Dimensions Check; Set Head Position Adjusting Plate ("V1" Head Only) - Beckett AFG Oil Burner Instruction Manual

Oil burner
Table of Contents

Advertisement

Check/adjust "Z" dimension - "L1" head
Figure 3 —
"L1" heads (see Table 3 and Figure 2 for dimensions)
1. See Figure 3. The important "Z" dimension is the distance from the leading
edge of the head to the end of the air tube. This distance for L1 heads is
1
" if the tube has a straight shroud (1
shroud). The "Z" dimension is factory set for burners shipped with the air
tube installed. Even if factory set, verify that the "Z" dimension has not been
changed.
2. Use the following procedure to adjust the "Z" dimension, if it is not correct:
• Turn off power to the burner.
• Disconnect the oil connector tube from the nozzle line.
• See Figure 3. Loosen the splined nut from the nozzle line. Loosen the
hex head screw securing the escutcheon plate to the burner housing.
• Place the end of a ruler at the leading edge of the head and, using a
straight edge across the end of the tube, measure the distance to the
end of the air tube. (A Beckett T500 gauge may also be used.)

Slide the nozzle line forward or back until this dimension is 1
heads if the air tube has a straight shroud (1
conic shroud).
• Tighten the hex head screw to secure the escutcheon plate to the burner
chassis. Then tighten the splined nut and attach the oil connector tube.
3. Recheck the "Z" dimension periodically when servicing to ensure the es-
cutcheon plate has not been moved. You will need to reset the "Z" dimen-
sion if you replace the air tube or nozzle line assembly.

Set head position adjusting plate ("V1" head only)

1. After setting "Z" dimension, loosen head adjusting plate hex head screw and
nozzle line splined nut. Move the nozzle line assembly until the burner reference
indicator lines up with the head adjusting plate setting number given in
Table 3.
2. Tighten the hex head screw and splined nut. (DO NOT loosen the acorn nut
when setting head position.) Refer to the Beckett OEM Specification Guide
or manufacturer's instructions for OEM settings.
3. The position of the head affects air flow volume and pattern. For most
applications, the burner will perform satisfactorily with the air adjustment
plate setting of Table 3.
4. If combustion results indicate the need for change, adjust the head position
adjusting plate forward or back one position at a time to optimize combustion.
Instruction Manual – Model AFG Oil Burner
Check/adjust "Z" dimension - "V1" head
Figure 4 —
1. See Figure 4. The important "Z" dimension is the distance from the leading
" if the air tube has a conic
2. Use the following procedure to adjust the "Z" dimension, if it is not correct:
" for L1
" if the air tube has a
3. Recheck the "Z" dimension periodically when servicing to ensure the es-
Table 3 — Starting adjusting plate settings with "V1" head
Prepare burner & site
"V1" heads (see Table 3 and Figure 2 for dimensions)
edge of the head to the end of the air tube. This distance for V1 heads is
1
". The "Z" dimension is factory set for burners shipped with the air tube
installed. