FUJITSU GENERAL AMERICA, INC SERVICE BULLETIN 353 Route West. Fairfield, NJ 07004 Number: 0006 Ph: 973-575-0381 Fx: 973-836-0449 Date: 9/22/09 Rev2 Em: ServiceHVAC@fujitsugeneral.com Type: Field PROBLEM Fresh Air Intake w/ Compressor Operation Only SOLUTION Duct Fan Control MODEL :18/24/36/42RLX Systems Production: All Cassettes 1.
Page 2
4. Components utilized Current sensor with built-in relay specifications: Split Core Fixed Threshold Current Status Sensor with Command Relay and Switching Power Supply. FGAI Fresh Air Kit Part # KHRS940-25 5. Recommended Fan size. Duct and Fan are field supply. A fan capable of generating 15 CFM at a static pressure of approximately .26 inches W.C.
Page 3
Current Sensor Installation • Install the current sensor around one of the compressor line voltage wires. • Tuck sensor into the clearance behind the compressor wire molex plug. • Secure the current sensor with a zip tie.
Page 4
Secure Current Sensor • 4 zip ties are needed for correct installation. • Secure the current sensor wires with all four zip ties according to the arrows. Do not tie around any of the copper lines. •Cut the ends of the zip ties.
Page 5
CEILING CASSETTE OUTSIDE (FRESH) AIR INTAKE 58.8 Pa .24 in W.C. 15 CFM 4” Duct Outside (Fresh) CASSETTE Air Intake 2.75” x 4” Field Supplied Transition Fan Static Pressure Requirements: Static pressure required at Cassette = .24 in W.C. 25 ft. 4” duct + intake=45ft. TEL x .04/100 = .018 in W.C. TOTAL =.258 in W.C.