Download Print this page

White Rodgers 1F83-0471 Installation And Operating Instructions Manual page 5

80 series thermostat with automatic heat/cool changeover option

Advertisement

INST
INST
INSTALLER/CONFIGURA
ALLER/CONFIGURA
ALLER/CONFIGURATION MENU
ALLER/CONFIGURA
INST
INST
ALLER/CONFIGURA
1) This control can be configured for:
MS 2 – Multi-Stage System (no heat pump)
HP 1 – Heat Pump with one stage of compressor
HP 2 – Heat Pump with two stage compressor or two
compressor system, Gas or Electric backup
SS 1 – Single Stage System
2) GAS or Electric (ELE) fan operation. If the heating system
requires the thermostat to energize the fan, select ELE.
Select GAS if the heating system energizes the fan on a
call for heat.
3) Select Cool Sa
Select Cool Savings™ v
Select Cool Sa
Select Cool Sa
vings™ value
vings™ v
vings™ v
Select Cool Sa
vings™ v
adjustment for the Cool Savings™ feature in Cool mode
with 1 (1°) being the least amount of adjustment and 6 (6°)
being the most amount of adjustment. Default value is 3.
Cool Savings is an optional energy saving feature that can
reduce your cooling costs. It is based on the principal that
lower indoor humidity makes a slightly higher temperature
feel more comfortable. Cool Savings operates during
periods of high demand which normally occur onthe hottest
summer days when a cooling system may run for hours to
reach the thermostat setting. Long cooling run times also
lower the indoor humidity. Cool Savings, very slowly,
adjusts the setpoint temperature to make the setpoint closer
to the displayed room temperature, to a maximum of the
number of degrees you select. Adjusting the setpoint
temperature over a long cooling run time allows the system
to reach your set temperature and turn off. The room
temperature will actually be higher than the thermostat
displays but the reduction in humidity will allow comfort at
the slightly higher temperature.
To turn this feature on in the Cool mode press Cool
ings. The display will show "Sa
ings
ings
ings
ings
temperature. When Cool Savings is making adjustments to
the room temperature display "Sa
the displayed room temperature may vary within the adjust-
ment range you selected.
If "Sa
"Sa
"Sa
"Sav v v v v e" e" e" e" e" is not displayed and this feature is OFF , no
"Sa
change will occur when the cooling system is continuously
running during periods of high demand.
4) Ener
Energ g g g g y Mana
Ener
Ener
Ener
y Manag g g g g ement R
y Mana
y Mana
y Mana
ement Reco
ement R
ement R
ement R
configured to be non-programmable).
Energy Management Recovery (E) On enables the ther-
mostat to start heating or cooling early to make the building
temperature reach the program setpoint at the time you
specify. Heating will start 5 minutes early for every 1° of
temperature required to reach setpoint.
Example
Example
Example
Example: E On is selected and your heating is pro-
Example
grammed to 65° at night and 70° at 7 AM. If the building
temperature is 65°, the difference between 65° and 70° is
5°. Allowing 5 minutes per degree, the thermostat setpoint
will change to 70° at 6:35 AM. Cooling allows more time per
degree, because it takes longer to reach set temperature.
5, 6 & 7) Cycle Rate Selection
Cycle Rate Selection
Cycle Rate Selection
Cycle Rate Selection
Cycle Rate Selection – The factory default setting for
Heat and Cool modes, SS1, MS2, is medium cycle (ME).
For Heat Pump, HP1, HP2, the default setting is medium
(ME). For Emer (Aux) the default setting is fast cycle
(FA).To change cycle rate, press the
Cycle rate differentials for different settings are:
