Description
The Genesis Ceiling Horn-Strobe is a fire alarm notification
appliance designed for indoor ceilings and walls. See Table 1 for a
list of model numbers.
Table 1: Models
Description
Horn-strobe,
15 to 95 multi-cd, white
Horn-strobe,
15 to 95 multi-cd, white, with
FIRE marking
Horn-strobe,
15 to 95 multi-cd, red, with
FIRE marking
Field configurable jumper options are available for selecting the
desired dB output, temporal or steady horn output, and strobe
signal output.
The horn-strobe includes a field configurable switch for selecting
the desired candela output. The candela output setting is locked in
place and remains visible after final installation.
This strobe features an enhanced synchronization circuit to
comply with the latest requirements of UL 1971 Signaling Devices
for the Hearing Impaired and the latest Canadian standard
CAN/ULC-S526. Synchronized operation requires a separately
installed synchronization control module. See Table 2 for a list of
compatible synchronization modules.
Install this device in accordance with applicable requirements in
the latest editions of the NFPA codes and standards and Canadian
Electrical Code, Part 1, Section 32 and CAN/ULC-S524, Standard for
the Installation of Fire Alarm Systems, and in accordance with the
local authorities having jurisdiction.
Table 2: Compatible synchronization module models
Description
Auto-sync output module
Genesis signal master -
remote mount
Number
ADTGC-HDVM
MGC-HDVM
EGC-HDVM
XLSGC-HDVM
GC-HDVM
ZGC-HDVM
ADTGCF-HDVM
MGCF-HDVM
EGCF-HDVM
XLSGCF-HDVM
GCF-HDVM
ZGCF-HDVM
EGCFR-HDVM
GCFR-HDVM
MGCFR-HDVM
Number
SIGA-CC1S
SIGA-MCC1S
GSA-CC1S
GSA-MCC1S
ADTG1M-RM
MG1M-RM
EG1M-RM
XLSG1M-RM
G1M-RM
ZG1M-RM
Installation
WARNING:
To reduce the risk of shock, disconnect all power and
allow 10 minutes for stored energy to dissipate before handling.
Caution:
Electrical supervision requires the wire run to be broken
at each terminal. Do not loop the signaling circuit field wires
around the terminals.
To install the horn-strobe:
1.
Remove the cover by depressing the tab on the side of the
unit with a small screwdriver. Turn the cover
counterclockwise to release.
2.
Set the horn signal, sound output level, and strobe signal to
the desired settings. See Figure 2.
3.
Connect the strobe terminals to the signal circuit field wiring.
You must observe polarity for the unit to function properly.
See Figure 4.
4.
Slide the candela switch to the desired candela output (95,
115, 150, or 177 cd) by aligning it with the indicator below the
switch. See Figure 1.
5.
Mount the unit onto a compatible electrical box. See Figure 5.
6.
Replace the cover by positioning the alignment arrows
together and rotating the cover clockwise.
7.
Test the unit for proper operation.
Figure 1: Candela switch
1.
Candela switch
© 2009 GE Security, Inc.
2.
Indicator
1 of 4
P/N 3100616 • REV 4.0 • ISS 30SEP09

Advertisement

loading

Summary of Contents for GE ADTGC-HDVM

  • Page 1 Description Number Auto-sync output module SIGA-CC1S SIGA-MCC1S GSA-CC1S GSA-MCC1S Candela switch Indicator Genesis signal master - ADTG1M-RM MG1M-RM EG1M-RM XLSG1M-RM remote mount G1M-RM ZG1M-RM 1 of 4 © 2009 GE Security, Inc. P/N 3100616 • REV 4.0 • ISS 30SEP09...
  • Page 2 Wiring Figure 2: Horn and strobe settings Figure 4: Wiring Diagram From NAC output JP1: Horn signal jumper: Cut to change from temporal to steady To next NAC output JP2: Strobe signal output: Cut to change from 1 flash per second Note: Signal polarity is shown in the alarm condition.
  • Page 3 Table 4: Sound level output (dBA) Figure 6: Light output profile Signal High db Low db 345 350 Temporal 79.8 75.0 83.3 78.0 85.0 80.9 Steady 83.2 79.3 85.4 83.0 87.8 85.9 UL464: Sound level output at 10 ft. (3.05 m) measured in a reverberant room Table 5: Minimum sound level output per ULC-S525 (dBA, peak) Signal...
  • Page 4: Specifications

    32 to 120°F (0 to 49°C) Relative humidity 0 to 93% noncondensing Regulatory information Manufacturer GE Security, Inc., 8985 Town Center Parkway, Bradenton, FL 34202, USA Year of The first two digits of the DATE MFG number (located manufacture on the product identification label) are the year of...