Toshiba Tosvert VF-AS1 Instruction Manual

Toshiba Tosvert VF-AS1 Instruction Manual

The new high-performance inverter
Hide thumbs Also See for Tosvert VF-AS1:
Table of Contents

Advertisement

Instruction Manual

The new
high-performance inverter
TOSVERT
200V class
400V class 0.75 500kW
1.Make sure that this instruction manual is delivered to the end user of
the inverter unit.
2.Read this manual before installing or operating the inverter unit, and
store it in a safe place for reference.
AS1
VF-
TM
0.4 75kW
NOTICE
E6581442 2
I
Safety
precautions
II II
Introduction
Contents
1
Read first
2
Connection
equipment
3
Operations
4
Searching and
setting parameters
5
Basic
parameters
6
Extended
parameters
7
Operation with
external signal
8
Monitoring the
operation status
9
Measures to
satisfy the
standards
10 10
Selection of
peripheral
devices
11 11
Table of
parameters
12 12
Specifications
13 13
Before making a
service call
14 14
Inspection and
maintenance
15 15
Warranty
16 16
Disposal of
the inverter

Advertisement

Table of Contents
loading

Summary of Contents for Toshiba Tosvert VF-AS1

  • Page 1: Instruction Manual

    E6581442 2 Safety precautions II II Introduction Contents Read first Connection Instruction Manual equipment Operations The new Searching and setting parameters high-performance inverter Basic parameters TOSVERT Extended parameters Operation with external signal Monitoring the operation status Measures to satisfy the standards 10 10 Selection of...
  • Page 2: Safety Precautions

    (Use in other than properly applied three-phase induction motors may cause an accident.) When the inverter is used to control the operation of a permanent magnet motor, a combination test must be conducted in advance. For details on the test, contact your Toshiba distributer.
  • Page 3: General Operation

    If the equipment is continued to operate in such a state, the result may be fire. Mandatory Call your Toshiba distributor for repairs. • Always turn power off if the inverter is not used for long periods of time since there is a possibility of malfunction caused by leaks, dust and other material.
  • Page 4 • Do not install or operate the inverter if it is damaged or any component is missing. This can result in electric shock or fire. Please consult your Toshiba distributor for repairs. • Do not place any inflammable objects nearby. If a flame is emitted due to malfunction, it 1.4.4...
  • Page 5 E6581442  Wiring Warning Reference • Do not connect input power to the output (motor side) terminals (U/T1,V/T2,W/T3). That will destroy the inverter and may result in fire. • Do not connect resistors to the DC terminals (between PA/+ and PC/-, or between PO and PC/-).
  • Page 6 E6581442  Operations Warning Reference • Do not touch inverter terminals when electrical power is applied to the inverter even if the motor is stopped. Touching the inverter terminals while power is connected to it may result in electric shock. •...
  • Page 7: Maintenance And Inspection

    • Never replace any part by yourself. 14.2 This could be a cause of electric shock, fire and bodily injury. To replace parts, call your Toshiba distributor. Prohibited • The equipment must be inspected frequently. If the equipment is not inspected and maintained, errors and malfunctions may not be discovered which could lead to accidents.
  • Page 8 E6581442 II. Introduction Thank you for your purchase of the Toshiba “TOSVERT VF-AS1” industrial inverter. This instruction manual is intended for inverters with CPU version 150 or later. The CPU version will be frequently upgraded.
  • Page 9: Table Of Contents

    E6581442 - Contents - I. Safety precautions ······················································································································································ I I. Introduction ······························································································································································· Read first····························································································································································· Check the product ········································································································································ Contents of the product code ······················································································································· Structure of the main body ··························································································································· 1.3.1 Names and functions ···························································································································· 1.3.2 Detaching the cover ······························································································································ 1.3.3 Grounding capacitor switching method ·································································································...
  • Page 10 E6581442 5.17 PWM carrier frequency ································································································································· E-31 5.18 Trip-less intensification ································································································································· E-32 5.18.1 Auto-restart (Restart during coasting)···································································································· E-32 5.18.2 Regenerative power ride-through control/Deceleration stop during power failure/ Synchronized acceleration/deceleration······································································································· E-33 5.19 Dynamic (regenerative) braking - For abrupt motor stop ·············································································· E-36 5.20 Standard default setting ································································································································...
  • Page 11 E6581442 6.23 Increasing the motor output torque further in low speed range ···································································· F-42 6.24 Torque control ·············································································································································· F-43 6.24.1 Torque command ·································································································································· F-43 6.24.2 Speed limits in torque control mode ······································································································ F-43 6.24.3 Selection of tension torque bias input and load sharing gain input ······················································· F-44 6.25 Torque limit···················································································································································...
  • Page 12 E6581442 6.36.5 Canceling the operation command ········································································································ F-76 6.36.6 Selection of operation panel stop pattern ······························································································ F-76 6.36.7 Setting of a torque command in panel operation mode ········································································· F-76 6.36.8 Torque-related parameters for panel operation······················································································ F-77 6.37 Tracing functions··········································································································································· F-77 6.38 Integrating wattmeter ····································································································································...
  • Page 13 E6581442 Table of parameters············································································································································· Specifications ······················································································································································ 12.1 Models and their standard specifications ····································································································· 12.2 Outside dimensions and weight ··················································································································· Before making a service call - Trip information and remedies ············································································· 13.1 Trip causes/warnings and remedies············································································································· 13.2 Method of resetting causes of trip ················································································································ 13.3 If the motor does not run while no trip message is displayed.······································································...
  • Page 14: Read First

    E6581442 1. Read first Check the product Before using the product you have purchased, check to make sure that it is exactly what you ordered. Caution Use an inverter that conforms to the specifications of the power supply and three-phase induction motor being used.
  • Page 15: Structure Of The Main Body

    E6581442 1. 3 Structure of the main body 1.3.1 Names and functions 1) Outside view Control circuit Operation panel terminal cover Be sure to close the cover before starting the operation to prevent persons from touching the terminal in error. Main circuit terminal cover Inverter type and...
  • Page 16 E6581442  Operation panel Up key RUN lamp EASY key [Note 1] EASY key lamp % lamp Lights when an ON Lights when the unit Press this key to control Lights when the EASY command is issued but no is %. the function assigned key is enabled.
  • Page 17 E6581442 2) Main circuit terminal VFAS1-2004PL~2015PL VFAS1-4007PL~4022PL Shorting-bar M4 screw Grounding capacitor switching switch Grounding terminal (M5 screw) Screw hole for EMC plate VFAS1-2022PL, 2037PL VFAS1-4037PL Shorting-bar M4 screw Grounding capacitor switching switch Grounding terminal (M5 screw) Screw hole for EMC plate VFAS1-2055PL VFAS1-4055PL, 4075PL Shorting-bar...
  • Page 18 E6581442 VFAS1-2075PL VFAS1-4110PL Shorting-bar M5 screw Grounding capacitor switching switch Grounding terminal (M5 screw) Screw hole for EMC plate VFAS1-2110PM, 2150PM VFAS1-4150PL, 4185PL Grounding capacitor switching switch Shorting-bar M6 screw Grounding terminal (M5 screw) Screw hole for EMC plate VFAS1-2185PM, 2220PM VFAS1-4220PL M8 screw Shorting-bar...
  • Page 19 E6581442 VFAS1-4300PL, 4370PL Grounding capacitor switching switch M8 screw Shorting-bar Use crimped ring lugs of appropriate size on input and output cables. Attach to the top side of the terminal block only. Do not place wires Grounding terminal in the hole of the (M8 screw) terminal block.
  • Page 20 E6581442 VFAS1-2750P VFAS1-4110KPC M12 screw M10 screw Grounding capacitor switching bar M4 screw M8 screw Grounding terminal(M10 screw) VFAS1-4132KPC Grounding capacitor M12 screw switching screw M10 screw M10 screw M4 screw Grounding terminal(M10 screw) VFAS1-4160KPC Grounding capacitor switching screw M12 screw M12 screw M10 screw M4 screw...
  • Page 21 E6581442 VFAS1-4200KPC~4280KPC M12 screw Grounding capacitor switching screw M12 screw Grounding terminal M4 screw (M12 screw) VFAS1-4355KPC, 4400KPC Grounding M12 screw capacitor switching screw M4 screw M12 screw Grounding terminal (M12 screw) VFAS1-4500KPC Grounding capacitor M12 screw switching screw M4 screw M12 screw Grounding terminal (M12 screw)
  • Page 22: Detaching The Cover

    E6581442 3) Control circuit terminal block The control circuit terminal block is common to all equipment. 4-wire RS485 PWR-P24/PLC Shorting bar connector Control circuit terminal block screw size: M3  For details on all terminal functions, refer to Section 2.3.2. 1.3.2 Detaching the cover ...
  • Page 23 E6581442 For 200V/0.4kW to 200V/15kW models and 400V/0.75kW to 400V/18.5kW models, cut off the tabs (part A in the figure below) on the main circuit terminal cover if necessary for connecting the cables from the power supply. 200V-0.4kW~3.7/4.0kW 200V-5.5kW~15kW 400V-0.75kW~3.7/4.0kW 400V-5.5kW~18.5kW ...
  • Page 24 E6581442  Charge lamp This lamp is lit when a high voltage remains in the inverter. When removing the main circuit terminal cover or opening the front cover, be sure to check that this lamp is off and follow the instructions about wiring on page 4. The mounting position of the charge lamp varies from model to model.
  • Page 25: Grounding Capacitor Switching Method

    E6581442 1.3.3 Grounding capacitor switching method The inverter is grounded through a capacitor. The leakage current from the inverter can be reduced using the selector switch, switching bar or switching screw (depending on the model) on the main circuit terminal board. This switching device is used to detach the capacitor from the grounding circuit or to reduce its capacitance.
  • Page 26 E6581442 200V 18.5~22kW 400V 22kW Part A 200V/400V class Grounding capacitor switching switch Only 400V class 400V 30kW、37kW Part A Grounding capacitor switching switch 200V 30kW~45kW 400V 45kW~75kW Part A Grounding capacitor switching switch A-13...
  • Page 27 E6581442  200V/55kW models and larger 400V/90kW, 110kW models: Grounding capacitor switching bar Large To change the capacitance from Small to Large, secure the upper end of the grounding capacitor switching bar to the inverter Small chassis, with a screw. To change the capacitance from Large Large to Small, remove the screw...
  • Page 28 E6581442 «200kW~280kW» To change the capacitance from Large Small Small to Large, fix to part A shown in the figure on the left with the grounding capacitor switching screw. To change the capacitance from Large to Small, fix to part B shown Large Small in the figure on the left with the grounding capacitor switching...
  • Page 29: Installing The Dc Reactor

    E6581442 1.3.4 Installing the DC reactor  How to install (Example: VFAS1-4160KPC) Reactor case Reactor unit Front cover Mount the reactor case on an inner wall Remove the front cover. of the cabinet and secure the reactor unit to the case with screws. Top panel Cover Front panel...
  • Page 30: Notes On The Application

    E6581442  Example of wiring of each model «VFAS1-4900PC~4132KPC» «VFAS1-4160KPC~4280KPC» «VFAS1-2550P, 2750P» PA/+ Earth cable Earth cable PA/+ PA/+ «VFAS1-4355KPC~4500KPC» PO.1 PA/+ PO.2 Earth cable Notes on the application 1.4.1 Motors Keep the following in mind when using the VF-AS1 to drive a motor. Caution Use an inverter that conforms to the specifications of power supply and three-phase induction motor being used.
  • Page 31 E6581442 High-speed operation at and above 50Hz/60Hz (rated frequency) Operating at frequencies greater than 50Hz/60Hz will increase noise and vibration. There is also a possibility that such operation will exceed the motor's mechanical strength under these conditions and the bearing limits. You should verify with the motor's manufacturer operating.
  • Page 32: Inverters

    Circuit configuration 2 uses low-speed signal OUT1 to turn on and off the brake. Turning the brake on and off with a low-speed detection (OUT1 function) may be better in such applications as elevators. Please confer with your Toshiba distributor before designing the system. Measures to protect motors against surge voltages In a system in which a 400V-class inverter is used to control the operation of a motor, very high surge voltages may be produced.
  • Page 33: What To Do About The Leak Current

    If the sensors and CRT are affected, it can be remedied by reducing the PWM carrier frequency described in 1 above, but if this cannot be remedied because of the increase in the motor's electric magnetic noise, please consult with your Toshiba distributor. * Cautions for applying models with a built-in noise filter.
  • Page 34 E6581442 (2) Affects of leakage current across supply lines Thermal relay inverter Power supply Leakage current path across wires (1) Thermal relays The high frequency component of current leaking into electrostatic capacity between inverter output wires will increase the effective current values and make externally connected thermal relays operate improperly. If the motor cables are more than 50m long, external thermal relay may operate improperly with models having motors of low rated current, especially the 400V class low capacity (3.7/4.0kW or less) models, because the leakage current will be high in proportion to the motor rating.
  • Page 35: Installation

