards whenever applicable.
  • Page 3 Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com placed after a specified term of service. For Viking ESFR Pendent Sprinklers, refer to the Installation Standards and the Authorities Having Jurisdiction for the specified period of time after which testing and/or replacement is required. Sprinklers that have operated cannot be reassembled or reused, but must be replaced.
  • Page 4 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com TABLE 2: ORDERING INFORMATION Instructions: Using the sprinkler base part number, (1) add the suffix for the desired Finish (2) add the suffix for the desired Temperature Rating.
  • Page 5 VK510 (K25.2) The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com 1-9/16” Wrench Flat Protective Sprinkler (40 mm) 3-3/16”...
  • Page 6 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com TABLE 4: COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW FOR...
  • Page 7 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com TABLE 6: COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW FOR...

This manual is also suitable for:

Vk5101220020373