BEFORE INSTALLATION

All wiring must comply with local electrical codes and
ordinances or as specified on installation wiring diagrams.
Wall module wiring can be sized from 16 to 22 AWG (1.5
to 0.34 mm
), depending on the application. The maximum
2
length of wire from a device to a wall module is 1000 ft
(305 m). Twisted-pair wire is recommended for wire runs
longer than 100 ft (30.5 m).
COVER DISASSEMBLY
The cover of the wall module is fixed in place using a tab
located on the underside of the unit; to disassemble the
cover and the subbase, see Fig. 1.
Fig. 1. Cover disassembly.
Table 1. Features of T7460 Versions
Sensor
Setpoint Bypass/ LED Fan speed

-
T7460A


T7460B


T7460C


T7460D


T7460E


T7460F
INSTALLATION
The T7460B,C,D,E,F packages include two setpoint dials.
By default, the "Celsius Relative" type is mounted. This can
be easily replaced with the "Celsius Absolute" type by
pulling the one dial off and inserting the other one.
® U.S. Registered Trademark
Copyright © 2002 Honeywell Inc. • All Rights Reserved
Проектирование. Монтаж. Продажа. - http://vskd.ru
-
-
-
-

-
-
5-position

3-position

5-position
T7460A,B,C,D,E,F
WALL MODULES
INSTALLATION INSTRUCTIONS
Mount the T7460A,B,C,D,E,F Wall Modules on an inside
wall approximately 54 in. (1.3 m) from the floor (or in the
specified location) to allow exposure to the average zone
temperature.
NOTE: Maintain a mounting clearance of approx. 4 in.
(10 cm) to the left-hand side of the module in
order to allow a free airflow for the temperature
sensor and accessibility of the setpoint dial.
Do not mount the wall modules on an outside
wall, on a wall containing water pipes, or near air
ducts. Avoid locations that are exposed to
discharge air from registers or radiation from
lights, appliances, or the sun.
The T7460D,E,F should not be connected to
controllers that do not support fan operation
(e.g. W7751, W7762, W7763).
Keep wiring at least one ft (305 mm) away from
large inductive loads such as motors, line starters,
lighting ballasts, and large power distribution
panels.
Run wall module wiring separately from 50 Vac or
greater power wiring.
The wall modules can be mounted on a 60-mm wall outlet
box using No. 6 (3.5-mm) screws or on a wall (see Fig. 2
and 5). When mounting directly on a wall, use the type of
screws appropriate for the wall material.
Fig. 2. Bore-holes for T7460 wall modules in in. (mm).
See Fig. 3 for T7460A,B,C,D,E,F mounting dimensions.
95-7620-2

Advertisement

loading

Summary of Contents for Honeywell EXCEL 5000 OPEN T7460A

  • Page 1: Before Installation

    Fig. 2. Bore-holes for T7460 wall modules in in. (mm). See Fig. 3 for T7460A,B,C,D,E,F mounting dimensions. ® U.S. Registered Trademark Copyright © 2002 Honeywell Inc. • All Rights Reserved 95-7620-2 Проектирование. Монтаж. Продажа. - http://vskd.ru...
  • Page 2 T7460A,B,C,D,E,F WALL MODULES NOTE: Graphics show E/F model. Dimensions are the same for all six models. Fig. 3. T7460A,B,C,D,E,F dimensions in in. (mm). 95-7610-2 Проектирование. Монтаж. Продажа. - http://vskd.ru...
  • Page 3: Mounting Procedure

    T7460A,B,C,D,E,F WALL MODULES Mounting Procedure Wiring 1. Disassemble the cover as is shown in Fig. 1. Attach the wires from the device sensor terminals to the appropriate wall module terminals and set the jumpers 2. (T7460B,C,D,E,F only) according to the connected controller. See Fig. 6, 7 and 8. Remove the setpoint dial by pulling it off.
  • Page 4 T7460A,B,C,D,E,F WALL MODULES Fig 7. Wiring diagram for T7460A,B Wall Modules. Fig 8. Wiring diagram for T7460C,D,E,F Wall Modules (for the jumper settings, see Fig. 6). 95-7610-2 Проектирование. Монтаж. Продажа. - http://vskd.ru...
  • Page 5 T7460A,B,C,D,E,F WALL MODULES ACCESSORIES T7460-LONJACK The T7460-LONJACK allows to easily access L via the wall module. L will be connected to the two LON ORKS ORKS terminals. A PC connection can be established using the 3.5-mm jack plug. Order quantity: set with 5 pieces Fig 9.
  • Page 6 Setpoint Limit 1 Fig 11. Mounting T7460-LIMITER(S) Home and Building Control Home and Building Control Home and Building Control Products Honeywell Inc. Honeywell Limited-Honeywell Limitee Honeywell AG Honeywell Plaza 155 Gordon Baker Road Böblinger Straβe 17 P.O. Box 524 North York, Ontario D-71101 Schönaich...

This manual is also suitable for:

Excel 5000 open t7460bExcel 5000 open t7460cExcel 5000 open t7460eExcel 5000 open t7460dExcel 5000 open t7460f