Chromalox Type SKR radiant heaters are designed for indoor
installation only, and are to be ceiling mounted with such spacing
between heaters to project heat radiation downwards to maintain
comfort level within the radiation field.
MOUNTING (See Figure 1)
1. Layout heater locations to the desired heat affected work area.
2. Minimum spacing to walls and ceiling are —
A. One foot (12") from top of heater to ceiling.
B. Two feet (24") from side or end of heater to adjacent walls.
3. Minimum safe height above floor level for combustible mater-
ial is 6 feet (72"). However, if ceiling height permits, more
practical height is 8 feet or more to avoid high radiation inten-
sities at head level when one stands directly below heater.
© 2010 Chromalox, Inc.
Type SKR Infrared Comfort Heater
Specifications – Table A
Model
Watts
SKR-2083
0800
SKR-3113
1100
SKR-4183
1800
SKR-5253
2500
SKR-6303
3000
SKR-7363
3600
GENERAL
Before Installing
1. Open carton and remove heater at the place of installation.
Mounting clamps are in parts bag in carton.
2. Check nameplate volt and watt rating against your power sup-
ply voltage and heating requirements of your installation. This
nameplate is located on one end of the heater.
INSTALLATION
12" Min.
24"
Min.
4
(Supersedes PG417-2)
161-048460-001
OCTOBER, 2004
Single Phase Power Circuit Amps
120V
208V
240V
275V
6.7
3.9
3.4
9.2
5.3
4.6
8.7
7.5
6.6
12.00
10.50
9.1
14.40
12.50
10.90
17.30
15.00
13.10
Combustible Surfaces
B
3/8" Conduit
2-3/4"
Protective Grille
A
72" Min.
SK
PG417-3
Dimensions (In.)
480V
A
B
3
7
24
/
22
/
8
8
30
5
/
29
1
/
8
8
5
1
46
/
45
/
8
8
5.3
61
3
/
59
7
/
8
8
3
1
6.3
73
/
72
/
4
4
7.5
85
3
/
84
1
/
4
4
3-11/16"
24"
Min.
Maximum
Radiation
Within
60° Included
Angle
Figure 1

Advertisement

loading

Summary of Contents for Chromalox PG417-3

  • Page 1 Type SKR Infrared Comfort Heater Chromalox Type SKR radiant heaters are designed for indoor installation only, and are to be ceiling mounted with such spacing between heaters to project heat radiation downwards to maintain comfort level within the radiation field.
  • Page 2 OPERATION 1. Although most heaters operate at full capacity, it is possible to reduce heating capacity with an Input Controller (Chromalox Type VC or VCR — check factory) which can be manually set to turn on heaters from 4% to 100% of a 15 or 30 second operating cycle, providing, in effect, infinite control of heater output.
  • Page 3 The reflector is aluminum. DO NOT use alkali cleaners since alkalies will dull reflector. Mild non-alkaline cleaners, such as used for scouring kitchen sinks, amy be used. Reflectors are replaceable and may be purchased from Chromalox. RENEWAL PARTS IDENTIFICATION Figure 6...
  • Page 4 152-017859-006 234-013411-038 134-017852-003 (2) 175-048143-022 175-048143-026 175-048142-224 Note: Part numbers suffixed by a number in ( ) indicates the quantity of the same part number used. Please refer to the Chromalox limited warranty applicable to this product at http://www.chromalox.com/customer-service/policies/termsofsale.aspx. RENEWAL PARTS IDENTIFICATION...

This manual is also suitable for:

Skr-2083Skr-3113Skr-4183Skr-5253Skr-6303Skr-7363