    E6581442 1.4.4 Installation  Installation environment The VF-AS1 Inverter is an electronic control instrument. Take full consideration to installing it in the proper operating environment. Warning • Do not place any inflammable substances near the VF-AS1 Inverter. If an accident occurs in which flames are emitted, this could lead to fire. Prohibited •...
  • Page 36 Operation cannot be stopped immediately by the inverter alone, thus risking an accident or injury. • All options used must be those specified by Toshiba. The use of any other option may result in an accident.
  • Page 37 Note2: Do not install in any location where there is high humidity or high temperatures and where there are large amounts of dust and metallic fragments. If you are going to install the equipment in any area that presents a potential problem, please consult with your Toshiba distributor before doing so.  Current reduction curve Depending on the way in which the inverter is installed, the ambient temperature and the carrier frequency setting, you may need to reduce the inverter’s continuous output current.
  • Page 38 E6581442 200V 0.75 、 2.2 、 3.7 、 15kW ( See lines shown in --- for 15kW ) 400V 7.5 、 15 kW ( See lines shown in --- for 7.5kW and 15kW ) ● Side-by-side installation ( without top cover ) ●...
  • Page 39 E6581442 200V 18.5kW ● Side-by-side installation ( without top cover ) ● Standard installation Ambient temperature Ambient temperature 110% 110% ith top cover 40℃:W 40℃:F631=1 100% 100% F631=1 90% 90% ith top cover 50℃:W 50℃ (F631=0) 80% 80% (F631=0) 70% 70%...
  • Page 40 E6581442 400V 37 、 75kW ● Side-by-side installation ( without top cover ) ● Standard installation Ambient temperature Ambient temperature 110% 110% ith top cover 40℃:W 40℃:F631=1 F631=1 100% 100% 90% 90% ith top cover 50℃ (F631=0) 50℃:W 80% 80% (F631=0) 70%...
  • Page 41 E6581442  Calorific values of the inverter and the required ventilation The energy loss when the inverter converts power from AC to DC and then back to AC is about 5%. In order to suppress the rise in temperature inside the cabinet when this loss becomes heat loss, the interior of the cabinet must be ventilated and cooled.
  • Page 42 E6581442  Panel designing taking into consideration the effects of noise The inverter generates high frequency noise. When designing the control panel setup, consideration must be given to that noise. Examples of measures are given below. • Wire so that the main circuit wires and the control circuit wires are separated. Do not place them in the same conduit, do not run them parallel, and do not bundle them.
  • Page 43: Connection Equipment

    E6581442 2. Connection equipment Warning • Never disassemble, modify or repair. This can result in electric shock, fire and injury. For repairs, call your sales agency. Disassembly prohibited • Don't stick your fingers into openings such as cable wiring hole and cooling fan covers. This can result in electric shock or other injury.
  • Page 44 E6581442 Caution • Do not attach devices with built-in capacitors (such as noise filters or surge absorber) to the output (motor side) terminal. This could cause a fire. Prohibited  Preventing radio noise To prevent electrical interference such as radio noise, separately bundle wires to the main circuit's power terminals (R/L1, S/L2, T/L3) and wires to the motor terminals (U/T1, V/T2, W/T3).
  • Page 45: Standard Connections

    E6581442 • Refer to the table in Section 10.1 for wire sizes. • The length of the main circuit wire in Section 10.1 should be no longer than 30m. If the wire is longer than 30m, the wire size (diameter) must be increased. •...
  • Page 46 *6: If you want to use a DC power supply to operate the inverter (200V: 18.5kW and above, 400V: 22kW and above), be sure to contact your Toshiba distributor, because an inrush current limiting circuit is required in such a case.
  • Page 47 *2: To supply a DC power, connect the cables to the PA/+ and PC/- terminals. *3: If you want to use a DC power supply to operate the inverter, be sure to contact your Toshiba distributor, because an inrush current limiting circuit is required in such a case.
  • Page 48 *2: To supply a DC power, connect the cables to the PA/+ and PC/- terminals. *3: If you want to use a DC power supply to operate the inverter, be sure to contact your Toshiba distributor, because an inrush current limiting circuit is required in such a case.
  • Page 49 *6: If you want to use a DC power supply to operate the inverter (200V: 18.5kW and above, 400V: 22kW and above), be sure to contact your Toshiba distributor, because an inrush current limiting circuit is required in such a case.
  • Page 50 *2: To supply a DC power, connect the cables to the PA/+ and PC/- terminals. *3: If you want to use a DC power supply to operate the inverter, be sure to contact your Toshiba distributor, because an inrush current limiting circuit is required in such a case.
  • Page 51 *2: To supply a DC power, connect the cables to the PA/+ and PC/- terminals. *3: If you want to use a DC power supply to operate the inverter, be sure to contact your Toshiba distributor, because an inrush current limiting circuit is required in such a case.
  • Page 52: Description Of Terminals

    E6581442 Description of terminals 2.3.1 Main circuit terminals This diagram shows an example of wiring of the main circuit. Use options if necessary.  Power supply and motor connections  VF-AS1  Connect the power Connect the motor Power supply cables to RL1, S/L2, cables to U/T1, V/T2 and T/L3.
  • Page 53: Control Circuit Terminal Block

    E6581442 2.3.2 Control circuit terminal block The control circuit terminal block is common to all equipment. Color of a label is yellow. PWR-P24/PLC Shorting bar  How to set input terminal function, refer to section 7. Note:Control circuit terminal block is different between the previous version of CPU(Up to Ver.124) and the present version of CPU(above Ver.130).If it was changed into different type, Inverter doesn't work correctly.
  • Page 54 E6581442 Terminal Input/ Electrical Function (Sink Source logic) Inverter internal circuits symbol output specifications If P24/PLC and PWR are short-circuited, the P24/PLC motor is put into a standby state. And if the SINK SOURCE circuit between them is opened, the motor Regardless of the coasts and stops.
  • Page 55 E6581442 Terminal Input/ Electrical Function (Sink Source logic) Inverter internal circuits symbol output specifications Common Analog input/output signal equipotential (0V) to input/ terminal for the control circuit. output Voltage:24Vdc±10% Use a power supply DC power input terminal for operating the with a current rating of 1.05A or more.
  • Page 56 E6581442  Sink logic/source logic (When inverter's internal power supply is used) Current flowing out turns control input terminals on. These are called sink logic terminals. The method generally used in Europe is source logic in which current flowing into the input terminal turns it on. Sink logic terminals and source logic terminals are sometimes referred to as negative logic terminals and positive logic terminals, respectively.
  • Page 57 E6581442  Sink logic/source logic (When an external power supply is used) The P24/PLC terminal is used to connect to an external power supply or to insulate a terminal from other input or output terminals. Use the slide switch SW1 to switch between sink logic and source logic configurations. Note that the PWR terminal is designed for safety purposes to work always in source logic mode, regardless of the setting of SW1.
  • Page 58 E6581442 2.3.3 RS485 communication connector The VF-AS1 is equipped with two connectors: a two-wire RS485 connector (on the operation panel) and a four-wire RS485 connector. The two wire RS485 connector is used to connect an external option (such as remote keypad or computer) to the inverter.
  • Page 59: Operations

    E6581442 3. Operations This section explains the basics of operation of the inverter. Check the following again before starting operation. 1) Are all wires and cables connected correctly? 2) Does the supply voltage agree with the rated input voltage? Warning •...
  • Page 60: Setting/Monitor Modes

    E6581442 Setting/monitor modes The VF-AS1 has the following three setting/monitor modes. Standard monitor mode The standard inverter mode. This mode is enabled when inverter power goes on. This mode is for monitoring the output frequency and setting the frequency reference value. If also displays information about status alarms during running and trips.
  • Page 61: Simplified Operation Of The Vf-As1

    E6581442 Simplified operation of the VF-AS1 On of three operation modes can be selected: terminal board operation, operation panel and combination of both.  For other operation modes, refer to Section 5.5. Terminal board mode :Operation by means of external signals Operation panel mode :Operation by pressing keys on the operation panel Operation panel + terminal board mode...
  • Page 62 E6581442  Frequency setting 1) Setting the frequency using potentiometer Potentiometer The operation frequency by potentiometer (1~10kΩ- 1/4W ) for setting  Refer to Section 7.3 for details of adjustment. :Frequency settings 60Hz RR/S4 With potentiometer Frequency [Parameter setting] Set the “basic parameter frequency setting mode selection 1” parameter  to  . (There is no need to set this parameter before the first use after purchase.) 2) Setting the frequency using input voltage (0~10V) Voltage signal...
  • Page 63 E6581442 4) Setting the frequency using input voltage (0~10Vdc) Voltage signal Voltage signal (0~10V) for setting the operation frequency  Refer to Section 7.3 for details of adjustment. VI/II :Voltage signal 0-10Vdc 60Hz Frequency 0Vdc 10Vdc [Parameter setting] Set the “extended parameter analog input VI/II voltage/current switching” parameter ...
  • Page 64 E6581442 Key operated LED display Operation Press either the key or the key to change to the parameter  group .  Press the ENTER key to display the first extended parameter .  Press the key to change to . Pressing the ENTER key allows the reading of parameter setting.
  • Page 65: Panel Operation

    E6581442 3.2.2 Panel operation This section describes how to start/stop the motor, and set the operation frequency with the operating panel. :Set frequency Example of basic connection MCCB Motor :Motor starts R/L1 U/T1 Power S/L2 V/T2 :Stop the motor supply STOP T/L3 W/T3...
  • Page 66 E6581442  Example of operation panel control Key operated LED display Operation The running frequency is displayed. (When standard monitor display  selection = [Output frequency]) Set the operation frequency.  Press the ENTER key to save the operation frequency. and the ...
  • Page 67: Searching And Setting Parameters

    E6581442 4. Searching and setting parameters There are two types of setting mode quick mode and standard setting mode. Quick mode : EASY key: ON Eight frequently used basic parameters are just displayed (Factory default position). Quick mode (EASY) Title Function ...
  • Page 68: How To Set Parameters

    E6581442 How to set parameters This section explains how to set parameters, while showing how parameters are organized in each setting monitor mode. 4.1.1 Setting parameters in the selected quick mode To place the inverter in this mode, press the key (the LED lights up), and then press the key.
  • Page 69: Setting Parameters In The Standard Setting Mode

    E6581442 4.1.2 Setting parameters in the standard setting mode Press the key to place the inverter in this mode. MODE  How to set basic parameters Selects parameter to be changed. (Press the key.) Reads the programmed parameter setting. (Press the key.) Change the parameter value.
  • Page 70: Functions Useful In Searching For A Parameter Or Changing A Parameter Setting

    E6581442  Adjustment range and display of parameters : An attempt has been made to assign a value that is higher than the programmable range. Or, as a result of changing other parameters, the programmed value of the parameter that is now selected exceeds the upper limit....
  • Page 71: Basic Parameters

    E6581442 5. Basic parameters This parameter is a basic parameter for the operation of the inverter.  Refer to Section 11, Table of parameters. History function  : History function • Function Automatically searches for 5 latest parameters that are programmed with values different from the standard default setting and displays them in the .
  • Page 72: Setting Acceleration/Deceleration Time

    E6581442 Setting acceleration/deceleration time  : Automatic acceleration/deceleration  : Acceleration time 1  : Deceleration time 1 • Function 1) For acceleration time 1  programs the time that it takes for the inverter output frequency to go from 0Hz to maximum frequency .
  • Page 73: Manually Setting Acceleration/Deceleration Time

    E6581442 5.2.2 Manually setting acceleration/deceleration time Set acceleration time from 0 (Hz) operation frequency to maximum frequency  and deceleration time as the time when operation frequency goes from maximum frequency  to 0 (Hz). Output frequency [Hz]  = (Manual setting) Time [s] ...
  • Page 74 E6581442 1) Increasing torque automatically according to the load Set the automatic torque boost = (automatic torque boost+auto-tuning 1) Automatic torque boost = detects load current in all speed ranges and automatically adjusts voltage output from inverter. This gives steady torque for stable runs. Note 1: The same characteristic can be obtained by setting the V/f control mode selection parameter ...
  • Page 75: Setting Parameters By Operating Method

    E6581442 Setting parameters by operating method  : Automatic function setting • Function Automatically programs all parameters (parameters described below) related to the functions by selecting the inverter's operating method. The major functions can be programmed simply. [Parameter setting] Title Function Adjustment range Default setting...
  • Page 76: Selection Of Operation Mode

