York PREDATOR R-410A Technical Manual page 95

R-410a zh/zr/xp series 6-1/2 - 12-1/2 ton 60 hertz
Table of Contents

Advertisement

ZR078-150 Standard Motor - With Powered Convenience Outlet (Continued)
Compressors
(each)
Size
Volt
(Tons)
RLA LRA
MCC
208
17.9 120.0 28.0
230
17.9 120.0 28.0
120
(10)
460
9.6
70.0
15.0
575
7.4
53.0
11.5
208
23.1 160.0 36.0
230
23.1 160.0 36.0
150
(12.5)
460
12.2
87.0
19.0
575
8.7
62.0
13.5
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
Johnson Controls Unitary Products
OD Fan
Supply
Pwr
Pwr
Motors
Blower
Exh
Conv
(each)
Motor
Motor
Outlet
FLA
FLA
FLA
FLA
1.5
8.2
5.5
10.0
1.5
8.2
5.5
10.0
0.8
4.1
2.2
5.0
0.6
3.6
1.8
4.0
1.5
10.9
5.5
10.0
1.5
10.9
5.5
10.0
0.8
5.3
2.2
5.0
0.6
4.1
1.8
4.0
Electric Heat Option
Model
kW
Stages Amps
None
-
-
-
E18
13.5
2
37.5
E24
18.0
2
50.0
E36
25.5
2
70.8
E54
40.6
2
112.7
None
-
-
-
E18
18.0
2
45.2
E24
24.0
2
60.2
E36
34.0
2
85.3
E54
54.0
2
135.6
None
-
-
-
E18
18.0
2
22.6
E24
24.0
2
30.1
E36
34.0
2
42.7
E54
54.0
2
67.8
None
-
-
-
E18
18.0
2
18.1
E24
24.0
2
24.1
E36
34.0
2
34.1
E54
54.0
2
54.2
None
-
-
-
E18
13.5
2
37.5
E24
18.0
2
50.0
E36
25.5
2
70.8
E54
40.6
2
112.7
None
-
-
-
E18
18.0
2
45.2
E24
24.0
2
60.2
E36
34.0
2
85.3
E54
54.0
2
135.6
None
-
-
-
E18
18.0
2
22.6
E24
24.0
2
30.1
E36
34.0
2
42.7
E54
54.0
2
67.8
None
-
-
-
E18
18.0
2
18.1
E24
24.0
2
24.1
E36
34.0
2
34.1
E54
54.0
2
54.2
246824-YTG-G-1208
1
MCA
Max Fuse
1
MCA
w/Pwr
Breaker
(Amps)
Exh
Size
(Amps)
(Amps)
61.5
67.0
70
69.6
76.5
70
85.2
92.1
90
111.2
118.1
125
163.6
170.5
175
61.5
67.0
70
76.9
83.8
80
94.9
101.8
100
125.0
131.9
125
152.7
159.5
175
32.3
34.5
40
38.4
41.2
40
47.5
50.2
50
62.5
65.2
70
76.3
79.1
90
25.5
27.3
30
31.2
33.4
35
38.4
40.6
40
50.4
52.6
60
61.5
63.7
70
78.9
84.4
100
78.9
84.4
100
88.6
95.5
100
114.6
121.5
125
167.0
173.9
175
78.9
84.4
100
80.3
87.1
100
98.3
105.2
100
128.4
135.2
150
156.0
162.9
175
41.0
43.2
50
41.0
43.2
50
49.0
51.7
50
64.0
66.7
70
77.8
80.6
90
30.1
31.9
35
31.8
34.0
35
39.0
41.2
40
51.0
53.3
60
62.1
64.3
70
2
Max Fuse
/
2
/
3
Breaker
3
Size w/ Pwr
Exh
(Amps)
80
80
100
125
175
80
90
110
150
175
40
45
60
70
90
30
35
45
60
70
100
100
100
125
175
100
100
110
150
175
50
50
60
70
90
40
40
45
60
70