LDWO SERIES—Oil-fired/Hot Water
A Caravan modular boiler system consists of
two or more compact cast-iron boilers that offer
significant advantages in terms of installed
cost, efficiency and reliability. Caravan
systems are based on step-firing just enough
modules to meet hot water or space heating
demands. LDWO systems are available in
602,000 to multi-million Btuh gross input.
For additional information, see Caravan
Engineering Manual, pub. C-30 and Caravan
oil application guide, pub. CG-10-HWO.
Standard Equipment
One per module unless otherwise noted
Pre-assembled cast-iron heat exchanger
with built-in air separators and insulated jacket
Swing-out/removable burner door
Flame retention oil burner, with nozzle;
cadmium sulfide flame detector
Hi-limit control, auto reset
Primary burner control
System pressure and temperature gauge
(unmounted)
Module pressure and temperature gauge
Module pressure relief valve (ASME)
(unmounted) Specify 30, 50 or 100 psi.
Draft regulator (unmounted)
Ratings
Oil Caravan ratings/hot water models — LDWO Series
No. of
Modules
Model No.
LDWO-600-2-5
2
LDWO-750-2-6
2
LDWO-850-2-7
2
LDWO-900-3-5
3
LDWO-1100-3-6
3
LDWO-1300-3-7
3
LDWO-1700-4-7
4
LDWO-2100-5-7
5
LDWO-2500-6-7
6
LDWO-2900-7-7
7
LDWO-3400-8-7
8
* Light oil, 140,000 Btuh per gallon.
† Based on 150 Btuh per square foot E.D.R. at 170°F average
water temperature.
‡ Net ratings are based on a piping and pick-up allowance of
1.15. Slant/Fin should be consulted before selecting a boiler
Modular Boiler Submittal Data
®
Control header (unmounted,
one per system)
Flue brush
Module drain cock
(unmounted)
I=B=R
I=B=R Ratings
Firing
(MBH)
Rate
#2 Oil
Gross
Input
GPH*
Output
4.30
602
500
5.20
728
596
6.00
840
684
6.40
896
750
7.80
1092
894
9.00
1260
1026
12.00
1680
1368
15.00
2100
1710
18.00
2520
2052
21.00
2940
2394
24.00
3360
2736
Optional Equipment
Hot water supply and return header
Control panel with automatic lead lag
I=B=R
EDR
Boiler
Net
Water †
Horse-
Output‡
(Sq. Ft.)
(MBH)
power
2900
435
14.9
3453
518
17.8
3967
595
20.4
4347
652
22.4
5180
777
26.7
5947
892
30.6
7933
1190
40.9
9913
1487
51.1
11893
1784
61.3
13880
2082
71.5
15860
2379
81.7
for installation having unusual piping and pick-up requirements.
§ Modules in excess of 8 are piped in parallel to first eight.
NOTE: For higher capacities, specify any combination of standard
Caravan models shown.
assemblies
Recom-
mended
Water
Header
Content
Ship
Size §
(gal.)
Wt.
31.0
1570
2"
35.6
1790
2"
45.2
2000
3"
46.5
2355
3"
53.4
2685
3"
67.8
3000
3"
90.4
4000
3"
113.0
5000
3"
135.6
6000
3"
158.2
7000
4"
180.8
8000
4"

Advertisement

loading

Summary of Contents for Slant/Fin Caravan LDWO-1100-3-6

  • Page 1 System pressure and temperature gauge (unmounted) Module pressure and temperature gauge Module pressure relief valve (ASME) (unmounted) Specify 30, 50 or 100 psi. Draft regulator (unmounted) Ratings Oil Caravan ratings/hot water models — LDWO Series I=B=R Firing Rate No. of #2 Oil Modules GPH* Model No.