    E6581442 Frequency setting with operation panel and operation with terminal board (=) This setting is used to set the frequency using the operation panel and to perform operation control using the terminal board. Use the keys to set the frequency. In sink logic mode: PWR-P24/PLC ON: Standby (ON (short-circuited) by default), F-CC ON: Forward run, R-CC ON: Reverse run.
  • Page 77 E6581442 <Frequency setting mode selection> [Parameter setting] Title Function Adjustment range Default setting :VI/II (voltage/current input) :RR/S4 (potentiometer/voltage input) :RX (voltage input) :Operation panel input enabled (including LED/LCD option input) :2-wire RS485 communication input :4-wire RS485 communication input Frequency setting mode ...
  • Page 78 E6581442 The functions assigned to the following control input terminals (contact input:  Refer to Section 7.2) are always activated regardless of the settings of the command mode selection  and frequency setting mode selection 1 . • Reset terminal (default setting: RES, valid only for tripping) •...
  • Page 79 E6581442 2) Setting the run and stop frequencies (forward run, reverse run and coast stop) by means of external signals and setting the operation frequency with the operation panel Title Function Setting value Run/stop : ON/OFF of terminals F-CC/R-CC (Standby: connection of terminals ...
  • Page 80 E6581442 4) Setting the run, stop and operation frequencies (forward run, reverse run and coast stop) by means of external signals (default setting) Title Function Setting value Run/stop :ON/OFF of terminals F-CC/R-CC Command mode Speed command :External signal input  :(Terminal input) selection (1) VI/II terminal: 0~+10Vdc...
  • Page 81: Selecting Control Mode

    E6581442 Selecting control mode  : V/f control mode selection • Function With “VF-AS1,” the V/f controls shown below can be selected. 0: Constant torque characteristics 1: Voltage decrease curve 2: Automatic torque boost (*1) 3: Sensorless vector control 1 (*1) 4: Sensorless vector control 2 5: V/f 5-point setting 6: PM control (*2)
  • Page 82 E6581442 2) Decreasing output voltage Setting of V/f control mode selection = (Voltage decrease curve) This is appropriate for load characteristics of such things as fans, pumps and blowers in which the torque in relation to load rotation speed is proportional to its square. Base frequency voltage 1 ...
  • Page 83 Setting of V/f control mode selection =,  (Sensorless vector control 1, 2) Using sensorless vector control with a Toshiba standard motor will provide the highest torque at the lowest speed ranges. The effects obtained through the use of sensorless vector control are described below.
  • Page 84 Permanent magnet motors (PM motors) that are light, small in size and highly efficient, as compared to induction motors, can be operated in sensorless operation mode. Note that this feature can be used only for specific motors. For more information, contact your Toshiba distributor. 7) Operating the motor at periodic speeds by means of a motor speed sensor Setting for V/f control mode selection =...
  • Page 85 30m, be sure to perform the auto-tuning (=) mentioned above, even when using a standard motor recommended by Toshiba. 2) The sensorless vector control exerts its characteristics effectively in frequency areas below the base frequency ().
  • Page 86: Manual Torque Boost-Increasing Torque Boost At Low Speeds

    E6581442 Manual torque boost–increasing torque boost at low speeds  : Manual torque boost 1 • Function If torque is inadequate at low speeds, increase torque by raising the torque boost rate with this parameter.  Base frequency voltage 1 ...
  • Page 87: Maximum Frequency

    E6581442 Maximum frequency  : Maximum frequency • Function 1) Programs the range of frequencies output by the inverter (maximum output values). 2) This frequency is used as the reference for acceleration/deceleration time. Output frequency [Hz] In case of =80Hz •...
  • Page 88: Setting Frequency Command Characteristics

    E6581442 5.11 Setting frequency command characteristics  ~  ,  : VI/II point setting  ~  ,  : RR/S4 point setting  ~  : RX point setting  ~  :  ~  : It sets up, when using the optional circuit board. ...
  • Page 89 E6581442 Example of preset speed contact input signal : ON –: OFF (Speed commands other than preset speed commands are valid when all are OFF) Preset speed Terminal         S1-CC – – – –...
  • Page 90 E6581442 Below is an example of 7-step speed operation.  Output frequency [Hz]       Time F-CC S1-CC S2-CC S3-CC Example of 7-step speed operation 4) Setting the operation mode An operation mode can be selected for each preset speed. Operation mode setting Title Function...
  • Page 91: Selecting Forward And Reverse Runs (Operation Panel Only

    E6581442 5.13 Selecting forward and reverse runs (operation panel only)  : Forward/reverse run selection • Function Program the direction of rotation of the motor when the running and stopping are made using the RUN key and STOP key on the operation panel. Valid when ...
  • Page 92: Setting The Electronic Thermal

    E6581442 5.14 Setting the electronic thermal  : Motor electronic thermal protection level 1  : Electronic thermal protection characteristic selection  : OL reduction starting frequency  : Motor 150%-overload time limit  : Temperature detection • Function This parameter allows selection of the appropriate electronic thermal protection characteristics according to the particular rating and characteristics of the motor.
  • Page 93 Note: The motor overload starting level is fixed at 30Hz. If necessary, set  to , ,  or . (See the following section.) Even if the inverter is used with a Toshiba standard motor, the load may need to be reduced at frequencies of 30Hz and below in some cases.
  • Page 94 E6581442  Setting of motor electronic thermal protection level 1  If the capacity of the motor is smaller than the capacity of the inverter, or the rated current of the motor is smaller than the rated current of the inverter, adjust the electronic thermal protection level 1  so that it fits the motor's rated current.
  • Page 95 E6581442 3) Inverter overload characteristics Set to protect the inverter unit. Cannot be turned off by parameter setting. The inverter has two overload detecting functions, which can be switched from one to another using parameter  (temperature detection). [Parameter setting] Title Function Adjustment range...
  • Page 96: Changing The Display Unit % To A (Ampere)/V (Volt

    E6581442 5.15 Changing the display unit % to A (ampere)/V (volt)   : Current/voltage unit selection • Function These parameters are used to change the unit of monitor display. % A (ampere)/V (volt) Current 100% = Inverter’s rated current 200V-class voltage 100% = 200Vac 400V-class voltage 100% = 400Vac ...
  • Page 97: Meter Setting And Adjustment

    E6581442  5.16 Meter setting and adjustment   : FM terminal meter selection   : FM output filter   : FM terminal meter adjustment   : AM terminal meter   : Constant at the time of filtering selection...
  • Page 98 E6581442 [Terminal FM-related parameters] Adjustment Title Function Adjustment range Default setting level  :  Output frequency  :  Frequency command value  :  Output current  :  Input voltage (DC detection)  :  Output voltage ...
  • Page 99 E6581442 [Terminal AM-related parameters] Title Function Adjustment range Default setting AM terminal meter selection Same as  (  :AM output disabled)    AM terminal meter adjustment – AM output gradient  :Negative gradient (downward-sloping),   characteristic ...
  • Page 100 E6581442 Meter adjustment Fixed output 1 Fixed output 2 Fixed output 3 Adjustment level  (  ) =  (  ) =  (  ) =  *2  185% 100% 150% 250% 135% 100% *1: The 100% value of input/output power is the product of 3 ×200V (400V) ×...
  • Page 101: Pwm Carrier Frequency

    E6581442  Gradient bias adjustment of analog monitor output Here is an example of the adjustment of output from 0-20mA  20-0mA, 4-20mA using the FM terminal.   =  ,  =   =  ,  =  (mA) (mA) 100%...
  • Page 102: Trip-Less Intensification

    E6581442 Note 2: If  is set at 2.0kHz or above, it cannot be decreased below 2.0kHz during operation. Changes made to decrease  below 2.0kHz take effect when operation is restarted after it is stopped. Note 3: If  is 1.9kHz or less, you cannot change the setting at 2.0kHz or more. Changes made to increase  to 2.0kHz or above take effect immediately.
  • Page 103: Regenerative Power Ride-Through Control/Deceleration Stop During Power Failure/Synchronized Acceleration/Deceleration

    E6581442 2) Restarting motor during coasting (Motor speed search function) Motor speed F-CC S3 (ST operation standby signal) -CC =: This function operates after the S3-CC terminal connection has been opened first and then connected again. Title Function Adjustment range Default setting Setting value :Disabled...
  • Page 104 E6581442 [Parameter setting] Title Function Adjustment range Default setting :Disabled :Power ride-through : Deceleration stop during power failure: Regenerative power ride-through :Synchronized deceleration/acceleration   control selection (synchronized acceleration/deceleration signal) :Synchronized deceleration/acceleration (synchronized acceleration/deceleration signal+power failure) Non-stop control time/Deceleration ~ sec. ...
  • Page 105 E6581442  An example of setting when = Input voltage Motor speed Time Deceleration stop • Even after the recovery from an input power failure, the motor continues slowing down to a stop. If the voltage in the inverter main circuit falls below a certain level, however, control will be stopped and the motor will coast. •...
  • Page 106: Dynamic (Regenerative) Braking - For Abrupt Motor Stop

    Note 1: The time set using  is the time for which the resistor sustains an overload. (Enter the time elapsed before the inverter trips if a load 10 times as large as the allowable continuous braking resistance specified using  is applied.) There is no need to change resistance settings recommended by Toshiba (except DGP resistance setting).
  • Page 107 E6581442 All 200V VF-AS1 and 400V VF-AS1 with ratings of up to 160kW have built-in dynamic braking transistors as standard equipment. If the rating of your inverter falls within this range, connect the resistor, as shown in Figure a) below or Figure b) on the next page.
  • Page 108 E6581442 b) When a using braking resistor without thermal fuse An external braking resistor (optional) * If no power supply is provided TH - Ry for the control circuit MCCB PA/+ Motor Three-phase R/L1 U/T1 main circuit S/L2 V/T2 power supply W/T3 T/L3 Depression...
  • Page 109 E6581442 c) Capacities of 400V-200kW and above TH - Ry An external braking resistor (optional) * If no power supply is Dynamic braking unit (optional) provided for the control circuit MCCB Motor R/L1 Three-phase U/T1 main circuit S/L2 V/T2 power supply T/L3 W/T3 Depression...
  • Page 110 E6581442  Selection of braking resistor option and braking unit Standard braking resistors are listed in the table below. The usage rate is 3%. (Except for type DGP***) Braking resistor Continuous regenerative Inverter type Model number Rating braking allowable capacity [Note 2] [Note 1] VFAS1-2004PL,...
  • Page 111 E6581442  Minimum resistance of connectable braking resistors The minimum allowable resistance values of the externally connectable braking resistors are listed in the table below. Do not connect braking resistors with smaller resultant resistance than the listed minimum allowable resistance values.
  • Page 112: Standard Default Setting

    E6581442 5.20 Standard default setting  : Factory default setting • Function This parameter is to set two or more parameters at a time for different commands. Using this parameter, all parameters can be also return to their respective default settings by one operation, and save or set specific parameters individually.
  • Page 113 E6581442 Default setting (=) Setting parameter  to  resets all parameters except the following to their default settings. When this parameter is set to 3,  is displayed for a while, then switches back to the original display (  ...
  • Page 114: Searching For All Reset Parameters And Changing Their Settings

    E6581442 5.21 Searching for all reset parameters and changing their settings  : Automatic edit function • Function Automatically searches for only those parameters that are programmed with values different from the standard default setting and displays them in the user parameter group . Parameter setting can also be changed within this group.
  • Page 115: Easy Key Function

    E6581442 5.22 EASY key function  : Registered parameter  ~  display selection Quick registration parameter 1~32  : EASY key function selection • Function The following three functions can be assigned to the EASY key for easy operation by means of a single key. •...
  • Page 116 E6581442 [How to select parameters] Select the desired parameters as parameters 1 to 32 (~). Note that parameters should be specified by communication number. For communication numbers, refer to Table of parameters. In the quick mode, only parameters registered as parameters 1 to 32 are displayed in order of registration. By default, parameters are set as shown in the table below.
  • Page 117: Extended Parameters

    E6581442 6. Extended parameters Extended parameters are provided for sophisticated operation, fine adjustment and other special purposes.  Refer to Section 11, Table of parameters. Input/output parameters 6.1.1 Low-speed signal  : Low-speed signal output frequency • Function When the output frequency exceeds the setting of  an ON signal will be generated. This signal can be used as an electromagnetic brake excitation/release signal.
  • Page 118: Putting Out Signals Of Arbitrary Frequencies

    E6581442 6.1.2 Putting out signals of arbitrary frequencies  : Speed reach setting frequency  : Speed reach detection band • Function When the output frequency becomes equal to the frequency set by  ± , an ON or OFF is generated.
  • Page 119: Input Signal Selection

    E6581442 Input signal selection 6.2.1 Priority when forward/reverse run commands are entered simultaneously  : Priority when forward/reverse run commands are entered simultaneously • Function This parameter allows you to select the direction in which the motor runs when a forward run (F) command and a reverse run (R) command are entered simultaneously.
  • Page 120: Assigning Priority To The Terminal Board In The Operation Panel And Operation Mode

    E6581442 6.2.2 Assigning priority to the terminal board in the operation panel and operation mode  : Input terminal priority selection • Function This parameter is used to give priority to certain external commands entered from the terminal board in operation panel and operation mode.
  • Page 121: Analog Input Signal Switching

