C7632A,B
Sensor and Controller

CARBON DIOXIDE SENSOR

C7632B
APPLICATION
The C7632 Sensor and Controller is a stand-alone carbon
dioxide (CO
) sensor for use in determining ventilation
2
necessity with heating ventilation and air conditioning
(HVAC) controllers. The C7632 measures the CO
concentration in the ventilated space or duct. The C7632 is
used in HVAC systems to control the amount of fresh
outdoor air supplied to maintain acceptable levels of CO
the space.
FEATURES
• Non-Dispersion-Infrared (NDIR) technology used to
measure carbon dioxide gas.
• Special plated sensor provides long-term calibration
stability.
• Device provides voltage output based on CO
• Used for CO
based ventilation control.
2
• Automatic Background Calibration (ABC) algorithm
based on long-term evaluation reduces required
typical zero-drift check maintenance.
• Fixed 0 to 10 Vdc from 0 to 2000 ppm. No
adjustments are necessary.
• Compatible with Honeywell Excel 10, 15, 5000, and
any controller requiring 0-10 Vdc input.
C7632A
2
in
2
levels.
2

SPECIFICATIONS

Models: C7632 Sensor and Controller. A stand-alone car-
bon dioxide (CO
) sensor with one 0-10 Vdc analog out-
2
put.
C7632A: Wall mount model.
C7632B: Duct mount model.
Dimensions:
C7632A: See Fig. 1.
C7632B: See Fig. 2.
Ambient Ratings:
Temperature:
Operating: +32°F to +122°F (0°C to +50°C).
Storage: -4°F to +158°F (-20°C to +70°C).
Relative Humidity (non-condensing): 0 to 95 percent.
Automatic Background Calibration (ABC) default: On.
Electrical Ratings:
Power Supply: 24 Vac ±20%, 50/60 Hz (Class 2).
Maximum Power Consumption:
Average: 1W.
Peak: 2W.
Peak Current (at 20 ms): 300 mA.
Linear Analog Output: 0-10 Vdc.
Mounting:
C7632A: Vertical surface with standard single-gang junction
box.
C7632B: Sheet metal duct with a sampling tube.
CO
Pressure Dependence: 1.6% change in reading per
2
1 kPa deviation from 100 kPa.
Output: Analog: 0-10 Vdc, 0-2000 ppm (fixed).
Sensor Performance Ratings:
Response Time: 1 min.
Carbon Dioxide Sensor:
Operation: Non-dispersive infrared (NDIR).
Sampling: Diffusion.
Range: 0 to 2000 ppm (fixed).
Annual Drift: ±10 ppm (nominal).
Accuracy: ±(30 ppm+2%) at normal temperature/pres-
sure.
Calibrated at the factory.
Uses automatic background calibration. No calibration
required for the life of the product.
Meets CEC Title 24 requirement of ±75ppm accuracy at
600ppm and 1000ppm ambient levels.
For proper CO2 operation, install only in spaces that see
at least 4 hours of continuous unoccupied time per
week.
PRODUCT DATA
63-2615-07

Advertisement

loading

Summary of Contents for Honeywell C7632A

  • Page 1: Carbon Dioxide Sensor

    Meets CEC Title 24 requirement of ±75ppm accuracy at • Compatible with Honeywell Excel 10, 15, 5000, and 600ppm and 1000ppm ambient levels. any controller requiring 0-10 Vdc input. For proper CO2 operation, install only in spaces that see at least 4 hours of continuous unoccupied time per week.
  • Page 2: Ordering Information

    TRADELINE® Catalog or price sheets for complete ordering number. If you have additional questions, need further information, or would like to comment on our products or services, please write or phone: 1. Your local Honeywell Environmental and Combustion Controls Sales Office (check white pages of your phone direc- tory).
  • Page 3 C7632A,B SENSOR AND CONTROLLER M19797 Fig. 4. Junction box mounting (C7632A). M19796 Fig. 3. C7632A cover removal. Wall Mounting (C7232A) Mount the C7232A to the wall as follows: 1. Remove the C7632 cover. 2. Mount the device in a vertical position.
  • Page 4 By using this Honeywell literature, you agree that Honeywell will have no liability for any damages arising out of your use or modification to, the literature. You will defend and indemnify Honeywell, its affiliates and subsidiaries, from and against any liability, cost, or damages, including attorneys’...