Control Selection Guide - Carrier 42 SERIES Application Data

Fan coil units control selection guide for fan coil air conditioners
Table of Contents

Advertisement

Use this guide to make sure that all necessary components are provided for and that the components are compatible
with the required control system.
NOTE: When thermostatic fan control is selected or when unit outside air dampers are used, unit-mounted thermostats
are not recommended as their use will result in poor room temperature sensing.
SYSTEM
DESCRIPTION
Fan
Fan manually cycled
Control
(2-Pipe)
Thermostat cycles fan on-off
from speed set with
fan switch.
Thermostat cycles fan on-off
from fan speed set
with switch. Mode
automatically switched
by changeover
sensing water temp.
Thermostat cycles fan from
high to low on cooling
and low to off on heating.
Two-
Thermostat cycles valve
position
open or closed.
electric
valves
Thermostat cycles valve
(2-pipe)
open or closed.
Mode automatically
switched by changeover
sensing water temp.
Pneumatic
Thermostat modulates
modulating
pneumatic control valve.
valves
(2-pipe)
Two-
Thermostat cycles valve
position
open or closed. 2° F after
electric
valve closes, thermostat
valve with
activates electric heater.
Auxiliary
Heater can't turn on
Electric
if hot water is in coil.
Heat
Thermostat cycles valve
(2-pipe)
open or closed. Manual
changeover switch
changes thermostat to
heat to activate electric
heater.
Two-
Thermostat cycles valve
position
open or closed.
electric
Manual changeover switch
valve with
changes thermostat to heat
total
to activate electric heater.
electric
Thermostat cycles valve
heat
open or closed.
(2-pipe)
2° F after valve closes,
thermostat activates
electric heater.
Pneumatic
Thermostat modulates
modulating
pneumatic control valve.
valves
After changeover,
(2-pipe)
thermostat
activates electric heater.
Two-
Thermostat cycles
position
cooling and heating
electric
valves open or closed.
valves
(4-pipe)
Thermostat cycles cooling
valve open or closed. 2° F
after valve closes,
thermostat cycles
heating valve open or closed.
Pneumatic
Thermostat modulates
modulating
cooling valve.
valves
After changeover,
(4-pipe)
thermostat modulates
heating valve.
*If system is HEATING-ONLY or COOLING-ONLY, no changeover or bypass is required.
NOTE: Unit-mounted thermostats are not recommended with either fan-cycle control or applications with outside air dampers.

CONTROL SELECTION GUIDE

CHANGEOVER
THERMOSTAT
ON
SUPPLY PIPE
None
None
Wall mounted
None
includes heat-cool
switch.
Wall mounted.
Yes
Heating/cooling
Thermostat
Wall or unit
Yes
mounted
Wall mounted
None
includes heat-cool
switch.
Wall or unit
Yes
mounted.
Heating/cooling
Thermostat
By others.
By others.
Wall or unit
Yes.
mounted. Sequenced
Two Required.
heating and cooling.
Wall mounted
None
includes heat-cool
switch.
Wall mounted
None
includes heat-cool
switch.
Wall or unit
None
mounted.
Sequenced heating
and cooling
By others.
By others.
Wall mounted
None
includes subbase
with heat-cool
switch.
Wall or unit
None
mounted.
Sequenced heating
and cooling.
By others.
By others.
3
FAN
VALVE
SWITCH (SW)
None
Standard
3-Speed SW
None
Thermostat has
integral
3-Speed SW
None
Standard
3-Speed SW
None
No Standard
3-Speed Switch,
ON-OFF toggle SW
only
Motorized (N.C.)
Thermostat
3-way or 2-way,
has integral
no bypass required.
3-Speed SW
Motorized (N.C.)
Standard
3-way or 2-way
3-Speed SW.
Others have
thermostats with
integral 3-Speed SW
2- and 3-way
Standard
furnished by others.
3-Speed SW
Can be equipped
with factory
assembled
valve package.
Motorized
Standard
3-way or 2-way
3-Speed SW
Others have
thermostats with
integral 3-Speed SW
Motorized
Thermostat
3-way or 2-way,
has integral
no bypass required
3-Speed SW
Motorized (N.C.)
Thermostat
3-way or 2-way,
has integral
no bypass required
3-Speed SW
Motorized (N.C.)
Standard
3-way or 2-way,
3-Speed SW
no bypass required
2- and 3-way
Standard
furnished by others.
3-Speed SW
Can be equipped
with factory
assembled
valve package.
Motorized (N.C.)
Thermostat
3-way or 2-way
has integral
(requires 2 valves)
3-Speed SW
Motorized (N.C.)
Standard
3-way or 2-way
3-Speed SW.
(requires 2 valves)
Others have
thermostats
with integral
3-Speed SW
2- or 3-way
Standard
furnished by others.
3-Speed SW
Can be equipped
with factory
assembled
valve package.
NOTES
Not recommended
for high humidity
application
Unit mounted
thermostats provide
very poor room
temperature control
Best fan cycle
control for
high humidity
applications
Valve packages
with belled end(s)
for field soldering
to coil.
Factory assembled
in valve package
w/flare nuts.
Valve packages
with belled end(s)
for field soldering
to coil.
Valve packages
with belled end(s)
for field soldering
to coil.
Valve packages
with belled end(s)
for field soldering
to coil.
Valve packages
with belled end(s)
for field soldering
to coil.
Factory assembled
in valve package
w/flare nuts.
Valve packages
with belled end(s)
for field soldering
to coil.
Valve packages
with belled end(s)
for field soldering
to coil.
Factory assembled
in valve package
w/flare nuts.
Valve packages
include unions for
for field assembly
to coil.