    E6581442 Output frequency [Hz] Forward run Set frequency Forward run 0 Panel key STOP STOP STOP S3-CC (Jog run) 6.2.3 Analog input signal switching  : Analog input VI/VII voltage/current switching  : Analog input AI2 (optional circuit board) voltage/current switching •...
  • Page 122: Terminal Function Selection

    E6581442 Terminal function selection 6.3.1 Keeping an input terminal function always active (ON)  ,  ,  : Always ON function selection 1~3  • Function This parameter specifies an input terminal function that is always kept active (ON). (Only one function selectable) [Parameter setting] Title...
  • Page 123 E6581442  Connection method 1) a-contact input Inverter a-contact switch Sink setting Input  This function is activated when the input terminal and CC terminal (common) are short-circuited. Use this function to specify forward/reverse run or a preset speed operation. 2) Connection with transistor output Inverter Programmable controller...
  • Page 124: Using The Servo Lock Function

    E6581442 6.3.3 Using the servo lock function  : Input terminal function selection 4 (RES)  : Starting frequency setting • Function As with the operation of a server motor, these parameters allow you to operate the motor at 0Hz by simply issuing an operation signal.
  • Page 125: Response Time Of Input/Output Terminals

    E6581442 6.3.5 Response time of input/output terminals  : Input terminal 1 response time selection  : Input terminal 2 response time selection  : Input terminal 4 response time selection  : Input terminal 5~12 response time selection  : Input terminal 13~20 response time selection ...
  • Page 126 E6581442  Setting of switching terminals The V/f1, V/f2, V/f3 and V/f4 switching function is not yet assigned to any terminal. Therefore, it is necessary to assign them to unused terminals. Ex.) Assigning the V/f switching 1 function to S1 and the V/f switching 2 function to S2. Title Function Adjustment range...
  • Page 127: V/F 5-Point Setting

    E6581442 V/f 5-point setting  : V/f 5-point setting VF1 frequency  : V/f 5-point setting VF4 frequency  : V/f 5-point setting VF1 voltage  : V/f 5-point setting VF4 voltage  : V/f 5-point setting VF2 frequency  : V/f 5-point setting VF5 frequency ...
  • Page 128 E6581442 Command selected with  2) Automatic switching by means of switching frequencies (=) Command selected Operation frequency with  command Command selected with  A: If the frequency set with  is higher than that set with  ························· Priority is given to the command set with .
  • Page 129: Operation Frequency

    E6581442 Operation frequency 6.7.1 Start frequency/Stop frequency  : Start frequency setting  : Stop frequency setting • Function The frequency set with the parameter  is put out as soon as operation is started. Use the  parameter when a delay in response of starting torque according to the acceleration/deceleration time is probably affecting operation.
  • Page 130: Frequency Setting Signal 0Hz Dead Zone Handling Function

    E6581442 Output frequency [Hz]  The inverter begins accelerating after the frequency command value has reached point B.   Deceleration stop begins when the frequency command value decreases  below point A.   – 100% Operation frequency command value 6.7.3.
  • Page 131: Dc Braking

    E6581442 Note:During DC braking, the DC braking current may be adjusted Output frequency [Hz] automatically to prevent the overload LED display protection function from being  displayed activated and causing the inverter to Set frequency trip. DC braking The DC braking current may be adjusted automatically to prevent tripping.
  • Page 132: Motor Shaft Fixing Control

    E6581442 [Priority to DC braking during forward/reverse operation] (Forward/reverse run DC braking priority control =[Enabled])    = = Output frequency [Hz] : DC braking      Set frequency  Time [s] Reference frequency   Forward run signal (F-CC) Reverse run signal (R-CC) (4) During normal forward/reverse run (=) : Not recognized as a stop command, so that the DC...
  • Page 133: Function Of Issuing A 0Hz Command During A Halt

    E6581442 LED display  is displayed. Output frequency [Hz]  is displayed. Set frequency   DC braking start frequency Time [s] Output current [A]  Operation signal (F-CC) Operation standby signal (S3-CC) Note 1: If the motor shaft fixing control parameter  is set at  (enabled) when the output frequency is below the DC braking start frequency ...
  • Page 134: Auto-Stop In Case Of Lower-Limit Frequency Continuous Operation (Sleep/Wake-Up Function

    E6581442 Auto-stop in case of lower-limit frequency continuous operation (Sleep/Wake-up function)   : Time limit for lower-limit frequency operation • Function If operation is carried out continuously at a frequency below the lower-limit frequency () for the period time set , theinverter will automatically slow down the motor to a stop. “”...
  • Page 135: Jog Run Mode

    E6581442 6.10 Jog run mode   : Jog run frequency   : Jog run stop pattern   : Operation panel jog run mode • Function Use the jog run parameters to operate the motor in jog mode. Input of a jog run signal generates a jog run frequency output at once, irrespective of the designated acceleration time.
  • Page 136: Setting Frequency Via External Contact Input (Up/Down Frequency Setting

    E6581442 [Setting of jog run setting terminal (S3-CC)] Assign control terminal S3 ([: preset speed 3] in default setting) as the jog run setting terminal. Title Function Adjustment range Setting value  ~  (Jog run setting terminal) Input terminal function selection 7 (S3) Note: During the jog run mode, there is LOW (low speed detection signal) output but no RCH (designated frequency reach signal) output, and PID control does not work.
  • Page 137 E6581442  Adjustment with continuous signals (Parameter setting example 1) Set parameters as follows to adjust the output frequency up or down in proportion to the frequency adjustment signal input time: Panel frequency incremental gradient =  /  setting time Panel frequency decremental gradient = ...
  • Page 138: Jump Frequency - Jumping Resonant Frequencies

    E6581442  If two signals are input simultaneously • If a clear single and an up or down signal are input simultaneously, priority will be given to the clear signal. • If up and down signals are input simultaneously, the frequency will be increased or reduced by the difference between the settings of ...
  • Page 139: Preset Speed Operation Frequencies

    E6581442 [Parameter setting] Title Function Adjustment range Default setting   ~  Hz   Jump frequency 1   ~  Hz   Jumping width 1   ~  Hz   Jump frequency 2  ...
  • Page 140: Trip-Less Intensification

    E6581442 6.14 Trip-less intensification 6.14.1 Retry function  : Retry selection (selecting the no. of times) Caution • Stand clear of motors and equipment. The motor and equipment stop when the alarm is given, selection of the retry function will restart them suddenly after the specified time has elapsed.
  • Page 141: Avoiding Overvoltage Tripping

    E6581442 During retry the blinking display will alternate between  and the monitor display specified by parameter monitor display selection parameter . The number of retries will be cleared if the inverter is not tripped for the specified period of time after a successful retry. “A successful retry”...
  • Page 142 E6581442 [Parameter setting] Title Function Adjustment range Default setting 200V class: Base frequency voltage 1 V class:~ V   (output voltage V class:~ V 400V class: adjustment)  :Without voltage compensation (limitless output voltage) Base frequency voltage : With voltage compensation (limitless output voltage) selection ...
  • Page 143: Reverse Run Prohibition

    E6581442 6.14.4 Reverse run prohibition  : Reverse run prohibition selection • Function This function prevents the motor from running in the forward or reverse direction when it receives the wrong operation signal. [Parameter setting] Title Function Adjustment range Default setting :Permit all, :Prohibit reverse run ...
  • Page 144 E6581442 [Parameter setting] Title Function Adjustment range Default setting  ~ %  Drooping gain [Note]  ~ Hz  Speed at drooping gain 0%  Speed at drooping gain  ~ Hz   ~ %  Drooping insensitive torque ...
  • Page 145: Light-Load High-Speed Operation Function

    E6581442 6.16 Light-load high-speed operation function  : Light-load high-speed operation  : Switching load torque during selection power running  : Light-load high-speed learning  : Heavy-load torque during power function running  : Automatic light-load high-speed  : Heavy-load torque during operation frequency constant-speed power running ...
  • Page 146 Note2: For the braking functions, the pre-excitation time is automatically determined by the inverter from motor-related constants. When the VFAS1-2037PL is used in combination with a Toshiba 4P-3.7kW-60Hz-200V standard motor, the preliminary excitation time is approximately 0.1 to 0.2 seconds.
  • Page 147: Acceleration/Deceleration Suspend Function

    E6581442  Torque bias function Reverse run Using this function, the load can be started smoothly, by the motor produces enough torque Forward run for load portion before the brake is released, Tension torque bias as additional torque Additional torque [Selection of external signals] ...
  • Page 148: Commercial Power/Inverter Switching

    E6581442 2) To suspend acceleration or deceleration by means of a signal from an external control device Set  for the desired external signal input terminal. As long as ON signals are inputted, the motor continues to rotate at a constant speed. Output frequency [Hz] Time [s] Terminal board input...
  • Page 149 E6581442 [Parameter setting] Title Function Adjustment range Default setting :Disabled :Automatic switching in the event of a trip Commercial power/inverter   :Commercial power switching frequency setting switching output selection :Commercial power switching frequency setting + automatic switching in the event of a trip [Note1] Inverter with a model number Commercial power/inverter...
  • Page 150: Pid Control

    E6581442 - Warning - • When switching to commercial power, make sure that the direction in which the motor rotates when operated on commercial power agrees with the forward direction when operated via the inverter. • Do not select any option (=) of  (reverse rotation prohibition selection) that prohibits forward rotation.
  • Page 151 E6581442 1) External connection Pressure transmitter (1) Process value DC:0~10V RR/S4 VI/II (2) Feedback value DC:4~20mA 2) Types of PID control interface Process value (frequency) and feedback value can be combined as follows for the PID control of the VF-AS1. (1)Process value(frequency setting) (2) Feedback value Frequency setting mode selection /...
  • Page 152 E6581442 3) Setting the PID control In case of controlling the airflow, water flow and pressure, please set the parameter  to ””(Process type PID control operation) (1)Please set the parameter (Acceleration time),(deceleration time) to the suitable time for the system. (2)Please set the following parameters to place limits to the setting value and the control value.
  • Page 153 E6581442  Differential (D) gain The differential (D) gain set with  is the differential (D) gain obtained by PID control. The differential gain increases the speed of response to rapid changes in deviation. If this gain is set excessively high, a phenomenon in which the output frequency greatly fluctuates may occur.
  • Page 154: Stop Position Control Function

    E6581442 The characteristic of the feedback value can also be reversed by means of a signal from an external device. Example: To use the S3 terminal as a PID normal/reverse characteristic switching signal input terminal Title Function Adjustment range Default setting ...
  • Page 155 Operation in automatic torque boost mode or vector control mode (=, , , , ) Is the motor Toshiba standard four-pole motor with the same capacity rating as the inverter? Is the motor cable 30m or less in length? *1 Set the following parameters, as specified on the motor nameplate.
  • Page 156 :Motor constant auto calculation ( after execution) =: Resets  (motor constant 1),  (motor constant 2),  (motor constant 3) and  (motor constant 4) to their factory default settings (constant of a Toshiba standard four-pole motor with the same capacity as the inverter).
  • Page 157: Setting Motor Constants

    E6581442  Examples of setting the motor constants a) Combination with a Toshiba standard motor (4P motor with the same capacity as the inverter) Inverter : VFAS1-2037PL Motor : 3.7kW-4P-60Hz 1) Set the V/f control mode selection  at  (Sensorless vector control).
  • Page 158: Increasing The Motor Output Torque Further In Low Speed Range

    E6581442 6.23 Increasing the motor output torque further in low speed range  : Exciting strengthening coefficient  : Stall prevention factor The output torque of the motor can adjusted using the parameters described in 6.22 in most cases, but if a finer adjustment is required, use these parameters.
  • Page 159: Torque Control

    E6581442 6.24 Torque control  For details, refer to Instruction Manual (E6581331) specified in Section 6.42. 6.24.1 Torque command  : V/f control mode selection  : Torque command selection  : VI/II input point 1 setting  : VI/II input point 1 rate ...
  • Page 160: Selection Of Tension Torque Bias Input And Load Sharing Gain Input

    E6581442 6.24.3 Selection of tension torque bias input and load sharing gain input Load sharing gain Torque reference Torque command × Tension torque bias [Parameter setting] Title Function Adjustment range Default setting :Disabled :VI/II (voltage/current input) :RR/S4 (potentiometer/voltage input) :RX (voltage input) :Operation panel input enabled (including Tension torque bias input ...
  • Page 161: Torque Limit

    E6581442 6.25 Torque limit 6.25.1 Torque limit switching  : Power running torque limit 1  : Power running torque limit 3 selection level  : Power running torque limit 1  : Regenerative braking torque level limit 3 level ...
  • Page 162 E6581442 [Parameter setting] Title Function Adjustment range Default setting :VI/II (voltage/current input) :RR/S4 (potentiometer/voltage   Power running torque limit 1 selection input) :RX (voltage input) :  ~ %  %:Disabled  % Power running torque limit 1 level :VI/II (voltage/current input) :RR/S4 (potentiometer/voltage Regenerative braking torque limit 1...
  • Page 163: Torque Limit Mode Selection At Acceleration/Deceleration

