Data Center Grade Three Phase Uninterruptible Power Supply
1.0
GENERAL
1.1
SUMMARY
This specification describes a three-phase, on-line, double conversion, solid state Uninterruptible
Power System hereafter referred to as the UPS. The UPS shall operate in conjunction with the
existing building electrical system to provide high quality power conditioning, back-up power
protection and distribution for electronic equipment loads. The system shall consist of a solid state
IGBT rectifier/inverter, power factor corrected rectifier, a 100% rated for continuous duty static
switch, battery plant, graphical status/control panel, and synchronizing circuitry as described herein.
1.2
STANDARDS
The UPS shall meet the requirements of the following standards:
A. UL listed under 1778, standards for uninterruptible power supply equipment
B. UL Canada (cUL)
C. FCC rules and regulations of part 15, subpart J, class A
D. IEC 1004/ANSI C62.41 Standards for Surge Withstand Ability
E. ISO 9001
F. The UPS shall be designed in accordance with the applicable sections of the documents
published by:
National Fire Protection Association (NFPA)/National Electric Code (NEC)
National Electrical Manufacturer's Association (NEMA) & (NEMA PE 1)
Occupational Safety & Health Administration (OSHA)
1.3
SUBMITTALS
Submittals shall contain the following documentation:
A. Installation Package: Complete electrical characteristics and connection requirements.
Provide detailed equipment outlines with cabinet dimensions and spacing requirements;
location of conduit entry/exit paths; location of floor/seismic mounting; available battery
types/sizes; all cabinet weights; heat rejection and air flow requirements; single-line diagram;
control and external wiring.
B. Product Data: Provide catalog sheets and technical data sheets to indicate physical data and
electrical performance, electrical characteristics, and connection requirements.
C. Manufacturer's Installation Instructions: Indicate application conditions and limitations of
use stipulated by Product testing agency. Include instructions for storage, handling, protection,
examination, preparation, installation, and starting of Product. Include equipment installation
APC – MGE Galaxy 5000 Specification (60Hz)
Parallel Module
APC by Schneider Electric
MGE GALAXY 5000
Parallel Module - Guide Specifications
40-130 kVA UPS
1
Effective: June 1, 2008 REV X0 JJG

   Related Manuals for Schneider Electric MGE GALAXY 5000

   Summary of Contents for Schneider Electric MGE GALAXY 5000

  • Page 1

    C. Manufacturer’s Installation Instructions: Indicate application conditions and limitations of use stipulated by Product testing agency. Include instructions for storage, handling, protection, examination, preparation, installation, and starting of Product. Include equipment installation APC – MGE Galaxy 5000 Specification (60Hz) Parallel Module MGE GALAXY 5000...

  • Page 2

    ENVIRONMENTAL REQUIREMENTS The UPS shall operate under the following environmental conditions: A. Temperature: APC – MGE Galaxy 5000 Specification (60Hz) Parallel Module Effective: June 1, 2008 REV X0 JJG...

  • Page 3

    APPROVED MANUFACTURERS & PRODUCT DESCRIPTION A. Approved Manufacturer(s): The specified equipment will be manufactured by APC by Schneider Electric or approved manufacturer in compliance with specifications. B. Product Description: This specification describes a three-phase, double conversion, on-line, solid state Uninterruptible Power System, hereafter referred to as the UPS. The UPS shall operate in conjunction with the existing building electrical system to provide power conditioning, back-up power protection and distribution for electronic equipment loads.

  • Page 4

    4. Voltage Distortion: Maximum 2% total (THD) and 1% any single harmonic on 100% linear loads. 5. Voltage Transient (Step Load) Response: + 3% for 50% step load change APC – MGE Galaxy 5000 Specification (60Hz) Parallel Module + 1.0% for balanced load + 1.75 for 50% unbalanced load...

  • Page 5

    Automatic re-transfer or forward transfer of the load shall be accomplished by turning the inverter on. COMPONENT DESCRIPTION A. PFC Rectifier and Battery Charger APC – MGE Galaxy 5000 Specification (60Hz) Parallel Module + 1% for loss or return of AC input power or manual transfer at full load...

  • Page 6

    The static bypass transfer switch shall be solid-state, rated for 100% continuous duty without mechanical contactor device in parallel for higher reliability and consistent response time and shall operate under the following conditions: APC – MGE Galaxy 5000 Specification (60Hz) Parallel Module Effective: June 1, 2008 REV X0 JJG...

  • Page 7

    UPS on or off without risk of load loss. • Display shall facilitate operation by offering the functions listed below. Operating information supplied on the screens. APC – MGE Galaxy 5000 Specification (60Hz) Parallel Module Effective: June 1, 2008 REV X0 JJG...

  • Page 8

    System Parameters Monitored: The visual display will display the following system parameters based on true RMS metering: Measurements: Input voltage (Ph-Ph) Input current per phase APC – MGE Galaxy 5000 Specification (60Hz) Parallel Module Effective: June 1, 2008 REV X0 JJG...

  • Page 9

    Opening of the automatic bypass Opening of the input, bypass, output and battery switches/circuit breakers Opening of the isolated dry contact on the programmable relay card APC – MGE Galaxy 5000 Specification (60Hz) Parallel Module Effective: June 1, 2008 REV X0 JJG...

  • Page 10

    UPS enclosure. Air exhaust shall be from the top portion of the unit. Full load heat rejection is [ APC – MGE Galaxy 5000 Specification (60Hz) Parallel Module ] (in lbs).

  • Page 11

    Two (2) dry contact inputs shall also be provided to turn the UPS inverter on and off remotely upon closure of the contacts. This feature may also be disabled if required. APC – MGE Galaxy 5000 Specification (60Hz) Parallel Module...

  • Page 12

    UPS modules, and effectively isolating the UPS modules. The bussing shall accommodate landing space for up to six UPS modules and input and out sources of up to APC – MGE Galaxy 5000 Specification (60Hz) Parallel Module...

  • Page 13

    UPS and the battery bank. Accredited professional service engineers employed exclusively in the field of critical power systems service shall perform all maintenance and service. The manufacturer shall also offer extended warranty contracts. APC – MGE Galaxy 5000 Specification (60Hz) Parallel Module Effective: June 1, 2008 REV X0 JJG...

  • Page 14

    END OF SECTION APC – MGE Galaxy 5000 Specification (60Hz) Effective: June 1, 2008 REV X0 JJG Parallel Module...

  • Page 15

    Additional configuration and runtimes are available. 2.2 B-2 INPUT CURRENTS A @ 480 VAC Max – Charging Battery 2.2 B-2 OUTPUT CURRENTS A @ 480 VAC APC – MGE Galaxy 5000 Specification (60Hz) Parallel Module Battery NPX-150 300 WPC 400 WPC 500 WPC 400 WPC...

  • Page 16

    80kVA 75.0 Height Width 28.0 Depth 33.4 Weight (stand-alone dimensions) 3.1 D UPS MODULE HEAT REJECTION APC – MGE Galaxy 5000 Specification (60Hz) Parallel Module 80 KVA Dimensions (Inches)/ WEIGHT (Lbs.) 100 to Entry 130kVA 75.0 75.0 28.0 14.0 33.4 33.4...

  • Page 17

    3.2D SYSTEM BYPASS CABINET (SBC) - Parallel Metering Input / output Volts Modules Height Width Depth Weight APC – MGE Galaxy 5000 Specification (60Hz) Parallel Module 28” SBC Cabinet 160/320 480V Up to Two 75.0” 28.0” 33.4” 300 lbs Effective: June 1, 2008 REV X0 JJG 42”...