Zh/Zr/Xp078-150 Unit Limitations - York PREDATOR R-410A Technical Manual

R-410a zh/zr/xp series 6-1/2 - 12-1/2 ton 60 hertz
Table of Contents

Advertisement

ZH/ZR/XP078-150 Unit Limitations

Size
(Tons)
120
(10)
150
(12.5)
Johnson Controls Unitary Products
Model
Unit Voltage
208/230-3-60
ZH/ZR/XP
460-3-60
575-3-60
208/230-3-60
ZH/ZR/XP
460-3-60
575-3-60
Unit Limitations
Applied Voltage
Min
Max
187
252
432
504
540
630
187
252
432
504
540
630
246824-YTG-G-1208
Outdoor DB Temp
Max (°F)
125
125
125
125
125
125