MODE
Heat (SS1, MS2)
Cool (SS1, MS2)
Heat Pump (HP1, HP2)
Emer (HP1, HP2)
Select Compr
Select Compr
essor Lock k k k k out CL OFF or ON
essor Loc
essor Loc
8) Select Compr
Select Compressor Loc
Select Compr
essor Loc
CL ON will cause the thermostat to wait 5 minutes between
cooling cycles. This is intended to help protect the compres-
sor from short cycling. Some newer compressors already
have a time delay built in and do not require this feature.
Your compressor manufacturer can tell you if the lockout
feature is already present in their system. When the
thermostat compressor time delay occurs, it will flash the
TION MENU
TION MENU
TION MENU
TION MENU
alue – Selects the amount of
alue
alue
alue
Cool
Cool
Cool
Cool Sa
"Sa
"Sav v v v v e" e" e" e" e" next to the setpoint
"Sa
"Sa
"Sav v v v v e" e" e" e" e" will be flashing and
"Sa
"Sa
"Sa
eco
eco
ecov v v v v er er er er ery y y y y : (this step is skipped if
eco
or
key.
Fast
Medium
FA
ME
0.4°F
0.6°F
0.9°F
1.2°F
0.9°F
1.2°F
0.6°F
-
out CL OFF or ON
out CL OFF or ON
out CL OFF or ON
out CL OFF or ON – Selecting
setpoint for up to five minutes.
9) System Mode Configur
System Mode Configur
System Mode Configur
System Mode Configura a a a a tion
System Mode Configur
ured for Heat and Cool (SYSTEM switch with Cool Off
Heat) default. It can also be configured for Heat and Cool
with Auto changeover (Heat, Auto, Cool, Off), Heat only
with fan (Off Heat), Heat only without fan, Auto only
(Auto Off), and Cool only (Cool Off).
Select Bac
Select Bac
klight Display y y y y – The display backlight improves
klight Displa
klight Displa
10) Select Bac
Select Bac
Select Backlight Displa
klight Displa
display contrast in low lighting conditions. When the "C"
terminal is powered, selecting backlight CdL ON will keep
the light on continuously. Select backlight OFF will turn the
light on momentarily after any key is pressed. When the
"C" terminal is not powered, the light will be on momen-
tarily after any key is pressed no matter whether the
backlight is selected ON or OFF .
11) Select
Select T T T T T emper
Select
Select
Select
emper
emper
empera a a a a tur
emper
Allows you to adjust the room temperature display up to 4°
higher or lower. Your thermostat was accurately calibrated
at the factory, but you have the option to change the dis-
play temperature to match your previous thermostat. The
current or adjusted room temperature will be displayed.
12) Select F° or C° R
Select F° or C° R
Select F° or C° R
Select F° or C° Readout
Select F° or C° R
to Centigrade or Fahrenheit as required.
13) Pr
Pr Pro o o o o g g g g g r r r r r am Options
Pr Pr
am Options
am Options: 1F85 only, configured for 5/1/1 day or
am Options
am Options
5/2 day programming or non-programming mode.
The default setting is P2, indicating 5/2 day programming.
The programs per week can be toggled to P3 or P0 by
pressing the
non-programmable will eliminate the need for EMR, and
that step in the menu will be skipped.
Sa
Sa
Sav- v- v- v- v-
Sa
14 & 15) Select
Select
Select
Select
Select A A A A A utoma
one touch of the A A A A A uto Sc
you to program a desired comfort temperature into all the
program periods along with a 6° set back for night periods
of both Heat and Cool programs. Factory default is "On" for
Hea
Hea
Heat t t t t AS On
both. When Hea
Hea
while in Heat or Cool mode, select desired setpoint tem-
perature and press A A A A A uto Sc
copied into all the morning, day and evening program
periods. The night program periods will have a 6°F set back.
Select F
Select F
