Honeywell MasterLogic 50 Series Installation Manual

Analog output module

Advertisement

Quick Links

MasterLogic-50 Series
Analog Output Module
MLF-DV04A
MLF-DC04A
Installation Manual
10-23-43-07-EN
May 2014
10310000839 Printed in Korea
For more information on MasterLogic PLCs , contact your nearest Honeywell office
Australia
Japan
Philippines
Honeywell Ltd.
Honeywell Inc.
Honeywell Systems (Philippines) Inc.
Phone : (61) 2-9353-7000
Phone: (81) 3-6730-7149
Phone: (63) 2-633-2830/31
Fax : (61) 7-3840-6488
Fax: (81) 3-6730-7228
Fax: (63) 2-638-4013
Indonesia
South Korea
Singapore
PT Honeywell Indonesia
Honeywell Co., Ltd.
Honeywell Pte Ltd.
Phone: (62) 21-535-8833
Phone : (82) 2-799-6114
Phone: (65) 6355-2828
Fax: (62) 21-536-71008
Fax : (82) 2-792-9015
Fax: (65) 6445-3033
India
Malaysia
Thailand
Honeywell Automation India Limited.
Honeywell Engineering Sdn Bhd.
Honeywell System (Thailand) Ltd.
Phone: (91) 20-6603-9400
Phone: (603) 7958-4988
Phone: (662) 693-3099
Fax : (91) 20-6603-9800
Fax: (603) 7958-8922
Fax: (662) 693-3085
Taiwan
New Zealand
For Countries (SE Asia) Listed
Honeywell Taiwan Ltd.
Honeywell Ltd.
below, call Honeywell Singapore
Phone : (886) 2-2245-1000
Phone: (64) 9-623-5050
Office
Fax : (62) 2-2245-3243
Fax: (64) 9-623-5060
Pakistan, Cambodia, Laos, Myanmar,
Vietnam and East Timor
For Countries Listed below,
call Honeywell India Office
Bangladesh, Nepal, and Sri Lanka
Honeywell offers a complete portfolio of products and solutions for process and machine control applications,
including controllers, recorders, transmitters, actuators, smart sensors, and analytical instruments. To learn more
about these offerings and how they can help your organization achieve breakthrough results, contact your local
Honeywell representative, or contact us at the following phone numbers:
U.S.A.: 1-800-784-3011
France: 33 1 60 19 80 75
Canada: 1-800-461-0013
Italy: 39 02 9214 6503
UK: 44 1344 655251
Spain: 34 91313.61.00
Germany: 49 69 8064-336
Asia/Pacific: 65 6355 2828
Latin America: 1-305-805-8188
Honeywell Process Solutions
HPS-FP Asia Pacific
Honeywell Building
17 Changin Business Park Central 1
Singapore 486073
www.honeywell.com/ps
10310000839 Printed in Korea
Safety Precautions
► Safety Precautions is for using the product safe and correct in order to prevent the
accidents and danger, so always follow the instructions.
► The precautions explained here only apply to the MLF-DV04A/DC04A(Analog output
module). For safety precautions on the PLC system, refer to the MasterLogic-50 CPU
User‟s manual.
► The precautions are divided into 2 sections, „Warning‟ and „Caution‟. Each of the meanings
is represented as follows.
If violated instructions, it can cause death, fatal injury or
Warning
considerable loss of property.
If violated instructions, it can cause a slight injury or slight loss
Caution
of products.
► The symbols which are indicated in the PLC and User‟s Manual mean as follows
This symbol means paying attention because of danger of injury, fire, or malfunction.
This symbol means paying attention because of danger of electrical shock.
► Store this datasheet in a safe place so that you can take it out and read it whenever
necessary. Always forward it to the end user.
► Store this datasheet in a safe place so that you can take it out and read it
whenever necessary. Always forward it to the end user.
Warning
Do not contact the terminals while the power is applied.
Risk of electric shock and malfunction.
Protect the product from being gone into by foreign metallic matter.
Risk of fire, electric shock and malfunction.
Do not charge, heat, short, solder and break up the battery.
Risk of injury and fire by explosion and ignition.
Caution
Be sure to check the rated voltage and terminal arrangement for the
module before wiring work.
Risk of electric shock, fire and malfunction.
Tighten the screw of terminal block with the specified torque range.
If the terminal screw looses, it can cause fire and electric shock.
Use the PLC in an environment that meets the general specifications
contained in this datasheet.
Risk of electrical shock, fire, erroneous operation and deterioration of the PLC.
Be sure that external load do not exceed the rating of output module.
Risk of fire and erroneous operation.
Do not use the PLC in the environment of direct vibration.
Risk of electrical shock, fire and erroneous operation.
Do not disassemble, repair or modify the PLC.
Risk of electrical shock, fire and erroneous operation
.
When disposing of PLC and battery, treat it as industrial waste.
