Dimplex FXPH1/42/750 Installation And Operating Instructions

Flameproof heaters

Advertisement

Quick Links

FXPH Flameproof Heaters
Models :
FXPH1/42/750, FXPH1/42/750/110, FXPH1/60/1000 - Single Element
FXPH2/42/1500, FXPH2/42/1500/110 & FXPH2/60/2000 - Double Elements
Dimensions
(millimetres)
Model(s)
Specification
Watts
FXPH1/42/750
750
FXPH1/42/750/110
750
FXPH1/60/1000
1000
FXPH2/42/1500
1500
FXPH2/42/1500/110 1500
FXPH2/60/2000
2000
THESE INSTRUCTIONS SHOULD BE READ CAREFULLY AND RETAINED FOR FUTURE REFERENCE.
IMPORTANT SAFETY ADVICE
THE HEATER SHOULD NOT BE CONNECTED UNTIL THE
INSTRUCTION LEAFLET HAS BEEN READ FULLY.
THIS PRODUCT SHOULD ONLY BE USED IN HAZARDOUS
AREAS FOR WHICH IT IS APPROVED, I.E.
USED IN ZONES 1 & 2. IT MUST NOT BE USED IN ZONE 0
WHERE POTENTIALLY EXPLOSIVE GAS MIXES WILL BE
PRESENT FOR LONG PERIODS.
THE INSTALLATION OF THESE APPLIANCES MUST ALWAYS
BE CARRIED OUT BY A SUITABLY QUALIFIED ELECTRICIAN
WITH A FULL UNDERSTANDING OF REGULATIONS :
ATEX 94/9/EC
BS EN 60079-0 :2004
BS EN 60079-1 :2004
AND BE IN ACCORDANCE WITH THE CURRENT IEE WIRING
REGULATIONS AND RELEVANT BUILDING REGULATIONS.
THE HEATER SHOULD BE CAREFULLY REMOVED FROM ITS
PACKING AND INSPECTED FOR ANY PHYSICAL DAMAGE
WHICH MAY HAVE OCCURED DURING TRANSIT.
THE HEATER SHOULD BE STORED IN A WARM DRY
ATMOSPHERE UNTIL INSTALLED.
DO NOT USE THE HEATER UNTIL IT IS CORRECTLY MOUNTED
USING THE WALL BRACKETS SUPPLIED.
THE SURFACE TEMPERATURE OF THIS APPLIANCE IS
CONSIDERABLE AND MUST BE TAKEN INTO ACCOUNT WHEN
POSITIONING THE HEATER - see Fig. 3
THE HEATER IS DESIGNED FOR USE IN A
T2 ENVIRONMENT. LIQUID IMMERSION, OR USE OUTSIDE
THESE CONDITIONS MUST NOT BE CARRIED OUT.
ALL CURRENT REGULATIONS, STANDARDS, AND
RECOMMENDATIONS MUST BE COMPLIED WITH AT THE TIME
OF INSTALLATION AND OPERATION.
THESE INSTRUCTIONS SHOULD BE READ IN CONJUNCTION
WITH BS EN 60079-0:2004. FOR REGULATIONS CONCERNING
INSTALLATION REFER TO BS EN 60079-14 AND FOR
MAINTENANCE REFER TO BS EN 60079-17.
ALWAYS ISOLATE THE HEATER FROM THE SUPPLY BEFORE
UNDERTAKING ANY MAINTENANCE WORK.
THE FLAMEPROOF TERMINAL BOX HAS ACCURATELY
MACHINED THREADS AND SURFACES. CARE MUST BE
TAKEN TO PREVENT THESE SURFACES BEING DAMAGED.
THE COVER IS SECURED WITH GRADE 8.8 SCREWS: (ISO/
R898/1 M8x30, IF SUBSITUTED, ONLY SCREWS OF THE SAME
QUALITY OR BETTER MAY BE USED). SCREWS TO BE
TIGHTENED WITH 12Nm OF TORQUE; MATING FACES OF THE
ENCLOSURE TO BE CLEAN AND UNMARKED.
CONTACT THE MANUFACTURER FOR REPLACMENT
SCREWS.
DO NOT COVER OR ENCLOSE THE HEATER .
Volts
'A'
'B'
240V
1067mm
870mm
110V
1067mm
870mm
240V
1524mm 1327mm
240V
1067mm
870mm
110V
1067mm
870mm
240V
1524mm 1327mm
IT MUST ONLY BE
II 2G EEx d IIB
Installation and Operating Instructions
246
Weight
Temp
14.7kg
T2
14.7kg
T2
16.4kg
T2
20.3kg
T2
20.3kg
T2
246
23.6kg
T2
Electrical connection
WARNING – THIS APPLIANCE MUST BE EARTHED
Verify that the electrical supply cable is sufficient for the rated loading.
Check that the incoming supply conforms to the rated supply.
The heater power circuit must be protected by a suitably rated over
current device.
The supply cables used must be suitable for hazardous area installation,
and for the temperature stated on the rating plate. They must be
connected to the heater using ATEX certified EEx d cable glands
designed for use with a female M20x1.5 parallel thread to BS ISO
262:1998.
Where the cable entry requires an adaptor, for size reduction, a suitable
ATEX certified EEx d adaptor must be used.
If the supply cable is housed in a conduit, to protect wiring, a suitable
ATEX certified EEx d adaptor must be used.
The incoming cables must be connected to the factory fitted heater
terminals provided. Do not alter any factory fitted wiring.
Before energising the heater for the first time, ensure that the insulation
resistance is at least 2 M
The heater is supplied with an earth stud, located inside the terminal box,
which must be connected to earth.
After connection check the continuity of earth connections.
General characteristics
Definitions
EEx
d
IIB T2
II 2G
08/18799/4
'A'
146
'B'
centres
FXPH 1 Range
95
centres
9.5mm dia. holes
Tapped 20mm
'A'
146
'B'
centres
FXPH 2 Range
197
centres
Tapped 20mm
9.5mm dia. holes
Ω.
Type of protection :
ATEX code:
Rated voltage:
Rated supply frequency:
Fig. 2 -
Rating Plate sample
Electrical Apparatus for potentially explosive
atmospheres.
Flameproof enclosure 'd' (BS EN 60079-1: 2004)
Equipment for use in areas in which explosive
atmospheres caused by gases, vapour, mists or
air/dust mixtures are likely to occur. Gas of
subdivision B and ignition temperature greater than
300° C.
Non-mining application, Group II Category 2 for use
in gas/vapour/mist atmospheres.
Issue 4
182
143
182
Fig. 1
143
EEx d IIB T2
II 2G
220-240V
50Hz

Advertisement

loading

Summary of Contents for Dimplex FXPH1/42/750

  • Page 1 Installation and Operating Instructions 08/18799/4 Issue 4 FXPH Flameproof Heaters Models : FXPH1/42/750, FXPH1/42/750/110, FXPH1/60/1000 - Single Element FXPH2/42/1500, FXPH2/42/1500/110 & FXPH2/60/2000 - Double Elements Dimensions (millimetres) centres FXPH 1 Range Model(s) Specification centres Watts Volts ‘A’ ‘B’ Weight Temp 9.5mm dia.