16 & 17) Select F
Select Fast Second Sta
Select F
or Multi-stage only, in the run mode, with the fast Heat
feature enabled (FA Heat On), if the Heat setpoint tem-
perature is manually raised by 3°F (2°C) or more above
the actual temperature using
energize immediately. With FA OFF , second stage will not
energize until the setpoint temperature is 1°F or more
above actual temperature for more than ten minutes. The
Fast Cool feature (FA Cool) provides the same controls
when the setpoint temperature is lowered.
18) Select Da
Select Daylight Sa
Select Da
Select Da
ylight Sa
ylight Sa
ylight Saving
Select Da
ylight Sa
this feature will allow the thermostat to calculate the DST
automatically and apply it to the Real Time Clock display.
Default On. Use
feature OFF .
19) Select Filter R
Select Filter R
Select Filter R
Select Filter Re e e e e placement
Select Filter R
Select the "Chang
Chang
Change Filter
Chang
Chang
ted On, press MENU
1975 hours in 25 hours increments. In a typical system,
Slow
200 hours (default) of run time is approximately 30 days.
SL
After the selected time of blower operation, the thermostat
will display "Chang
Change Filter
Chang
Chang
Chang
1.7°F
clean your air filter. When "Chang
1.7°F
MENU
MENU or R R R R R UN SCHED
MENU
press MENU
MENU
1.7°F
display and restart the time to the next filter change.
1.7°F
20) Select R
Select R
Select Re e e e e v v v v v er er er er ersing
Select R
Select R
sing
sing
sing V V V V V alv
sing
factory set at "O" position. This will accommodate the
majority of heat pump applications, which require the
changeover relay to be energized in COOL. If the thermo-
stat you are replacing or the heat pump being installed with
this thermostat requires a "B" terminal, to energize the
changeover relay in HEAT, the O/B option should be set at
"B" position.
tion – This thermostat is config-
tion
tion
tion
tur
ture Displa
tur
tur
e Displa
e Displa
e Display y y y y Adjustment 4 L
e Displa
Adjustment 4 L
Adjustment 4 L
Adjustment 4 L
Adjustment 4 LO to 4 HI
eadout – Changes the display readout
eadout
eadout
eadout
or
keys. A selection of 0 Days for
utoma
utomatic Sc
utoma
utoma
tic Sc
tic Sc
tic Sc
tic Schedule
hedule
hedule
hedule
hedule – 1F85 only, with just
uto Schedule
uto Sc
uto Sc
uto Sc
hedule
hedule
hedule
hedule key this feature allows
AS On
AS On
Cool
Cool
AS On
AS On
AS On
AS On and Cool
Cool
Cool AS On
AS On are activated
AS On
uto Sc
uto Schedule
uto Sc
uto Sc
hedule. This value will be
hedule
hedule
hedule
ast Second Sta
ast Second Sta
ast Second Stag g g g g e ON or OFF
e ON or OFF
e ON or OFF
ast Second Sta
e ON or OFF – Heat pump
e ON or OFF
the second stage will
ving Time Calcula
ving
ving
Time Calculation
Time Calcula
Time Calcula
tion – 1F85 only,
tion
tion
ving
Time Calcula
tion
or
touch keys to select the
placement
placement
placement
placement R R R R R eminder and Set
eminder and Set
eminder and Set
eminder and Set R R R R R un
eminder and Set
e Filter
e Filter" reminder On or OFF . If selec-
e Filter
e Filter
MENU
MENU
MENU
MENU to select the time period from 25 to
e Filter
e Filter" as a reminder to change or
e Filter
e Filter
Change Filter
Chang
Chang
e Filter
e Filter
e Filter" is displayed,
Chang
e Filter
UN SCHED
UN SCHED
UN SCHED
UN SCHED button to clear the
alv
alv
alve Output
alv
e Output
e Output
e Output
e Output – The O/B option is
O to 4 HI –
O to 4 HI
O to 4 HI
O to 4 HI
un
un
un Time
un
Time
Time
Time
Time
5

Hide quick links:

Advertisement

loading

This manual is also suitable for:

1f85-0471White rodgers 80 seriesWhite rodgers 1f83-0471