Siemens ZN-34US Installation Instructions

Gate valve supervision modules

Advertisement

Quick Links

Installation Instructions
Models ZN-34US and ZN-34UA
Gate Valve Supervision Modules
Description
The Sprinkler Valve Supervision Modules, Model ZN-
34US and Model ZN-34UA, are designed to provide
two circuits for the supervision of sprinkler system
gate valves and ancillary equipment in accordance
with NFPA Standard 72. The module provides two
yellow LED indicators per circuit. The first illuminates
when a supervisory condition exists and the second
when a circuit trouble condition occurs. The module
utilizes an end-of-line resistor in parallel with normally
open switches to provide this supervision.
The Model ZN-34US provides annunciation of condi-
tions as follows; when a sprinkler valve is closed the
supervisory circuit is shorted, the yellow supervisory
LED is illuminated and the supervisory module output
is energized. The output should be used to operate a
separate AE-30U Module with an audible device.
When a break in the circuit occurs the module trouble
LED is illuminated and the control panel is placed in
system trouble. The supervisory condition is non-
latching, therefore, the supervisory condition will
clear if the sprinkler valve is restored to its normal,
open position.
The Model ZN-34UA is a latching device. Operation
is the same as the ZN-34US except that the condition
latches and can only be cleared through a system re-
set after the sprinkler valve is restored to its normal,
open position.
In addition to gate valves, other sprinkler supervisory
limit functions such as water pressure, water level,
temperature, air pressure and fire pump supervision
may be supervised with the ZN-34US/-UA.
All module LEDs are illuminated when the system re-
set/lamp test switch on the CP-35 main module is op-
erated. The ZN-34US/-UA sprinkler valve supervision
module is placement supervised, providing a system
trouble signal upon removal from the system.
Installation
1.
Mount the module to the horizontal mounting
brackets in the control enclosure.
Siemens Industry, Inc.
Building Technologies Division
Florham Park, NJ
P/N 315-094221-10
2.
Install the Model JA-5 (5 in long) bus connector
cable assembly between receptacle P2 of the
module and receptacle P1 of the module or
control panel immediately preceding it in the bus.
Note: If the preceding module is on another row
in the enclosure, a JA-24 (24 in long) bus
connector cable assembly will be required.
3.
Modules are to be bus-connected from right to
left. For two-row enclosures, the modules in the
lower row are to be connected from left to right.
Succeeding
rows
connected, right to left, left to right, etc.
4.
If a module is the last module in the system,
install either a JS-30 (30 in long) or JS-64 (64 in
long) bus connector assembly from the unused
receptacle of the last module to terminal 41 of
the CP-35 control panel. This completes the
module supervision circuit.
5.
Wire the circuit(s) as described in the CP-35
Control Panel Instruction Manual (P/N 315-
085063) Installation and Wiring. Refer to the Wiring
illustration.
Note: If a zone is not used, the EOL device
should be connected to the alarm initiating circuit
terminals 2 and 3 (Zone 1) or 4 and 5 (Zone 2) of
the module.
6.
If a supplementary relay module, annunciator, or
other output module is used, then the alarm
outputs, terminals 1 (Zone 1) and 6 (Zone 2),
should be connected to these units.
Wiring Test
Refer to the CP-35 Control Panel Instruction Manual,
Installation and Wiring.
Electrical Information
21.5 VDC at 18mA Supervision and 100mA Supervi-
sory Switch Activated
Maximum loop resistance: 100 ohms
Siemens Building Technologies, Ltd.
Fire Safety & Security Products
2 Kenview Boulevard
Brampton, Ontario
L6T 5E4 Canada
are
to
be
alternately

Advertisement

loading

Summary of Contents for Siemens ZN-34US

  • Page 1 The Model ZN-34UA is a latching device. Operation Note: If a zone is not used, the EOL device is the same as the ZN-34US except that the condition should be connected to the alarm initiating circuit latches and can only be cleared through a system re-...
  • Page 2 (SEE NOTE 1) Wiring Information, P/N 315-085178, (SEE NOTE 1) ZONE 1 for signal factor load units. ZONE 2 4. The ZN-34US is a non-latching device SUPERVISORY and follows NFPA 72 guidelines for TROUBLE operation. 5. Minimum wire size: 18 AWG...

This manual is also suitable for:

Zn-34ua