ASSURE GAS PIPING IS LEAK FREE
AND OF PROPER SIZE and type for the
connected load.
SHUT OFF MAIN GAS SUPPLY prior to
installing or servicing boiler gas piping.
Determine the boiler's maximum gas
1.
demand and minimum gas supply pressure
(printed on the boiler's rating label) and the
demand of other gas appliances served by
the same gas meter.
Ensure that gas piping, fittings, and gas
2.
meter capacities can supply the maximum
gas demand of all appliances at pressures
above their minimum allowable gas
pressure. Tables C-1 and C-2 provide typical
capacities of gas pipes and fittings.
Derate the gas flow through pipes by
3.
multiplying by a correction factor in Table
C-3 based on the specific gravity of the gas.
For materials or conditions other than those
4.
listed above, refer to the National Fuel Gas
Table C-1: Maximum Capacity of Schedule 40 Pipe in Cubic Feet Per Hour (CFH)
Length
(Feet)
½
10
132
20
92
30
73
40
63
50
56
60
50
70
46
80
43
90
40
100
38
*
1 CFH of Natural Gas is approximately equal to 1000 BTU/hr; 1 CFH of LP is approximately equal to 2500 BTU/hr.
Table C-2: Equivalent Lengths (ft) Of Standard Pipe Fittings & Valves
Pipe
Gate
Size
½"
0
¾"
0
1"
1
1 ¼"
1
1 ½"
1
36
APPENDIX C – GAS PIPING
0.3" w.c. Pressure Drop
¾
1
278
520
190
350
152
285
130
245
115
215
105
195
96
180
90
170
84
160
79
150
Swing
Globe
Angle
Check
19
9
23
12
29
15
39
20
45
22
11
Table C-3: Specific Gravity Correction Factors For
Natural Gas
Specific
Gravity
0.50
0.55
0.60
0.65
0.70
0.75
0.80
Code, NFPA54/ANSI Z223.1, or size the
system using standard engineering methods
acceptable to authority having jurisdiction.
USE PROPER THREAD COMPONENTS
on all gas connectors.
USE THREAD (JOINT) COMPOUNDS
(pipe dope) rated for liquefied petroleum
gas.
½
1050
175
730
120
590
97
500
82
440
73
400
66
370
61
350
57
320
53
305
50
90°
45°
Elbow
Elbow
4
2
1
5
2
1
7
3
1
9
4
2
5
3
Correction
Specific
Factor
Gravity
1.10
0.85
1.04
0.90
1.00
1.00
0.96
1.10
0.93
1.20
0.90
1.30
0.87
1.40
*
0.5" w.c. Pressure Drop
¾
1
360
680
250
465
200
375
170
320
151
285
138
260
125
240
118
220
110
205
103
195
90° 'T', Flow
90° 'T', Flow
Through Run
Through Branch
1
1
2
2
3
Correction
Factor
0.81
0.82
0.78
0.74
0.71
0.68
0.66
1400
950
770
660
580
530
490
460
430
400
3
4
5
7
8