    E6581442 RX-CCA RR/S4 -CCA, VI/II-CCA 100% +100% Torque produced Torque produced by motor by motor -10V +10V VI/II-CCA -100% 100% Torque produced by motor 20mA [Parameter setting] Title Function Adjustment range Default setting :VI/II (voltage/current input) :RR/S4 (potentiometer/voltage   Power running torque limit 1 selection input) :RX (voltage input)
  • Page 164 E6581442 Operation frequency Frequency [Hz] If the torque limit function is not activated Actual speed Time [s] Torque [N·m] Torque limit level Time [s] Mechanical brake (released) Time [s] (2) =(In sync with min. time) The operation frequency keeps increasing, even if the torque limit function is activated. In this control mode, the actual speed is kept in sync with the operation frequency, while torque is held at a limit level when it decreases as a result of the release of the mechanical brake.
  • Page 165: Stall Prevention Function

    E6581442 6.26 Stall prevention function 6.26.1 Power running stall continuous trip detection time  : Power running stall continuous trip detection time • Function A function for preventing lifting gear from failing accidentally. If the stall prevention function is activated in succession, the inverter judges that the motor has stalled and trips.
  • Page 166: Current And Speed Control Adjustment

    E6581442 6.27 Current and speed control adjustment 6.27.1 Current and speed control gain  ~  : Current and speed control gain  For details, refer to Instruction Manual (E6581333) specified in Section 6.42. 6.27.2 Prevention of motor current oscillation at light load ...
  • Page 167: Fine Adjustment Of Frequency Setting Signal

     ,  : Step-out detection current level/ detection time This parameter is used only when the inverter is used with a synchronous motor. If you intend to use your inverter with a synchronous motor, contact us at the your Toshiba distributor. F-51...
  • Page 168: Acceleration/Deceleration

    E6581442 6.30 Acceleration/deceleration 2 6.30.1 Setting acceleration/deceleration patterns and switching acceleration/deceleration patterns 1, 2, 3 and 4  : Acceleration time 2  : Deceleration S-pattern upper limit adjustment  : Deceleration time 2  : Acceleration time 3  : Acceleration/deceleration 1 pattern ...
  • Page 169 E6581442 2) Switching by frequencies - Automatically switching acc/dec times at certain frequencies Title Function Adjustment range Default setting  ~ Hz  Acceleration/deceleration switching frequency 1  ~ Hz  Acceleration/deceleration switching frequency 2  ~ Hz  Acceleration/deceleration switching frequency 3 Note: Regardless of the sequence of input of frequencies, acc/dec times are switched from 1 to 2 at the lowest frequency, from 2 to 3 at the middle frequency and from 3 to 4 at the highest frequency.
  • Page 170 E6581442  Setting parameters a) Operating method: Terminal input Set the command mode selection  to . b) Use the S2 and S3 terminals for switching. (Instead, other terminals may be used.) S2: Acceleration/deceleration switching signal 1 S3: Acceleration/deceleration switching signal 2 Title Function Adjustment range...
  • Page 171: Pattern Operation

    E6581442 3) S-pattern acceleration/deceleration 2 Select this pattern to obtain slow acceleration in a demagnetizing region with a small motor acceleration torque. This pattern is suitable for high-speed spindle operation. Output frequency [Hz] Output frequency [Hz] Maximum frequency Maximum frequency ...
  • Page 172 E6581442 <Basic operating> Step Setting Parameter = (Disabled) Set the pattern operation selection  (Pattern operation enabled, setting in seconds) parameter at “Enabled.”  (Pattern operation enabled, setting in minutes) ~ Set all necessary operation frequencies. (Preset speed operation frequencies 1~7) ~...
  • Page 173: Preset Speed Mode

    E6581442  Pattern operation switching output (output terminal function: , ) If the pattern operation switching output function is selected (activated), a signal is put out on completion of all the predetermined patterns of operation. When there is no operation command left to be entered or the pattern operation selection signal changes, the output terminals are turned off.
  • Page 174: Protection Functions

    E6581442 6.33 Protection functions 6.33.1 Setting of stall prevention level  : Stall prevention level Caution • Do not set the stall prevention level () extremely low. If the stall prevention level parameter () is set at or below the no-load current of the motor, the stall preventive function will be always active and increase the frequency when it judges that regenerative Prohibited braking is taking place.
  • Page 175: Emergency Stop

    E6581442 Be sure to select this setting if the main power supply is turned on and off endlessly for reasons of sequence, as shown below, in the event the control power supply backup device fails or not connected. R/L1 In case of ...
  • Page 176: Output Phase Failure Detection

    E6581442 3) Selecting the operation of the FL relay Using the output terminal selection parameter, you can specify whether or not to operate the FL relay.  (output terminal selection 3) =  (default): Operates the FL relay in the event of an emergency stop. ...
  • Page 177: Ol Reduction Starting Frequency

    E6581442 6.33.5 OL reduction starting frequency  : OL reduction starting frequency  For more details, refer to Section 5.14. 6.33.6 Motor 150%-overload time limit  : Motor 150%-overload time limit  For more details, refer to Section 5.14. 6.33.7 Input phase failure detections ...
  • Page 178: Detection Of Output Short Circuit

    E6581442 <Example of operation> Output terminal function: 26 (UC) Low current detection = (No trip) Ex.) When outputting low current detection signals through output terminal OUT1 Title Function Adjustment range Setting value Output terminal function selection 1(OUT1)  ~  Note: To put out signals to the terminal OUT2, select the parameter .
  • Page 179: Cooling Fan Control Selection

    E6581442 • Function Trips the inverter or issues an alarm if the total time for which torque is above the level set with    /    reaches the time set with    . Trip information is displayed as “ .” =...
  • Page 180: Cumulative Operation Time Alarm Setting

    E6581442 The cooling fan automatically operates whenever the ambient temperature is high, even when the inverter is out of operation. Title Function Adjustment range Default setting  Cooling fan control selection :Auto, :Always ON  6.33.12 Cumulative operation time alarm setting ...
  • Page 181: Overvoltage Limit Operation

    E6581442 6.33.14 Overvoltage limit operation  : Overvoltage limit operation level  For more details, refer to Section 6.14.2. 6.33.15 Undervoltage trip  : Undervoltage detection level  : Undervoltage trip selection  : Undervoltage (trip alarm) detection time • Function This parameter is used for selecting the control mode when an undervoltage is detected.
  • Page 182: Analog Input Wire Breakage Detection Level

    E6581442 6.33.18 VI/II analog input wire breakage detection level  : VI/II analog input wire breakage detection level • Function The inverter will trip if the VI/II value remains below the specified value for 0.3 seconds or more the message “” is displayed. =: Disabled ·········...
  • Page 183: Motor Thermal Protection

    E6581442 DC voltage  Rush current suppression relay 6.33.21 Motor thermal protection  ~  : PTC thermal selection  For details, refer to Instruction Manual (E6581339) specified in Section 6.42. 6.33.22 Braking resistance overload curve  : Braking resistance overload time ...
  • Page 184: Protection Against A Failure Of The Control Power Backup Device (Optional Cps002Z

    E6581442 6.33.24 Protection against a failure of the control power backup device (optional CPS002Z)  : Control power supply backup option failure monitoring • Function If the control power backup device (optional CPS002Z) fails to supply power for some reason or other for fifteen minutes and over, the inverter will put out an alarm signal or a trip signal depending on the setting.
  • Page 185: Override

    E6581442 6.34 Override  : Override addition input selection  : Override multiplication input selection • Function These parameters are used to adjust reference frequencies by means of external input. Title Function Adjustment range Default setting :Disabled :VI/II (voltage/current input) :RR/S4 (potentiometer/voltage input) :RX (voltage input) :Operation panel input enabled (including...
  • Page 186 E6581442 Ex.1: = (VI/II input), = (disabled) Output frequency = Reference frequency + Override (VI/II input [Hz]) Ex.2: = (VI/II input), = (disabled) Output frequency = Reference frequency + Override (VI/II input [Hz]) 2) Multiplicative override In this mode, each output frequency is multiplied by an externally override frequency. [Ex.1: RR/S4 (Reference frequency), VI/II (Override input)] [Ex.2: RX (Reference frequency), VI/II (Override input)] Output frequency...
  • Page 187: Adjustment Parameters

    E6581442 6.35 Adjustment parameters 6.35.1 Pulse train output for meters  : Logic output/pulse output selection (OUT1)  : Pulse output function selection  : Selection of number of pulses  Function Pulse trains can be sent out through the OUT1-CC output terminals. To do so, it is necessary to select a pulse output mode and specify the number of pulses.
  • Page 188: Setting Of Optional Meter Outputs

    E6581442 6.35.2 Setting of optional meter outputs  ~  ,  ~  : Meter output settings  For details, refer to Instruction Manual (E6581341) specified in Section 6.42. 6.35.3 Calibration of analog outputs  : FM voltage/current output switching ...
  • Page 189: Operation Panel Parameter

    E6581442 6.36 Operation panel parameter 6.36.1 Prohibition of key operations and parameter settings  : Parameter write protect selection  : Operation panel frequency setting prohibition selection  : Operation panel emergency stop operation prohibition selection  : Operation panel reset operation prohibition selection ...
  • Page 190: Displaying The Rotational Speed Of The Motor Or The Line Speed

    E6581442 6.36.2 Displaying the rotational speed of the motor or the line speed  : Frequency free unit display magnification  : Frequency free unit conversion selection  : Free unit display gradient characteristic  : Free unit display bias ...
  • Page 191: Changing The Steps In Which The Value Displayed Changes

    E6581442  An example of setting: When  is , and  is  =, = =, = Panel indication Panel indication 1000   80(Hz) 80(Hz) Output frequency Output frequency =, = Panel indication  Output frequency 80 (Hz) 6.36.3 Changing the steps in which the value displayed changes ...
  • Page 192: Changing The Standard Monitor Display

    E6581442 6.36.4 Changing the standard monitor display  : Standard monitor display selection  ~  : Status monitor 1~8 display selection These parameters are used to select the item to be displayed when the power turned on and also to change items displayed in status monitor mode.
  • Page 193: Torque-Related Parameters For Panel Operation

    E6581442 6.36.8 Torque-related parameters for panel operation  : Operation panel tension torque bias  : Operation panel load sharing gain These parameters are used to specify the torque bias and how to share the load.  For details, refer to Instruction Manual (E6581331) specified in Section 6.42. 6.37 Tracing functions ...
  • Page 194 E6581442 1) To acquire trace data at the occurrence of tripping: = (Examples of current date output) Trip Monitor value of output current Failure FL signal :Trace data Trace data 1 2) To acquire trace data at the time of triggering: = Trigger input Trace data 1 Ex.) When using the RR/S4 terminal as the tracing back trigger signal terminal...
  • Page 195 E6581442 [Setup values of ~] Communication Communication Default setting Trace (monitor) function unit at tracing  FD00 Output frequency 0.01Hz  FD02 Frequency command value 0.01Hz  FD03 Output current 0.01%  FD04 Input voltage (DC detection) 0.01%  FD05 Output voltage 0.01% ...
  • Page 196: Integrating Wattmeter

    E6581442  Trace data communication number Communication Minimum setting Function Setting/readout range Default setting /readout unit / ~  E000 Trace data 1~4 pointer / ~  E100 Data 1 of trace data 1  / ~  Data 2~99 of trace data 1 /...
  • Page 197: Communication Function

    E6581442 6.39 Communication function 6.39.1 2-wire RS485/4-wire RS485  : Communication speed (2-wire RS485)  : Parity (common to 2-wire RS485 and 4-wire RS485)  : Inverter number (common)  : Communications time-out time (common to 2-wire RS485 and 4-wire RS485) ...
  • Page 198  communications something goes wrong with the (2-wire RS485) master) :Master (sends a frequency command) :Master (sends an output frequency) :Master (sends a torque command) :Master (sends an output torque command)  :TOSHIBA, :MODBUS  Protocol selection (2-wire RS485) F-82...
  • Page 199 E6581442 Title Function Adjustment range Default setting :Disconnection detection :When communication mode Communication1 time-out condition   enable selection :1+Driving operation :Disabled :2-wire RS485  Frequency point selection  :4-wire RS485 :Communication add option  Point 1 setting ~ % ...
  • Page 200 E6581442 2) 4-wire RS485 The 4-wire RS485 device included as standard equipment, allows you to connect the inverter to a higher-level system (host) and to set up a network for data communications between inverters. It makes it possible for the inverter to be linked to a computer and to carry out data communications with other inverters.
  • Page 201 E6581442 <Broadcast> When an operation frequency command is broadcasted from the host computer to inverters : Wiring : Data (host  INV) Host computer      No.00 No.01 No.02 No.03 No.29 No.30 : Use the terminal board to branch the cable. (1) Data is sent from the host computer.
  • Page 202   something goes wrong with the (4-wire RS485) master) :Master (sends a frequency command) :Master (sends an output frequency) :Master (sends a torque command) :Master (sends an output torque command) :TOSHIBA   Protocol selection (4-wire RS485) :MODBUS F-86...
  • Page 203 E6581442 Title Function Adjustment range Default setting :Disabled :Command information 1 :Command information 2  Block write data 1 :Frequency command  :Terminal board output data :Communication analog output :Rotational speed instruction  Block write data 2  Ditto :Deselect :Status information :Output frequency :Output current...
  • Page 204: Open Network Option

