24 hour dial time switch with skipper four pole single throw

Advertisement

Quick Links

158TS11733
7/27/04
MODEL: T1472BR
24 HOUR DIAL TIME SWITCH WITH ''SKIPPER ''
FOUR POLE SINGLE THROW
40 AMP. RESISTIVE,EACH POLE 120-480V. AC;
40 AMP. INDUCTIVE TUNGSTEN OR 1000 V.A. PILOT DUTY EACH POLE 120-277 V. AC;
2 H.P. (24 FLA) - 120 V. AC; 5 H.P. (28 FLA) - 240 V. AC SINGLE PHASE
7 1/2 H.P. (28 FLA) - 208V. A.C.; 10 H.P. (28 FLA) -240V. A.C.; THREE PHASE.
INDEPENDENTLY WIRED CLOCK MOTOR: 208/277V. 60 HZ.
CLOCK MOTOR VOLTAGE AND CYCLE MUST BE AS SPECIFIED. TO
ORDER REPLACEMENT, INDICATE PART NO. (WG--) ON MOTOR COVER.
TIME
POINTER
TIME
DIAL
OFF
TRIPPER
MANUAL
LEVER

WIRING INSTRUCTIONS:

To wire switch follow diagram above.
Use solid or stranded COPPER
wire with insulation to suit installation. See gauge selection table for nor-
mal service applications. To make power connections see illustration
below. Replace front insulator before turning on electricity. Motor
voltage and cycle (Hz). must be as specified above.
MAX.
MIN.
MINIMUM
INSUL-
COPPER
LOAD
ATION
WIRE SIZE
(AMP)
TEMP(°C)
(AWG)
14
15
60
12
20
60
10
30
60
8
75
40
PROGRAMMING INSTRUCTIONS
TO SET "ON" AND "OFF" TIMES: Hold trippers against edge of CLOCK-DIAL,
pointing to time (AM or PM) when ON and OFF operations are desired, tighten
tripper screws firmly. See caution below. For additional tripper pairs on CLOCK-
DIAL order 156T1978A.
TO SET TIME-OF-DAY: Pull CLOCK-DIAL outward. Turn in either direction and
align the exact time-of-day on the CLOCK-DIAL (the time now, when switch is
being put into operation) TO TIME POINTER. DO NOT MOVE THE POINTER.
TO SKIP OPERATION(S) ON SELECTED DAY(S): Insert SKIPPING SCREW(S)
in SKIPPER WHEEL for day(s) automatic operation(s) is/are NOT required.
Tighten screws firmly. Move MANUAL LEVER to "OFF" and rotate SKIPPER
WHEEL to locate correct day-of-week opposite DAY ARROW--"YESTERDAY" if
ON/CUTOUT TRIPPER has not yet advanced wheel "TODAY" if it has.
OPERATING INSTRUCTIONS
TO OPERATE SWITCH MANUALLY: Move MANUAL LEVER below CLOCK-
DIAL left or right as indicated by arrows. This will not effect next operation.
CAUTION: TO AVOID SLOW TRIPPER ACTION FAILURE, DO NOT OPERATE
SWITCH MANUALLY NOR PLACE A TRIPPER 4 HOURS PRIOR TO ON/OFF
CUTOUT TRIPPER SWITCHING.
IN CASE OF POWER FAILURE, reset CLOCK-DIAL to proper time-of-day. See
programming instructions.
INTERMATIC INCORPORATED
158TS11733
3:58 PM
ON/CUTOUT
TRIPPER
DAY
ARROW
SKIPPER
WHEEL
SKIPPING
SCREW
75°C INSULATION MAX. MOTOR
LOAD (HP)
SINGLE PHASE
3 PHASE
120 V.
240 V.
208 V.
240 V.
3
2
3
1/2
5
2 1/2
4
1
71/2
3
5
2
10
-
5
7/12
SPRING GROVE, ILLINOIS 60081-9698
Page 1
®
CLOCK
MOTOR
A
1 2
5 6
208
277 V
B
60 HZ
SUPPLY
GROUND
SCREW
WIRING DIAGRAM
LR3730
3 4
7 8
TO
LOADS
(4PST)
PRESSURE PLATE
TERMINAL SCREW
MAKE SURE WIRE
INSULATION CLEARS
PRESSURE PLATE

Advertisement