Risk of poisonous pollution or explosion.
Precautions for use
► Do not Install other places except PLC controlled place.
► Make sure that the FG terminal is grounded with class 3 grounding which is dedicated to
the PLC. Otherwise, it can cause disorder or malfunction of PLC
PLC
Others
PLC
Others
PLC
Others
< Best >
< Good >
< Bad >
► Connect expansion connector correctly when expansion module are needed.
► Do not detach PCB from the case of the module and do not modify the module.
► Turn off power when attaching or detaching module.
► Cellular phone or walkie-talkie should be farther than 30cm from the PLC.
► Input signal and communication line should be farther than minimum 100mm from a high-
tension line and a power line in order not to be affected by noise and magnetic field.
Before handling the product
Before using the product, read the datasheet and the User‟s manual through to the end
carefully in order to use the product efficiently.
MasterLogic-50 Series User's Manual
Name
Code
MasterLogic-50 User‟s manual(Programming software)
10310000512
MasterLogic-50 Basic Instruction & Programming User‟s manual
10310000510
1. Introduction
Analog output module designed for
series is used to convert the digital
MasterLogic-50
value of signed 12 bit binary data to analog signal.
2. General Specifications
No
Item
Specifications
1
Operating temp.
0℃∼+55℃
2
Storage temp.
-25℃∼+70℃
Operating
3
5∼95%RH (Non-condensing)
humidity
4
Storage humidity
5∼95%RH (Non-condensing)
For discontinuous vibration
Frequency
Acceleration Amplitude
Number
10≤f< 57 ㎐
-
0.075mm
57≤f≤150 ㎐
2
9.8m/s
(1G)
-
Each 10
5
Vibration
For continuous vibration
times in
Frequency
Acceleration Amplitude
X,Y,Z
10≤f< 57 ㎐
directions
-
0.035mm
2
57≤f≤150 ㎐
4.9m/s
(0.5G)
-
* Max. impact acceleration:147 ㎨(15G)
* Authorized time :11 ㎳
6
Shocks
* Pulse wave : Sign half-wave pulse
(Each 3 times in X,Y,Z directions)
Square wave impulse noise
±1,500V
Voltage : 4kV
Electrostatic discharging
(contact discharging)
Radiated electromagnetic field
27 ~ 500MHz, 10 V/m
7
Noise
noise
Fast
Digital/Analog I/O
Power
Class
communication
Transient
module
/burst
interface
noise
Voltage
2kV
1 kV
Ambient
8
No corrosive gas or dust
conditions
9
Operating height
2000m or less
10
Pollution degree
2 or less
11
Cooling method
Self-cooling
3. Performance Specifications
Specifications
Item
XBF-DV04A
Type
Voltage
Analog
DC 0 ~ 10V
output
Range
(Load resistance: 2kΩ or more)
Type
Signed 12 bit binary data
Unsigned value
0 ~ 4000
Digital
Singed Value
-2000 ~ 2000
input
Precise Value
0 ~ 1000
Percentile Value
0 ~ 1000
2.5 ㎷(1/4000)
Max. resolution
Accuracy
Max. conversion speed
Absolute max. output
DC ±15V
Output channel
Photo-coupler insulation between output terminal and
Insulation method
PLC power (no insulation between channels)
Terminal connected
11 Point terminal
I/O occupied points
Fixed point assignment: 64 Point
110 ㎃
Consumed
Internal(DC 5V)
70 ㎃
current
External(DC24V)
Weight
64g
Standard
Remark
▶ Format of input data can be set through applicable program or parameters for respective
channels
▶ When Analog output module is released from the factory, Offset/Gain value is as
adjusted for respective analog output ranges, which is unavailable for user to change.
4. Parts Names and Descriptions
MLF-DV04A
XBF-DV04A
RUN
IEC61131-2
IEC61131-2
CH0
CH1
CH2
IEC61131-2
CH3
IEC61000-4-2
IEC61131-2,
IEC61000-4-3
IEC61131-2
IEC61000-4-4
No.
Description
RUN LED
Displays the operation status
On: Operation normal
Blink: Error occurs
Off: DC 5V disconnected, Module error
Analog output(voltage, current) terminal
Analog output(voltage, current) terminal, whose respective channels can be
connected with external devices
External power input terminal
External power input terminal supplied DC 24V for analog output(voltage, current)
XBF-DC04A
Current
DC 4 ~ 20 ㎃
DC 0 ~ 20 ㎃
(Load resistance: 510Ω or less)
0 ~ 4000
-2000 ~ 2000
400 ~ 2000/0 ~ 2000
0 ~ 1000
5 ㎂(1/4000)
±0.5% or less
1 ㎳/Channel
DC +25 ㎃
4 Channel
110 ㎃
120 ㎃
70g
MLF-DC04A
XBF-DC04A
RUN
CH0
CH1
CH2
CH3

Advertisement

loading

Summary of Contents for Honeywell MasterLogic 50 Series

  • Page 1 IEC61000-4-3 call Honeywell India Office Risk of poisonous pollution or explosion. Bangladesh, Nepal, and Sri Lanka Fast Digital/Analog I/O Honeywell offers a complete portfolio of products and solutions for process and machine control applications, Power Class communication Transient IEC61131-2 including controllers, recorders, transmitters, actuators, smart sensors, and analytical instruments. To learn more...