    E6581442 6.39.2 Open network option  ~  : For Ethernet Communication option  ~  : MAC address data 1~6  ~  : Device name data 1~8  : Address monitor (Modbus plus)  : Command selection (Modbus plus) ...
  • Page 205: Instruction Manuals For Optionally Available Devices And Special Functions

    E6581442 Instruction manuals for optionally available devices and special functions 6.42 For details, refer to the instruction manual for each optional device or function. Model Instruction Description Remarks number Manual No. Light-load high-speed operation function – E6581327 – PID control operation function –...
  • Page 206: Operation With External Signal

    E6581442 7. Operation with external signal External operation The inverter can be freely controlled externally. Parameters must be differently set depending on the operation method. Make sure of the operation method before setting parameters, and set parameters properly to the operation mode according to the procedure mentioned below. [Steps in setting parameters] Check of external signal conditions Operation signal:...
  • Page 207: Applied Operation With Input And Output Signals (Operation By Terminal Board

    E6581442 Applied operation with input and output signals (operation by terminal board) 7.2.1 Functions of input terminals (in case of sink logic) Use the above parameters to send signals from an external programmable controller to various control input terminals to operate and/or set the inverter. The desired contact input terminal functions can be selected from 120 types.
  • Page 208 E6581442 3) Connection with transistor output Inverter Programmable controller Input terminal  The inverter can be controlled by connecting the input terminal with output (contactless switch) of a programmable controller. Use this function to specify forward/reverse run or a preset speed operation. Use a transistor that operates on 24Vdc, 5mA power.
  • Page 209 E6581442  Table of setting of contact input terminal function Parameter setting Parameter setting Function Function Positive Negative Positive Negative logic logic logic logic   No function is assigned   Servo lock signal F: Forward run command Simple positioning (positioning loop) ...
  • Page 210: Functions Of Output Terminals (Incase Of Sink Logic

    E6581442  Sink logic/source logic Switching between sink logic and source logic (input/output terminal logic) is possible.  For details, refer to the Section 2.3.2. 7.2.2 Functions of output terminals (incase of sink logic) Use the above parameters to send various signals from the inverter to external equipment. By setting parameters for the OUT1, OUT2 and FL (FLA, FLB and FLC) terminals on the terminal board, you can use 0~255 functions and functions obtained by combining them.
  • Page 211 E6581442  Output terminal function (open collector, relay outputs) setting and detection levels For the open connector output terminals (OUT1, OUT2) and the relay output terminals (FLA, FLB and FLC), functions can be selected from 0 to 255 functions. The selectable functions and detection levels are listed in the table below.
  • Page 212 E6581442 Parameter setting Function Operation output specifications (in case of positive logic) Positive Negative logic logic ON:The state that torque component is  ,  set Over-torque detection   value or larger continued more than  set value. ON:A certain rate of braking resister overload trip (  ) Braking resistor detection time is over.
  • Page 213 E6581442 Parameter setting Function Operation output specifications (in case of positive logic) Positive Negative logic logic Specified data output   Specified data output   Specified data output   Specified data output Output of the designated data in 7-bit. ...
  • Page 214: Setup Of Input Terminal Operation Time

    E6581442 7.2.3 Setup of input terminal operation time •Function The input/output terminal operation time setup function is used to extend response time if there is something malfunctioning because of noise or chattering of input relay.  Setup of response time Title Function Adjustment range...
  • Page 215: Setup Of External Speed Command (Analog Signal

    E6581442 Setup of external speed command (analog signal) Function of analog input terminals can be selected from four functions (external potentiometer, 0 to 10Vdc, 4 (0) to 20mAdc, -10 to +10Vdc). The selective function of analog input terminals gives system design flexibility. ...
  • Page 216: Setup By Analog Input Signals (Rr/S4 Terminal

    E6581442 7.3.1 Setup by analog input signals (RR/S4 terminal) If a potentiometer (1~10kΩ-1/4W) for setting up frequency is connected with the RR/S4 terminal, the inverter can be run and stopped with external commands. For bringing this function into practice, connect a potentiometer to the terminals of PP, RR/S4 and CC so as to divide the reference voltage (10Vdc) at the terminal PP and to input 0 to 10Vdc of divided voltage between the RR/S4 and CC terminals.
  • Page 217: Setup By Analog Input Signals (Vi/Ii Terminal

    E6581442 7.3.2 Setup by analog input signals (VI/II terminal) Connect current signal (4 (0) to 20mAdc) or voltage signal (0 to 10Vdc) to the terminal II so that the inverter can be run and stopped with external commands. Adjustment Setting value Title Function Default setting...
  • Page 218: Setup By Analog Input Signals (Rx Terminal

    E6581442 7.3.3 Setup by analog input signals (RX terminal) Connect voltage signal (0 to ±10Vdc) to the terminal RX so that the inverter can be run and stopped with external commands. Title Function Adjustment range Default setting Setting value  Command mode selection ...
  • Page 219: Monitoring The Operation Status

    E6581442 8. Monitoring the operation status Screen composition in the status monitor mode The status monitor mode is used to monitor the operation status of the inverter.  For modes available and instructions about how to switch them, refer to section 3.1. Here is the screen composition in the status monitor mode.
  • Page 220: Monitoring The Status

    E6581442 Monitoring the status 8.2.1 Status monitor under normal conditions In this mode, you can monitor the operation status of the inverter. twice To monitor the inverter when it is normally running, press the MODE and the current status is indicated on the LED display.
  • Page 221 E6581442 (Continued) Commun ication Item displayed Description operated display  FE08 CPU1 version The version of the CPU1 is displayed.  FE73 CPU2 version The version of the CPU2 is displayed.  [Note 5] FE10 Past trip 1 Past trip 1 (displayed alternately at 0.5-sec. intervals) ...
  • Page 222 E6581442  Input terminal information Data bit of communication No. F E 06 :  : 0 Input terminal 1 (F) :  : 1 Input terminal 2 (R) When there is signal input :  : 3 Input terminal 4 (RES) When there is no signal input : ...
  • Page 223: Display Of Detailed Information On A Past Trip

    E6581442 8.2.2 Display of detailed information on a past trip Details on a past trip (of trips 1 to 4) can be displayed, as shown in the table below, by pressing the key when the trip record is selected in the status monitor mode. Unlike the "...
  • Page 224: Changing Status Monitor Function

    E6581442 Changing status monitor function  Changing the display format while power is on The item displayed in the standard monitor mode (*1 on the left side of table on page H-2), for example, operation frequency which is displayed by default in this way: “=” when power is on or “” when power is off, can be changed to any item shown on page H-7.
  • Page 225 E6581442 [Setup values of monitor indication parameters (~)] Communication Default Unit Item displayed Marking Unit (Panel) setting (Communication)   FD00 Output frequency 0.1Hz [note 4] 0.01Hz   FE02 Frequency command value 0.1Hz [note 4] 0.01Hz   1% or  FE03 Output current 0.01%...
  • Page 226 E6581442 (Continued) Communication Default Unit Item displayed Marking Unit (Panel) setting (Communication)  RP  FE56 0.1% 0.01%  COUNT1  FD85  COUNT2  FD86  PID result frequency  FD52 0.1Hz 0.01Hz Synchronous speed frequency   FE84 0.1Hz 0.01Hz command...
  • Page 227: Display Of Trip Information

    E6581442 Display of trip information 8.4.1 Trip code display If the inverter trips, an error code is displayed to suggest the cause. In the status monitor mode, the status when the inverter trip is held.  Display of trip information Communication/Error code Error code Description...
  • Page 228 E6581442 (Continued) Communication/Error code Error code Description Communication No.:FC90  Speed error (Over speed)  Terminal input error  Abnormal CPU2 communication  V/f control error  CPU1 fault  Abnormal logic input voltage  Option 1 error  Option 2 error ...
  • Page 229: Monitor Display At Tripping

    E6581442 8.4.2 Monitor display at tripping At the occurrence of a trip, the same information as that displayed in the mode described in 8.2.1, “Status monitor under normal conditions,” can be displayed, as shown in the table below, if the inverter is not turned off or reset. To display trip information after turning off or resetting the inverter, follow the steps described in 8.2.2, “Display of detailed information a past trip.”...
  • Page 230 E6581442 (Continued) Commun ication Item displayed Description operated display    Past trip 1 (displayed alternately at 0.5-sec. intervals) FE10 Past trip 1 [Note 7]    Past trip 2 (displayed alternately at 0.5-sec. intervals) FE11 Past trip 2 [Note 7] ...
  • Page 231: Display Of Alarm, Pre-Alarm, Etc

    E6581442 Display of alarm, pre-alarm, etc. When the inverter alarm, pre-alarm, etc. occurred, the contents are displayed. (Some are not displayed.) Listed below ones can be monitored via communication (FC91). Refer to 13.1 for the other alarms. Description Panel indication ...
  • Page 232: Measures To Satisfy The Standards

    The CE mark must be put on every final product that includes an inverter(s) and a motor(s). The VF-AS1 series of inverters complies with the EMC directive if an EMC filter recommended by Toshiba is connected to it and wiring is carried out correctly.
  • Page 233: Measures To Satisfy The Emc Directive

    E6581442 9.1.2 Measures to satisfy the EMC directive Concrete measures for EMC directive of CE markings are shown below.  Models with a built-in EMC filter (1) 200V class: VFAS1-2004PL~2075PL 400V class: VFAS1-4007PL~4500KPC The above mentioned models install EMC noise filter inside. So the conducted and radiated noise can be reduced, optional EMC noise filters are not needed.
  • Page 234 E6581442 (2) Use shielded power cables and control signal cables for the input and output lines of the inverter. Route the cables and wires so as to minimize their lengths. Keep a distance between the power cable and the control cable and between the input and output wires of the power cable.
  • Page 235 E6581442  When an external EMC filter is added (1) Additional external EMC filters have the further effect of suppressing conduction and radiation noises. Use the recommended EMC noise filter specified in Table 3. This combination of inverter and filter was used when examining the inverter for compliance with the EMC directive.
  • Page 236 E6581442 (Continued) Requirements Conducted noise Conducted noise PWM carrier Length of motor IEC61800-3 category C2 IEC61800-3 category C1 Inverter type frequency  connecting cable (EN55011 classA Group1) (EN55011 classB Group1) (kHz) Applicable filters Applicable filters EMF3-4090F EMF3-4090F EMF3-4090F VFAS1-4220PL EMF3-4090F EMF3-4090F 4.1~12 EMF3-4090F...
  • Page 237 E6581442 [Ex. Countermeasure - inverter wiring] Strip and earth the shielded cable, following the example shown in Fig. Peel off the outer sheath of the cable and fix the shielded part with a metal saddle. EMC plate (Refer to Table 2.) PG feedback signal line (Shielded cabless) Control wiring (Shielded cabless) Relay contact output FLA, FLB, FLC...
  • Page 238 E6581442...
  • Page 239: Low-Voltage Directive

    Type : NF series 9.1.3 Low-voltage directive The low-voltage directive provides for the safety of machines and systems. All Toshiba inverters are CE-marked in accordance with the standard IEC61800-5-1 specified by the low-voltage directive, and can therefore be installed in machines or systems and imported without a problem to European countries.
  • Page 240: Measures To Be Taken To Satisfy The Ul/Csa Standards

    E6581442 Measures to be taken to satisfy the UL/CSA standards All VF-AS1 series inverters are certified by UL and CSA, and have nameplates with UL and CSA markings. 9.2.1 Caution in installing the inverter A UL certificate was granted on the assumption that the inverter would be installed in a cabinet. Therefore, install the inverter in a cabinet and if necessary, take measures to maintain the ambient temperature (temperature in the cabinet) within the specified temperature range.
  • Page 241: Caution As To The Protection Of Motors From Overload

    E6581442 Table 5 AIC, Fuse and Wire sizes Applicable AIC (A) Fuse class Input wire sizes of Output wire sizes of Voltage Earth motor output current (Interrupting and current power circuit power circuit Inverter model class [kW] (A) *2, *3 capacity) VFAS1-2004PL 2.5 (=)
  • Page 242: Compliance With Safety Standards

