IMPORTANT: Read carefully before installing fixture. Retain for future reference.
General: Upon receipt of fixture thoroughly inspect for any
freight damage, which should be brought to the attention of
the delivery carrier. Compare the catalog description listed
on the packing slip with the fixture label on the housing to
assure you have received the correct merchandise.
WARNING:
TOOLS REQUIRED: 3/16" Allen Wrench
1. Using 3/16" Allen Wrench, remove wiring
compartment cover.
2. Feed supply leads through fitter and out wireway
compartment opening. Slide fitter over tenon.
FIXTURE
LEADS
FITTER
3. Tighten (4) set screws to 225 in. lbs. using 3/16"
Allen Wrench.
4. Splice supply leads to fixture leads making sure to
ground the fixture in a manner that complies with
National Electric Code and applicable local codes.
DO NOT USE POLE AS GROUND. Push wires in to
wiring compartment and reinstall cover and gasket.
These instructions do not claim to cover all details or variations in the equipment, procedure, or process described, nor to provide directions for meeting every possible
contingency during installation, operation or maintenance. When additional information is desired to satisfy a problem not covered sufficiently for user's purpose, please
contact your nearest representative.
TM
Risk of Electric Shock. Disconnect power at fuse or circuit breaker before installing
or servicing.
3/8" Allen Wrench
GASKET
1/4-20 BOLT
SUPPLY LEADS
2-3/8" OD TENON
ALLEN WRENCH
SET SCREWS
Customer First Center • 1121 Hwy 74 South • Peachtree City, GA 30269
Safety: This fixture must be wired in accordance with
the national electrical code and applicable local codes
and ordinance. Proper grounding is required to insure
personal safety. Carefully observe grounding procedure
under installation section. All work should be done by a
qualified electrician.
5. Loosen fitter bolt using 3/8" Allen Wrench and
adjust fixture to desired aiming angle. Retighten bolt
to a minimum of 250 in. lbs.
WIRING
COMPARTM
COVER
6. Open door using 3/16" Allen Wrench and install
lamp.
REFLECTOR AND LENS CLEANING
1. Open fixture door.
2. Dust reflector with soft, clean dry cloth.
3. Clean lens with any non-abrasive glass cleaning
solution and rinse with clean water.
4. Wipe lens dry with clean, dry cloth.
NOTE: A regular maintenance schedule should be
followed to retain optimal light output and reduce
heat retention.
DO NOT use alkaline or acid cleaners on reflector
surfaces.