62
Installation
Connecting to T racer Summit
IntelliPak
®
self-contained units operate
with Trane building automation software,
Tracer Summit
®
version 10.0.4 or later or
any OS2 operating system.
CAUTION
!
Tape the non-insulated end of the
shield on shielded wire at the
unit. Any connection between the
shield and ground will cause a
malfunction. If daisy-chained in
the unit, splice and tape the
shields to prevent contact with
ground.
Pre-Startup
Requirements
®
Communication Wiring
Note: Communication link wiring is a
shielded, twisted pair of wire and must
comply with applicable electrical codes.
An optional communication link provides
a serial communication interface (SCI)
between Tracer Summit
commercial self-contained (CSC) unit in
the system. The CSC system can have a
maximum of 12 CSC units per connection
®
link to Summit
. Use a single 18 AWG
shielded, twisted pair wire with stranded,
thinned copper conductors to establish
each communication link between
®
Summit
and each unit.
®
and each
SCXG-SVX01B-EN