    E6581442 Compliance with safety standards The VFAS1 inverter has the “power removal” safety function that complies with safety standards. To ensure safety performance, however, the mechanical system with which the VFAS1 inverter is used has to adhere to such standards as a whole. To be more specific, in order for the system to satisfy the following safety standards, it needs to be configured, as shown on the next page, with the power removal terminal of the VFAS1 inverter (PWR terminal on the control terminal board) so that it will coast or decelerate to a stop in the event of a failure.
  • Page 243 E6581442 Safety category1: EN954-1 category1, IEC/EN61508, SIL1 Stop category1: IEC/EN60204-1 Coast stop under the control of the MC in the main circuit (1) An example of connection for operation in sink mode (common: CC) • In this connection, the PWR terminal is not used. This connection falls under Stop Category 0 defined in IEC/EN60204-1.
  • Page 244 E6581442 Safety category1: EN954-1 category1, IEC/EN61508, SIL1 Stop category0: IEC/EN60204-1 Coast stop under the control of the MC in the main circuit (2) An example of connection for operation in source mode (common: P24) • In this connection, the PWR terminal is not used. This connection falls under Stop Category 0 defined in IEC/EN60204-1.
  • Page 245 E6581442 Safety category3: EN954-1 category3, IEC/EN61508, SIL2 Stop category0: IEC/EN60204-1 Coast stop under the control of PWR (1) An example of connection for operation in sink mode (common: CC) • In this connection, the PWR terminal is used to connect a safety device. The emergency stop circuit is supervised by the external safety relay.
  • Page 246 E6581442 Safety category3: EN954-1 category3, IEC/EN61508, SIL2 Stop category0: IEC/EN60204-1 Coast stop under the control of PWR (2) An example of connection for operation in source mode (common: P24) • In this connection, the PWR terminal is used to connect a safety device. The emergency stop circuit is supervised by the external safety relay.
  • Page 247 E6581442 Safety category3: EN954-1 category3, IEC/EN61508, SIL2 Stop category1: IEC/EN60204-1 Deceleration stop under the control of PWR (1) An example of connection for operation in sink mode (common: CC) • In this connection, the PWR terminal is used to connect a safety device. The emergency stop circuit is supervised by the external safety relay.
  • Page 248 E6581442 Safety category3: EN954-1 category3, IEC/EN61508, SIL2 Stop category1: IEC/EN60204-1 Deceleration stop under the control of PWR (2) An example of connection for operation in source mode (common: P24) • In this connection, the PWR terminal is used to connect a safety device. The emergency stop circuit is supervised by the external safety relay.
  • Page 249: Selection Of Peripheral Devices

    E6581442 10. Selection of peripheral devices Warning • When using the inverter without the front cover, be sure to place the inverter unit inside a cabinet. If they are used outside the cabinet, it may cause electric shock. Mandatory • Be sure to ground every unit. If not, it may cause electric shock or fire on the occasion of failure, short-circuit or electric leak.
  • Page 250: Selection Of Wiring Equipment

    1200 1600 (*1): Selections for use of the Toshiba 4-pole standard motor with power supply voltage of 200V/400V-50Hz. (*2): Choose the MCCB according to the power supply capacity. For comply with UL and CSA standard, use the fuse certified by UL and CSA.
  • Page 251: Installation Of A Magnetic Contactor

    () or appropriate to the motor used should be installed between the inverter and the motor.  When using a motor with a current rating different to that of the corresponding Toshiba general-purpose motor  When operating a single motor with an output smaller than that of the applicable standard motor.
  • Page 252: Application And Functions Of Options

    E6581442 10.4 Application and functions of options Separate type options shown below are prepared for the inverter VF-AS1 (2) DC reactor (4) Braking unit (DCL) (200kW models and larger) (4) Braking resistor No-fuse (3) EMC filter for CE breaker Magnetic compliance Power supply (MCCB)
  • Page 253 E6581442 Option name Function, purpose. LED Remote Keypad Extention operation panel unit with parameter copy function. Includes LED display, option RUN/STOP key, UP/DOWN key, MODE key, ENT key, EASY key, and COPY MODE key. (with parameter copy (When using this unit, set as follows:  (common serial transmission waiting time) = function) ...
  • Page 254 E6581442 Selection table of separate-type options (1/2) Dynamic Applicable Voltage Inverter EMC filter DC reactor brake drive circuit Control power motor class model (*1) (DCL) (GTR7) supply backup [kW] (*2) VFAS1-2004PL Built-in Option Built-in Option 0.75 VFAS1-2007PL Built-in Option Built-in Option VFAS1-2015PL Built-in...
  • Page 255 E6581442 Selection table of separate-type options (2/2) Motor end Control Appli-cable DC reactor Voltage Inverter Input AC reactor Braking resistor surge voltage power motor (DCL) class model (ACL) (*1) suppression supply [kW] (*5) filter (*4) backup VFAS1-2004PL DCL2-2004 PFL-2005S PBR-2007 0.75 VFAS1-2007PL DCL2-2007...
  • Page 256: Optional Internal Devices

    E6581442 Optional internal devices 10.5 Here are the internal devices optionally available. There are two types of optional devices: Add-on type and Plug-in type.  Table of optional devices Type of Option name Function, purpose Model installation (1) Expansion I/O card1 option ETB003Z Add-on (Logic input/output + PTC input)
  • Page 257 E6581442 (2) Expansion I/O card2 option (Function of optional card 1 + Analogue input/output + Pulse input) Function Description Multifunction programmable contact No-voltage contact input (24Vdc-5mA or less) input (4 points) Sink logic input (at a common voltage of 24V) Source logic input ON: Less than 10Vdc ON: 11Vdc or more...
  • Page 258 E6581442  How to install Add-on type devices and insertion type devices are installed in different ways. Install them correctly, as shown in the figures below. Add-on type Plug-in type Up to two Add-on type devices and one Plug-in type device can be installed at the same time.
  • Page 259: Connection Of A Dc Power Supply And Other Electric Units

    E6581442 10.6 Connection of a DC power supply and other electric units Besides a three-phase commercial power supply, a single-phase 200V power supply (5.5kW or less) and a DC power supply can be connected to the VFAS1 inverter. When connecting each of these units, keep in mind the points described in the following sections. 10.6.1 Connection of a single-phase 200V power supply The table below shows which model to select when operating a three-phase induction motor, using a single-phase 200V power supply (200-240V, 50/60Hz).
  • Page 260 E6581442  Power consumed by the fans VFAS1 Power consumed by the fans 2750P, 4110KPC~4160KPC 700VA 4200KPC~4280KPC 1300 VA 4355KPC, 4400KPC 1900 VA 4500KPC 2500 VA Connecting fans for a separate power supply In order to remove the link between the fans and the transformer power supply and relocate it at terminals RO, SO, TO, connectors X1 and X4 must be crossed as indicated on the diagrams below.
  • Page 261 E6581442 VFAS1-4200KPC~4280KPC VFAS1-4355KPC, 4400KPC, 4500KPC J-13...
  • Page 262: Table Of Parameters

    11. Table of parameters 1. User parameter *3 Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range control Reference Speed Torque (Panel/Communi setting running control control cation) Operation frequency of ...
  • Page 263 2. Basic parameter [2/4] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi Default Write during setting unit Title cation Function Adjustment range Reference Speed Torque setting running control (Panel/Communi control control cation) 0:Constant torque characteristics ● 1:Voltage decrease curve ●...
  • Page 264 2. Basic parameter [3/4] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque Reference (Panel/Communi setting running control control control cation) Motor electronic thermal  0600 10~100% Enabled ●/●...
  • Page 265 2. Basic parameter [4/4] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Reference Speed Torque setting running control (Panel/Communi control control cation) 0: - 1:50 Hz default setting 2:60 Hz default setting 3:Factory default setting 4:Trip clear...
  • Page 266 3. Extended parameters [1] Frequency signal Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Reference Speed Torque (Panel/Communi setting running control control control cation) Low-speed signal output  0100 0.0~...
  • Page 267 [3] Terminal function selection Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Reference Speed Torque setting running control (Panel/Communi control control cation) 0110 Always ON function selection 1 0~135 *1 Disabled ●/●...
  • Page 268 [4] Terminal response time setup Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque Reference (Panel/Communi setting running control control control cation) Input terminal 1 response time ...
  • Page 269 [5] V/f 5-point setting Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Reference Speed Torque setting running control (Panel/Communi control control cation) V/f 5-point setting VF1 0190 0.0~ Hz 0.1/0.01 Disabled ●...
  • Page 270 [6] Speed/torque reference gain/bias setup [2/2] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Reference Speed Torque (Panel/Communi setting running control control control cation)  0212 RR/S4 input point 2 setting 0~100% Enabled ●/●...
  • Page 271 [8] DC braking Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Reference Speed Torque setting running control (Panel/Communi control control cation) 0250 DC braking start frequency 0.0~120.0Hz 0.1/0.01 Enabled ●/●...
  • Page 272 [11] Preset speed operation frequency (8~15) Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi Write during setting unit Default Title cation Function Adjustment range running Speed Torque Reference (Panel/Communi setting control control control cation) Preset speed operation  0287 ~...
  • Page 273 [12] Tripless intensification setup [2/2] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Reference Speed Torque setting running control (Panel/Communi control control cation) Parameter is changeable, but fixed to 0:Without voltage compensation (limitless output voltage) "with voltage compensation"...
  • Page 274 [14] Functions for lift [1/2] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque Reference (Panel/Communi setting running control control control cation)  0324 Drooping output filter 0.1~200.0 rad/s (Enabled if =3, 4, 7 or 8) 0.1/0.1 100.0...
  • Page 275 [14] Functions for lift [2/2] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Reference Speed Torque setting running control (Panel/Communi control control cation) 0:Disabled  0348 Braking time learning function Enabled ●/●...
  • Page 276 [16] PID control [2/2] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Reference Speed Torque setting running control (Panel/Communi control control cation) 0:Deviation input (no feedback input) 1:VI/II (voltage/current input) 2:RR/S4 (potentiometer/voltage input) PID control feedback control ...
  • Page 277 [18] Motor constant Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range V/f Constant Reference Speed Torque setting running control (Panel/Communi control control cation) 0:No auto-tuning 1:Initialize motor constant (0 after execution) 2:Continue operation continued after auto-tuning (0 ...
  • Page 278 [19] Torque control [2/2] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range V/f Constant Reference Speed Torque (Panel/Communi setting running control control control cation) Load sharing gain input ...
  • Page 279 [20] Torque limit [2/2] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range V/f Constant Reference Speed Torque setting running control (Panel/Communi control control cation) Regenerative braking torque 0445 0.0~249.9%, 250.0:Disabled 0.1/0.01 250.0...
  • Page 280 [21] Adjustment parameters [2/2] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque V/f Constant Reference (Panel/Communi setting running control control control cation) 0469 Overvoltage limit constant 0: Automatic, 1~1000ms Disabled ●...
  • Page 281 [22] Acceleration/deceleration 2 [2/2] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range V/f Constant Reference Speed Torque setting running control (Panel/Communi control control cation) Deceleration S-pattern upper 0509 0~50% Enabled ●/●...
  • Page 282 [23] Pattern operation [2/3] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque V/f Constant Reference (Panel/Communi setting running control control control cation)  0537 Pattern group 2 selection 6 0:Skip, 1~15 Disabled ●/●...
  • Page 283 [23] Pattern operation [3/3] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range V/f Constant Reference Speed Torque (Panel/Communi setting running control control control cation) Preset speed operation frequency 0570 Ditto Disabled...
  • Page 284 [25] Protection functions [1/2] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque V/f Constant Reference (Panel/Communi setting running control control control cation)  0601 Stall prevention level 10~164%, 165:Deactivated Enabled ●/●...
  • Page 285 [25] Protection functions [2/2] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range V/f Constant Reference Speed Torque setting running control (Panel/Communi control control cation) 0622 Abnormal speed detection time 0.01~100.0 sec.
  • Page 286 [26] Override Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque V/f Constant Reference (Panel/Communi setting running control control control cation) 0:Disabled 1:VI/II (voltage/current input) 2:RR/S4 (potentiometer/voltage input) 3:RX (voltage input) 4:Operation panel input enabled (including LED/LCD option input)
  • Page 287 [27] Meter output [2/2] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during cation Function Adjustment range V/f Constant Reference Title Speed Torque setting running control (Panel/Communi control control cation) 0:No filter 1:Filter approx. 10ms 2:Filter approx.
  • Page 288 [28] Operation panel parameters [1/3] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque V/f Constant Reference (Panel/Communi setting running control control control cation) Parameter write protect 0:Permit ...
  • Page 289 [28] Operation panel parameters [2/3] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range V/f Constant Reference Speed Torque setting running control (Panel/Communi control control cation) Operation panel frequency 0:Permit ...
  • Page 290 [28] Operation panel parameters [3/3] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque V/f Constant Reference (Panel/Communi setting running control control control cation)  0756 Quick registration parameter 6 0~999 *1 Enabled ●/●...
  • Page 291 (2-wire RS485) 3:Master (sends a frequency command) 4:Master (sends an output frequency) 5.Master (sends a torque command) 6.Master (sends an output torque command) Protocol selection (2-wire 0:TOSHIBA  0807 Enabled ●/● ●/● ● ●...
  • Page 292 [29] Communication function [2/4] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque V/f Constant Reference (Panel/Communi setting running control control control cation) 0:Disconnection detection Communication1 time-out ...
  • Page 293 RS485) 3:Master (sends a frequency command) 4:Master (sends an output frequency) 5:Master (sends a torque command) 6:Master (sends an output torque command) Protocol selection (4-wire 0:TOSHIBA 0829 Enabled ●/● ●/● ● ● 6. 39. 1 ...
  • Page 294 [29] Communication function [4/4] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque V/f Constant Reference (Panel/Communi setting running control control control cation) Communication option station  0853 0~255 Enabled...
  • Page 295 [30] My function [1/5] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range V/f Constant Reference Speed Torque setting running control (Panel/Communi control control cation) Input terminal function number 0:Deselect 1:F terminal 2:R terminal...
  • Page 296 [30] My function [2/5] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi Default Write during setting unit Title cation Function Adjustment range V/f Constant Reference Speed Torque (Panel/Communi setting running control control control cation) 0:NOP (not operation) 1:ST (move) 2:STN 3:AND (logical product) 4:ANDN...
  • Page 297 [30] My function [3/5] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range V/f Constant Reference Speed Torque (Panel/Communi setting running control control control cation) 0915 Input function command 33 Same as ...
  • Page 298 [30] My function [4/5] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi Default Write during setting unit Title cation Function Adjustment range V/f Constant Reference Speed Torque (Panel/Communi setting running control control control cation)  0948 Input function command 62 Same as ...
  • Page 299 [30] My function [5/5] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range V/f Constant Reference Speed Torque setting running control (Panel/Communi control control cation) 0:Disabled 1:VI/II 2:RR/S4  0962 Analog input function target 21 3:RX...
  • Page 300 [Contents of monitor displays] Sensorless vector/vector with sensor (●: valid, -: invalid) Unit Meter Communi Monitor output Trip Speed Torque Function (Commun output PM control Reference cation No. selection retention control control ication) selection Standard monitor  Contents of status monitor display FE01 Status (rotation direction) Fixed ○...
  • Page 301 [Monitor FM/AM/pulse output function selection (1/3)] Sensorless vector/vector with sensor ●: valid, -: invalid) FM/AM/pulse output Monitor output Unit Speed Torque Function (Communicat Trip retention PM control Reference Communicati Communicati control control Option No. Option No. ion) on No. on No. FD00 FE00 Output frequency...
  • Page 302 [Monitor FM/AM/pulse output function selection (2/3)] Sensorless vector/vector with sensor (●: valid, -: invalid) FM/AM/pulse output Monitor output Unit Function (Communicat Trip retention Speed control Torque control PM control Reference Communicati Communicati Option No. Option No. ion) on No. on No. Depends on FE76 FE76...
  • Page 303 [Monitor FM/AM/pulse output function selection (3/3)] Sensorless vector/vector with sensor (●: valid, -: invalid) FM/AM/pulse output Monitor output Unit Function (Communicat Trip retention Speed control Torque control PM control Reference Communicati Communicati Option No. Option No. ion) on No. on No. FE71 Rated voltage ×...
  • Page 304 [Input terminal function setting (1/2)] Sensorless vector/vector with sensor (●: valid, -: invalid) Positive Negative Speed Torque Function PM control = = Reference logic logic control control No function is assigned ●/● ●/● ● ● F: Forward run command ●/● ●/●...
  • Page 305 [Input terminal function setting (2/2)] Sensorless vector/vector with sensor (●: valid, -: invalid) Positive Negative Speed Torque Function PM control = = Reference logic logic control control Servo lock signal ●/● ● ● ● Simple positioning (positioning loop) ●/● ● ●...
  • Page 306 [Output terminal function setting (1/3)] Sensorless vector/vector with sensor (●: valid, -: invalid) Positive Negative Function Speed control Torque control PM control Reference logic logic ●/● ●/● ● ● ●/● ●/● ● ● ●/● ●/● ● ● ●/● Acceleration/deceleration completion ●...
  • Page 307 [Output terminal function setting (2/3)] Sensorless vector/vector with sensor (●: valid, -: invalid) Positive Negative Function Speed control Torque control PM control Reference logic logic Inverter healthy output ●/● ●/● ● ● ●/● ●/● RS485 communication error ● ● Error code output 1 (6-bit output) ●/●...
  • Page 308 [Output terminal function setting 3/3] Sensorless vector/vector with sensor (●: valid, -: invalid) Positive Negative Function Speed control Torque control PM control Reference logic logic ●/● ●/● My function output 10 ● ● My function output 11 ●/● ●/● ● ●...
  • Page 309 Standard default settings classified by inverter model (capacity) Torque Base Acc/dec Allowable Motor Motor Motor Display unit boost frequency time Dynamic Inverter side Motor rated Motor voltage PWM Carrier continuous Motor rated Motor rated constant 1 constant 2 constant 3 selection for ...
  • Page 310: Specifications

