NAPCO FIREWOLF FW-2-E Installation And Maintenance Instructions
NAPCO FIREWOLF FW-2-E Installation And Maintenance Instructions

NAPCO FIREWOLF FW-2-E Installation And Maintenance Instructions

Advertisement

Quick Links

Connect these detectors only to a Napco listed-compatible control panel: Series GEM-P816, GEM-P1632, GEM-
P1664, F-64, Series GEM-P3200, GEM-P9600, GEM-X255, Series GEMC-32, GEMC-96, GEMC-128, GEMC-255, Series
FL-32FACP-xxxxx, FL-96FACP-xxxxx FL-128FACP-xxxxx, FL-255FACP-xxxxx, Series XP-600, GEM-P800, GEM-P801.
Refer to the control panel installation manual for additional instructions. Smoke detectors are not to be used with
detector guards unless the combination has been evaluated and found suitable for that purpose.
Sensing Element
Supply Voltage
Current Consumption
Startup
Included Separable Base
Included Separable Head
Temperature
Operating Humidity
FW-2-H-E Conventional Photoelectric Smoke and Heat Detector and Base
Sensing Element
Heat Sensitivity Range
Supply Voltage
Current Consumption
Startup
Included Separable Base
Included Separable Head
Temperature
Operating Humidity
MODEL
Base ID
FW-2-EH6-BASE
HB-55
CAUTION
Install this and all life safety devices in accordance with applicable NFPA standards, local codes, and the authorities
having jurisdiction. Failure to follow these instructions may result in failure of the detector to initiate an alarm condition.
Napco Security Systems, Inc. and the original equipment manufacturer, are not responsible for detectors that have been
improperly installed, tested, or maintained.
333 Bayview Avenue, Amityville, New York 11701
For Sales and Repairs, (800) 645-9445
For Technical Service, (800) 645-9440 or visit us at Tech.NapcoSecurity.com
(Note: Technical Service is for security professionals only)
Publicly traded on NASDAQ
INSTALLATION AND MAINTENANCE INSTRUCTIONS
FW-2-E Conventional Photoelectric Smoke Detector and Base
Smoke
IR LED, Blue LED, Photodiode
Blue LED enhances the photoelectric smoke sensor to reduce sensitivity
to false alarms and increase sensitivity to fire conditions.
Operating Voltage Range
Maximum Voltage Ripple
Standby Current
Alarm Current
Cold Start Time
Alarm Verification Restart
Time
Current
FW-2-EH6-BASE (HB-55) 6 inch diameter base
FW-2-E-HEAD (Detector ID HD-3) Smoke Detector
UL Listed Ambient: 32F ~ 120F, Storage: -22F ~ +140F
<95%RH at 104F, <80%RH at 120F
Smoke
IR LED, Blue LED, Photodiode
Blue LED, thermistor enhance the photoelectric smoke sensor to reduce
sensitivity to false alarms and increase sensitivity to fire conditions.
Heat
Thermistor
135F
Operating Voltage Range
Maximum Voltage Ripple
Standby Current
Alarm Current
Cold Start Time
Alarm Verification Restart
Time
Current
FW-2-EH6-BASE (HB-55) 6 inch diameter base
FW-2-H-HEAD (Detector ID HD-3) Smoke and Heat Detector
UL Listed Ambient: 32F ~ 117F, Storage: -22F ~ +140F
<95%RH at 104F, <80%RH at 120F
SEPARABLE BASE SPECIFICATIONS
Alarm Current
limit by panel
150mA
@15.0 - 33.0V max
Symbol: NSSC
8 – 35VDC
8200mVAC
59A
5mA (Min), 150mA (Max)
25s (Max)
20s (Max)
160A (Max)
8 – 35VDC
8200mVAC
59A
5mA (Min), 150mA (Max)
25s (Max)
20s (Max)
160A (Max)
Mounting Box
4"Octogonal / 4"Square
WI2485ALF 01/23
PAGE 1 of 2

Advertisement

loading

Summary of Contents for NAPCO FIREWOLF FW-2-E

  • Page 1 Failure to follow these instructions may result in failure of the detector to initiate an alarm condition. Napco Security Systems, Inc. and the original equipment manufacturer, are not responsible for detectors that have been improperly installed, tested, or maintained.
  • Page 2 Cleaning Use clean, dry compressed air to remove dust from a detector, or return to Napco for service. Disassembly of the detector may result in the failure of the detector to initiate an alarm condition or initiation of a false alarm condition.