Table 2a: Rating Data - Models aLP080 thru aLP99 (0 to 2000 Feet Elevation above Sea Level)
alpine Series gas-Fired Boilers
Input
(MBH)
* Model
Number
Min. Max.
ALP080
16
80
ALP105
21
105
ALP150
30
150
ALP210
42
210
ALP285
57
285
ALP399
80
399
Add Suffix "N" for Natural Gas or Suffix "P" for LP Gas Models.
*
notes: ** DOE Heating Capacity (ALP080 thru ALP285); Gross Output (ALP399)
Maximum Working Pressure, Water - 30 PSI Shipped from Factory (std.); 50 PSI - Optional (ALP080 thru ALP285)
Maximum Working Pressure, Water - 50 PSI Shipped from Factory (std.); (ALP399)
Maximum Allowable Temperature, Water - 210°F
Boilers are factory shipped as Natural Gas builds and have to be field adjusted for LP gas application. Refer to 'System Start-
Up Section of this manual for detailed procedure.
Ratings shown are for installations at sea level and elevations up to 2000 Feet. For elevations above 2000 Feet, ratings should be
reduced at the rate of four percent (4%) for each 1000 Feet above sea level.
Table 2B: Rating Data - Models aLP080 thru aLP99 (2001 to 000 Feet Elevation above Sea Level)
alpine Series gas-Fired Boilers
Input
(MBH)
Model
Number *
Min. Max.
ALP080
27
80
ALP105
35
105
ALP150
50
150
ALP210
70
210
ALP285
57
285
ALP399
80
399
Add Suffix "N" for Natural Gas or Suffix "P" for LP Gas Models.
*
notes: ** DOE Heating Capacity (ALP080 thru ALP285); Gross Output (ALP399)
Maximum Working Pressure, Water - 30 PSI Shipped from Factory (std.); 50 PSI - Optional
Maximum Allowable Temperature, Water - 210°F
Boilers are factory shipped as Natural Gas builds and have to be field adjusted for LP gas application. Refer to 'System Start-
Up Section of this manual for detailed procedure.
For elevations above 2000 Feet, ratings should be reduced at the rate of four percent (4%) for each 1000 Feet above sea level.
Net I=B=R
** Output
Ratings
(MBH)
Water (MBH)
73
63
96
83
138
120
194
169
265
230
377
328
Net I=B=R
** Output
Ratings
(MBH)
Water (MBH)
73
63
96
83
138
120
194
169
265
230
377
328
Thermal
AFUE
Combustion
Efficiency
Efficiency (%)
%
(%)
95
95
95
95
95
94.1
Thermal
AFUE
Combustion
Efficiency
Efficiency (%)
%
(%)
95
95
95
95
95
94.1
Boiler Water
Volume
(Gal.)
0.6
0.7
1.3
1.7
2.4
94.5
3.4
Boiler Water
Volume
(Gal.)
0.6
0.7
1.3
1.7
2.4
94.5
3.4
Heat Transfer
Area
(Sq. Ft.)
7.3
9.1
16.4
21.8
29.1
41.8
Heat Transfer
Area (Sq. Ft.)
7.3
9.1
16.4
21.8
29.1
41.8