    E6581442 12. Specifications 12.1 Models and their standard specifications 1) Standard specifications (small/medium capacity types) Item Specification Voltage class 200V class Applicable motor (kW) 0.75 3.7/4.0 18.5 Applicable motor (HP) Type VFAS1- Form 2004PL 2007PL 2015PL 2022PL 2037PL 2055PL 2075PL 2110PM 2150PM 2185PM 2220PM 2300PM 2370PM 2450PM Output capacity (kVA) [Note 1] Output current...
  • Page 311 E6581442 2) Standard specifications (large capacity types) [Note 1] Item Specification Voltage class 200V class Applicable motor (kW) Applicable motor (HP) Type VFAS1- Form 2550P 2750P Output capacity (kVA) [Note 2] Output current Output voltage Three-phase 200V~240V (The maximum output voltage is equal to the input supply voltage.) Overload 150%-1 minute, 165%-2 sec.
  • Page 312 E6581442 3) Common specification Item Specification Control system Sinusoidal PWM control Output voltage adjustment Main circuit voltage feedback control. (Switchable between automatic adjustment/fix/control off) Setting between 0.01 to 500Hz. Default max. frequency is set to 0.01 to 60Hz. Output frequency range Maximum frequency adjustment (30 to 500Hz) Minimum setting steps of 0.01Hz: operation panel input (60Hz base),...
  • Page 313 E6581442 (Continued) Item Specification Stall prevention during operation, overload limit, overload, undervoltage on power source side, DC circuit Alarms undervoltage, setting error, in retry, upper limit, lower limit. Overcurrent, overvoltage, overheat, short circuit on the load side, ground fault on the load side, inverter overload, arm overcurrent at starting, overcurrent on the load side at starting, CPU error, EEPROM error, Causes of RAM error, ROM error, communication error, (dynamic braking resistor overcurrent/overload),...
  • Page 314: Outside Dimensions And Weight

    E6581442 12.2 Outside dimensions and weight  Outside dimensions and weight Applicable Applicable Dimensions (mm) Approx. Voltage motor motor Inverter type Drawing weight class (kW) (HP) (kg) VFAS1-2004PL 0.75 VFAS1-2007PL VFAS1-2015PL VFAS1-2022PL 3.7/4.0 VFAS1-2037PL VFAS1-2055PL VFAS1-2075PL VFAS1-2110PM VFAS1-2150PM 200V 18.5 VFAS1-2185PM VFAS1-2220PM VFAS1-2300PM...
  • Page 315: Outline Drawing

    E6581442  Outline drawing (Installation di m ension) (Installation dimension) Fig. A Fig. B (Installation dimension) (Installation dimension) Fig. C Fig.D (Installation dimension) (Installation dimension) Fig. E Fig. F...
  • Page 316 E6581442 (Installation dimension) (Installation dimension) Fig. G Fig. H (Installation dimension) (Instal l ation di m ension) Fig. I Fig. J...
  • Page 317 E6581442 (Installation dimension) (Installation dimension) Fig. K Fig. L (Installation dimension) (Installation dimension) Fig. M Fig. N...
  • Page 318 E6581442 Braking unit (optional) (Installation dimension) (Installation dimension) Fig. O Braking unit (optional) (Installation dimension) (Installation dimension) Fig. P...
  • Page 319: Before Making A Service Call

    •If this error message appears when a motor is not inverter was damaged. connected to the inverter, the inverter itself may be faulty, so contact your Toshiba distributor. •PB-PC/+ circuit is shorted. •Check the impedance wiring for the resistor, etc.
  • Page 320 (). * Low current operation. •Contact your Toshiba distributor if the setting is correct. •The input voltage (in the main •Check the input voltage. circuit) is too low. •To cope with a momentary stop due to undervoltage, enable ...
  • Page 321 E6581442 (Continued overleaf)
  • Page 322 •A data writing error occurs. •Turn off the inverter, then turn it again. If it does  EEPROM error not recover from the error, contact your Toshiba distributor. •Some internal data is corrupted. •Contact your Toshiba distributor.
  • Page 323 •P24 overcurrent •Check P24 terminal short circuit to CC or CCA. Abnormal •An error arises during CPU2 •Contact your Toshiba distributor.  CPU2 communication. communication • Set Base frequency voltage 1 vlv and Base • Output voltage / Output frequency frequency vl in accordance with motor rating.
  • Page 324 E6581442 (Continued) •Motor control CPU is defective. •Contact your Toshiba distributor. •The drive circuit board in the Internal circuit inverter was damaged.  error •Power device is defective. •Using braking function in not •If the braking function is used, operate a motor in =,,,,...
  • Page 325 E6581442 (Continued) Error Problem Possible causes Remedies code Parameters in •Parameters are being initialized to •Normal if the message disappears after a while  the process of default values. (several seconds to several tens of seconds). initialization •Auto-tuning 1 in process. •Normal if it the message disappears after a few ...
  • Page 326: Method Of Resetting Causes Of Trip

    E6581442 13.2 Method of resetting causes of trip Do not reset the inverter when tripped because of a failure or error before eliminating the cause. Resetting the tripped inverter before eliminating the problem causes it to trip again. For recovering inverter from trip status, (1) By turning off the power (Keep the inverter off until the LED turns off.) ...
  • Page 327: If The Motor Does Not Run While No Trip Message Is Displayed

    E6581442 13.3 If the motor does not run while no trip message is displayed... If the motor does not run while no trip message is displayed, follow these steps to track down the cause. YES : The motor does not run. NO : Is power being Supply the power...
  • Page 328: How To Check Other Troubles

    E6581442 13.4 How to check other troubles The following table provides a listing of other troubles, their possible causes and remedies. Troubles Causes and remedies The motor runs in the •Invert the phases of the output terminals U, V and W. wrong direction.
  • Page 329: Inspection And Maintenance

    E6581442 14. Inspection and maintenance Warning • The equipment must be inspected frequently. If the equipment is not inspected and maintained, errors and malfunctions may not be discovered which could lead to accidents. Mandatory • Before inspection, perform the following steps. (1) Shut off all input power to the inverter.
  • Page 330: Periodical Inspection

    E6581442 14.2 Periodical inspection Make a periodical inspection at intervals of 3 or 6 months depending on the operating conditions. Warning • Before inspection, perform the following steps. (1) Shut off all input power to the inverter. (2) Wait at least 15 minutes and check to make sure that the charge lamp is no longer lit. Mandatory (3) Use a tester that can measure DC voltages (800VDC or more), and check that the voltage to the DC main circuits (between PA/+ and PC/-) does not exceed 45V.
  • Page 331 By checking the cumulative operating time and the part replacement alarm information, you can get a rough idea of when each part should be replaced. For the replacement of parts, contact the service network or your Toshiba distributor. (Operation hours can be known by alarm output, if it is set. For more details, refer to Section 6.33.12.) ...
  • Page 332: Making A Call For Servicing

    14.3 Making a call for servicing For the Toshiba service network, refer to the back cover of this instruction manual. If defective conditions are encountered, please contact the Toshiba service section in charge via your Toshiba dealer. When making a call for servicing, please inform us of the contents of the rating label on the right panel of the inverter, the presence or absence of optional devices, etc., in addition to the details of the failure.
  • Page 333: Warranty

    • Failure or damage caused by the use of the inverter for any purpose or application other than the intended one 4. All expenses incurred by Toshiba for on-site services shall be charged to the customer, unless a service contract is signed beforehand between the customer and Toshiba, in which case the service contract has priority over this warranty.
  • Page 334: Disposal Of The Inverter

    E6581442 16. Disposal of the inverter Caution • For safety's sake, do not dispose of the disused inverter yourself but ask an industrial waste disposal agent (*). If the collection, transport and disposal of industrial waste is done by someone who is not Mandatory licensed for that job, it is a punishable violation of the law.

Table of Contents