Trane IntelliPak SCWG 020, SCWG 025, SCWG 030, SCWG 035, SWG 020, SWG 025, SWG 030, SWG 035, SCRG 020, SCRG 025, SCRG 032, SRG 020, SC Installation Manual page 79

Commercial self-contained modular series
Table of Contents

Advertisement

Occupied/Unoccupied Contacts
To provide night setback control if a
remote panel with night setback was not
ordered, install a field-supplied contact.
This binary input provides the building's
occupied/unoccupied status to the RTM. It
can be initiated by a time clock, or a
building automation system control
output. The relay's contacts must be rated
for 12 ma @ 24 VDC minimum. Refer to
the appropriate wiring diagrams
(attached to the unit control panel for the
proper connection terminals in the unit
control panel.
Emergency Stop Input
A binary input is provided on the RTM
board for installation of a field-supplied
normally closed (N.C.) switch to use
during emergency situations to shut
down all unit operations. When open, an
immediate shutdown occurs. An
emergency stop diagnostic enters the
human interface and the unit will require
a manual reset. Refer to the unit wiring
diagrams (attached to the unit control
panel for the proper connection
terminals. The switch must be rated for
12 ma @ 24 VDC minimum. This input
will override all VOM inputs, if the VOM
option is on the unit.
VAV Box Option
To interlock VAV box operation with
evaporator fan and heat/cool modes,
wire the VAV boxes/air valves to VAV box
control connections on the terminal block.
Supply Duct Static Pressure Control
The RTM relies on input from the duct
pressure transducer when a unit is
equipped with IGV or VFD to position the
IGV or set the supply fan speed to
maintain the supply duct static pressure
to within the static pressure setpoint
deadband.
RTM Sensors
RTM sensors include: zone sensors with
or without setpoint inputs and modes,
supply air sensor, duct static pressure,
outside air temperature, outside air
humidity, airflow proving, and dirty filter.
SCXG-SVX01B-EN
Owner
Table O-GI-2. RTM Sensor Resistance vs. Temperature
Temperature (F)
Resistance (ohms)
-40
346.1
-30
241.7
-20
170.1
-10
121.4
-5
103.0
0
87.56
5
74.65
10
63.8
15
54.66
20
46.94
25
40.40
30
34.85
35
30.18
40
26.22
45
22.85
50
19.96
55
17.47
60
15.33
65
13.49
66
13.15
67
12.82
68
12.50
69
12.19
70
11.89
Table O-GI-3. RTM Setpoint Analog Inputs
Cooling or Heating Setpoint Input (F)
(using RTM as zone temp. source)
40
45
50
55
60
65
70
75
80
NA
NA
Table O-GI-4. RTM Resistance Value vs. System Operating Mode
Resistance
applied to RTM Mode
input terminals (Ohms)
Fan Mode
2320
Auto
4870
Auto
7680
Auto
10,770
On
13,320
On
16,130
On
19,480
Auto
27,930
On
Note: Mode boundaries are 1000 to 40,000 ohms. Other boundaries are equal to the midpoint between the
nominal mode resistance.
General
Information
Temperature (F)
71
72
73
74
75
76
77
78
79
80
85
90
100
105
110
120
130
140
150
160
170
180
190
200
Cooling Setpoint Input (F)
(using RTM as supply air temp. source)
40
45
50
55
60
65
70
75
80
85
90
CV Units
System Mode
Off
Cool
Auto
Off
Cool
Auto
Heat
Heat
Resistance (ohms)
11.60
11.31
11.03
10.76
10.50
10.25
10.00
9.76
6.53
9.30
8.25
7.33
5.82
5.21
4.66
3.76
3.05
2.50
2.05
1.69
1.40
1.17
0.985
0.830
Resistance (ohms)
1084
992
899
796
695
597
500
403
305
208
111
VAV Units
System Mode
Off
Auto
79

Advertisement

Table of Contents
loading

Table of Contents