Unit Dimensions; Unit Height; Unit Clearances - York DM090 Installation Manual

Predator single package air conditioners and single package gas/electric units 7-1/2, 10 and 12-1/2 ton (9.0 to 10.0 eer) 50 hz
Hide thumbs Also See for DM090:
Table of Contents

Advertisement

FIGURE 8 -

UNIT DIMENSIONS

TABLE 6: UNIT HEIGHT
Unit Model Number
DM090
DM120
DM150
DETAIL B
TABLE 7: UNIT CLEARANCES
72(1830)
Top
Front
36(915)
36(915)
Rear
*.
In inches and millimeters, in.(mm).
†.
Units must be installed outdoors. Overhanging struc-
ture or shrubs should not obstruct condenser air dis-
charge outlet.
‡.
To remove the slide-out drain pan, a rear clearance of
60" (1525 mm) is required. If space is unavailable, the
drain pan can be removed through the front by separat-
ing the corner wall.
**.
Units may be installed on combustible floors.
12
X
42 (1067)
50 3/4 (1289)
50 3/4 (1289)
*
Right
12(305)
Left
36(915)
**
0(0)
Bottom
NOTE: A one-inch clearance must be provided between
any combustible material and the supply ductwork
for a distance of 3 feet from the unit.
DETAIL C
DETAIL D
NOTE: If the unit includes gas heating, locate the unit so
the flue exhaust is at least:
Three (3) feet above any forced air inlet located within 10
horizontal feet (excluding those integral to the unit).
Four (4) feet below, four (4) horizontal feet from, or one
(1) foot above any door or gravity air inlet into the build-
ing.
Four (4) feet from electric meters, gas meters, regula-
tors, and relief equipment.
127408-YIM-B-0606