Download Print this page
Intermatic ET8000 SERIES Owner/Installer Instruction Manual

Intermatic ET8000 SERIES Owner/Installer Instruction Manual

Electronic astronomic 7-day time switches with battery carryover

Advertisement

Quick Links

Electronic Astronomic 7-Day
Time Switches
With Battery Carryover
OWNER/INSTALLER INSTRUCTION MANUAL
ATTENTION: READ CAREFULLY BEFORE ATTEMPTING TO INSTALL YOUR INTERMATIC TIME
SWITCH. FAILURE TO COMPLY WITH INSTRUCTIONS COULD RESULT IN PERSONAL INJURY
AND/OR PROPERTY DAMAGE! RETAIN FOR FUTURE REFERENCE.
®
TIME SWITCH INPUT VOLTAGE:
120/208/240/277 V.A.C., 50/60 Hz.
POWER CONSUMPTION: 6.0 Watts Max.
CONTACT CONFIGURATION: SPST model ET8015C, DPST
model ET8215C, and SPDT model ET8115C
SWITCH RATINGS: ET8015C & ET8215C (Per Pole)
• 30 A Inductive/Resistive, 24/120/208/240/277 VAC, 60 Hz.
• 20 A Ballast 120-277 VAC 60 Hz.
• 20 A Resistive - 28 V DC
• 5 A Tungsten 120/240 VAC 60 Hz.
• 1 H.P. 120 VAC 60 Hz.
• 2 H.P. 240 VAC 60 Hz.
SWITCH RATINGS: ET8115C (NO/NC) normally closed contact
• 20A/ 10A Inductive/Resistive, 120/208/240/277 VAC, 60 Hz.
• 20A/ 10A Resistive - 28 VDC
• 6A/ 3A Ballast 120-277 VAC 60 Hz.
• 1 H.P./ 1/4 H.P. 120 VAC 60 Hz.
• 2 H.P./ 1/2 H.P. 240 VAC 60 Hz.
• 5A/ 3A, 120/240 VAC Tungsten
SET POINTS (EVENTS): 56 total (14 ON & 14 OFF plus 14
Astro ON & 14 Astro OFF). These set points can be
programmed for any or all 7 days to provide for up to 224 set
points each week.
BATTERY POWERED CLOCK OPERATION: 2 Years minimum
(Two AAA industrial grade alkaline supplied with time switch)
MIN. "ON" or "OFF" TIME: 1 minute.
MAX. "ON" or "OFF" TIME: 6 days 23 hours 59 minutes.
SHIPPING WEIGHT: 2.5 Lbs. (1.1 Kg)
CASE: NEMA 1 drawn steel; 7-3/4" (19.7 cm) high, 5" (12.7 cm)
wide, 3" (7.6 cm) deep; gray finish w/lockable spring hasp.
KNOCKOUTS: Combination 1/2 - 3/4" (one on back and each
side, two on bottom).
WIRE SIZE: AWG #10 through #18.
WARNING: Disconnect all power before installing or servicing
this time switch or its connected loads.
1. Follow all local electrical and safety codes, National Electric
Code (NEC), as well as Occupational Safety and Health Act
(OSHA).
2. If the power disconnect point is out of sight, lock it in the "OFF"
position and tag it to prevent unexpected application of power.
3. This time switch case must be grounded.
4. Do not exceed the maximum current carrying capacity of this
time switch.
5. Always replace the plastic insulator covering the terminal
before turning power "ON".
ET8000 SERIES

Specifications

General Safety Information

Advertisement

loading

Summary of Contents for Intermatic ET8000 SERIES

  • Page 1: Specifications

    Electronic Astronomic 7-Day Time Switches With Battery Carryover OWNER/INSTALLER INSTRUCTION MANUAL ATTENTION: READ CAREFULLY BEFORE ATTEMPTING TO INSTALL YOUR INTERMATIC TIME SWITCH. FAILURE TO COMPLY WITH INSTRUCTIONS COULD RESULT IN PERSONAL INJURY AND/OR PROPERTY DAMAGE! RETAIN FOR FUTURE REFERENCE. ®...
  • Page 2 The Intermatic Electronic Astronomic 7-Day Time Switch automatically switches loads according to a preset weekly schedule with up-to-the- minute accuracy. The astronomic feature provides sunset On and sunrise Off settings to eliminate the need for separate photo control devices. The independent 7-day programming provides complete flexibility for applications where load switching differs each day of the week.
  • Page 3 By pressing the [MODE] button the time switch will cycle through the menus necessary for programming the current date, time, astro zone, astro events, and timed events. Note: The Date and Time must be entered before any other menus will become available for programming. MANUAL MODE Press the [MODE] button repeatedly until MANUAL appears in the upper portion of the display.
  • Page 4: Wiring Diagrams

    IND. If within one (1) year from date of purchase, this product fails due to a defect in material or workmanship, Intermatic Incorporated will repair or replace, at its sole option, the unit free of charge. This warranty applies only to the original purchaser and is not transferable. The warranty does not apply to: (a) damage caused by accident, abuse, mishandling, dropping, acts of God, or any negligent use;...