NCA FSD-RD-211 Installation, Operation & Maintenance Instructions Manual

True round fire & fire/smoke damper

Advertisement

Quick Links

FSD-RD
Application & General Notes:
These installation instructions apply to static Fire, dynamic Fire
and Combination Fire/Smoke Dampers of the true round types
mounted in the plane of a UL* approved fire partition. The
dampers are designed for operation in the vertical or horizontal
orientation with the blade running horizontal.
Safety Warning:
Read all installation, operating and maintenance instructions
thoroughly before installing or servicing this equipment.
Improper installation, adjustment, alteration, service or
maintenance can cause property damage, injury or death.
Receiving & Handling:
Check for damage when this product is received. If damage is
found, record all necessary information on the bill of lading and
file a claim with the final carrier. Check to be sure that all parts
of the shipment are accounted for.
*When UL is referred to in this document, it represents UL/ULC
(Underwriter's Laboratories of United States and Canada).
This IOM manual is the property of the owners, and is required for future
maintenance. Please leave it with the owner when the job is complete.
1
NCA MANUFACTURING INC. • 1985 CARROLL ST. • CLEARWATER, FL 33765 • 727.441.2651 • www.ncamfg.com
TRUE ROUND FIRE & FIRE/SMOKE
DAMPER INSTALLATION, OPERATION
& MAINTENANCE INSTRUCTIONS
UL/ULC File: R8218
New York BSA/MEA Listing: 79-03-M
California State Fire Marshall Listing: 3235:1721:0100
and 3225-1721:0102
The following installation instructions are UL
approved to be used with the following NCA
Models: FSD-RD-211, -212, FD and FDD-RD.
FD(D)-RD
Installation Supplements:
- Installing Fire and Combination Fire/Smoke
Dampers in a Shaft Wall
- Framing Requirements for Wood or Steel Stud Walls
- UL Approved Breakaway Duct Connections
- Optional Sealing of Dampers in Fire and Smoke
Rated Walls or Floors
- Installing the SL-2000 Smoke Detector
- Field Modification of Factory Supplied Sleeves
- Installing Fire and Fire/Smoke Dampers in Concrete
Floor with Steel Deck
Other Installation References:
- Out-of-Wall Fire and Fire/Smoke Damper IOM
- Combination Fire/Smoke Damper IOM
- Fire Damper IOM
Electrical Guidelines:
Electrical input may be needed for products discussed
within this IOM. All wiring shall be done in accordance
with the latest edition of the National Electrical Code
ANSI/NFPA-70, any local codes that may apply and
wiring diagrams developed in compliance with the job
or project design and specifications.
Electrical input work should be performed by a
qualified electrician. Verify power before wiring
actuator. NCA is not responsible for damage to or
failure of the unit caused by incorrect field wiring.
Follow all instructions carefully.
IOM - TRUE ROUND FIRE & FIRE/SMOKE DAMPERS - 1016
R8218

Advertisement

loading

Summary of Contents for NCA FSD-RD-211

  • Page 1 Follow all instructions carefully. maintenance. Please leave it with the owner when the job is complete. IOM - TRUE ROUND FIRE & FIRE/SMOKE DAMPERS - 1016 NCA MANUFACTURING INC. • 1985 CARROLL ST. • CLEARWATER, FL 33765 • 727.441.2651 • www.ncamfg.com...
  • Page 2: Table Of Contents

    8” - 24” 8” - 24” FDD-RD (203-610) (203-610) (All dimensions in parentheses () are in millimeters.) IOM - TRUE ROUND FIRE & FIRE/SMOKE DAMPERS - 1016 NCA MANUFACTURING INC. • 1985 CARROLL ST. • CLEARWATER, FL 33765 • 727.441.2651 • www.ncamfg.com...
  • Page 3: Damper Sleeves & Mounting Clips

    Clip Angle Detail 20 Ga. Splice Clip Detail (1) Galv. Steel IOM - TRUE ROUND FIRE & FIRE/SMOKE DAMPERS - 1016 NCA MANUFACTURING INC. • 1985 CARROLL ST. • CLEARWATER, FL 33765 • 727.441.2651 • www.ncamfg.com...
  • Page 4: Angle Method Of Installation

    Jackshaft Shaft 30˚ Factory Supplied Plate +/- 30˚ Max. Off Horizontal Angle (in either direction) IOM - TRUE ROUND FIRE & FIRE/SMOKE DAMPERS - 1016 NCA MANUFACTURING INC. • 1985 CARROLL ST. • CLEARWATER, FL 33765 • 727.441.2651 • www.ncamfg.com...
  • Page 5: Angle Method Of Installation

    Axle Auxiliary 30˚ Operating Blade Jackshaft Shaft +/- 30˚ Max. Off Horizontal (in either direction) IOM - TRUE ROUND FIRE & FIRE/SMOKE DAMPERS - 1016 NCA MANUFACTURING INC. • 1985 CARROLL ST. • CLEARWATER, FL 33765 • 727.441.2651 • www.ncamfg.com...
  • Page 6: Actuator Connections

    Fire & Fire/Smoke Damper Operation: All NCA fire/smoke dampers are operated at the factory, however pre-installation testing of its operation should be con- ducted. Wire the actuator (if applicable) per correct wiring diagrams. Applying power to the actuator should drive the damper open and disconnecting power should activate the actuator’s internal springs and drive closed.