Rinnai E110CN Installation & Servicing Instructions Manual page 27

High efficiency condensing gas boiler
Table of Contents

Advertisement

6.7.2 b
Examples vent and air supply systems (parallel)
Horizontal with concentric termination
Vertical vent and horizontal air intake
Wall thickness for vent termination installation:
Minimum:
100mm / 4"
Maximum:
508mm / 20"
figure 11A
Vertical with concentric termination
figure 11C
Examples sealed combustions
Horizontal with parallel termination
12" OVER
MAXIMUM
SNOW LEVEL
OR 24"
WHICHEVER IS
GREATER
Vertical with parallel termination
figure 11D
figure 11B
10" MINIMUM INSIDE EDGE
T`O INSIDE EDGE
figure 11E
27