Download Print this page
Pentair ERICO CRITEC TSF Series Instruction Sheet

Pentair ERICO CRITEC TSF Series Instruction Sheet

Transient surge filter

Advertisement

Quick Links

INSTRUCTION SHEET
Transient Surge Filter
ERICO CRITEC TSF Series
1. Preparation
Electrical shock or burn hazard.
Installation of this Transient Surge
Filter should only be made by
qualified personnel. Failure to lockout electrical power
during installation or maintenance can result in fatal
electrocution or severe burns. Before making any
connections to the electrical panel, be sure that power
has been removed from all associated wiring, electrical
panels, and other electrical equipment.
1.
The installation of this surge filter should be
installed in accordance with all applicable codes,
such as the National Electrical Code (NEC
Canadian Electrical Code.
2.
Check to make sure line voltage does not exceed
surge filter voltage requirement. Prior to installation
ensure that the TSF is of the correct voltage,
current, and frequency rating for your application.
3.
The ground / earth terminal must be connected to a
low impedance earth for correct operation.
4.
Do not perform a "Dielectric Withstand" or use a
Mega-Ohm Meter (Megger) to test circuits that are
protected with TSF units. Damage may occur to the
TSF units.
5.
Follow all instructions to ensure correct and safe
operation.
6.
Do not attempt to open or tamper with TSF units in
any way as this may compromise performance and
will void warranty.
WARNING:
1.
Pentair products shall be installed and used only as indicated in Pentair product instruction sheets and training materials. Instruction sheets are available at
www.erico.pentair.com and from your Pentair customer service representative.
2.
Pentair products must never be used for a purpose other than the purpose for which they were designed or in a manner that exceeds specified load ratings.
3.
All instructions must be completely followed to ensure proper and safe installation and performance.
4.
Improper installation, misuse, misapplication or other failure to completely follow Pentair's instructions and warnings may cause product malfunction, property
damage, serious bodily injury and/or death, and void your warranty.
SAFETY INSTRUCTIONS:
All governing codes and regulations and those required by the job site must be observed.
Always use appropriate safety equipment such as eye protection, hard hat, and gloves as appropriate to the application.
NEC is a registered trademark of, and National Electrical Code (NEC) standard is a copyright of the National Fire Protection Association, Inc. UL, UR, cUL, cUR,
cULus and cURus are registered certification marks of UL LLC.
Pentair, CADDY, ERICO CADWELD, ERICO CRITEC, ERICO, ERIFLEX, and LENTON are owned by Pentair or its global affiliates. All other trademarks are
the property of their respective owners. Pentair reserves the right to change specifications without prior notice.
TECHNICAL SUPPORT
www.erico.pentair.com
, or the
®)
IP8276_E
1 OF 2
© 2016 Pentair All Rights Reserved
Table 1: Model and Plug-in Module Part Number
2. Introduction
Transient Surge Filters (TSF) are designed for simple
installation onto 35mm DIN rails. They can be selected
for use on distribution systems with nominal RMS
voltages of 120V or 240V at frequencies of 50/60Hz.
The TSF6A24V unit is suitable for 12V and 24Vac/dc
signaling and control systems.
3. Quick Installation Overview
Install in the following manner:
1.
Ensure that power is removed from the area and
the circuits that will be connected.
2.
Snap lock the TSF module to the DIN rail.
3.
Install the appropriate upstream overcurrent
protection (refer to Section 8)
4.
Connect wiring to the indicated input and output
terminals.
4. Protection Concepts
The terminals on the TSF units are labeled
"INPUT/LINE" (unprotected side) and "OUTPUT/LOAD"
(protected side) assuming that the source of the
transients is on the input side of the TSF module.
To optimize effectiveness of the TSF protection, the
unprotected and protected wiring should be separated.
Wiring from the exposed transient source to the TSF
should be considered unprotected and kept
approximately 12" (300mm) from all other wiring
wherever possible. Wiring on the equipment side of the
TSF should be considered protected.
The separation of protected and unprotected wiring is
recommended to minimize the risk that transients on
unprotected wiring may cross couple onto protected
circuits and diminish the level of protection available
from the TSF module.

Advertisement

loading

Summary of Contents for Pentair ERICO CRITEC TSF Series

  • Page 1 Pentair customer service representative. Pentair products must never be used for a purpose other than the purpose for which they were designed or in a manner that exceeds specified load ratings. All instructions must be completely followed to ensure proper and safe installation and performance.
  • Page 2 Figure 3: Remote Alarm Contacts Pentair, CADDY, ERICO CADWELD, ERICO CRITEC, ERICO, ERIFLEX, and LENTON are owned by Pentair or its global affiliates. All other trademarks are the property of their respective owners. Pentair reserves the right to change specifications without prior notice.

This manual is also suitable for:

Erico critec tsf6a24vErico critec tsf6a120vErico critec tsf6a240vErico critec tsf20a120vErico critec tsf20a240v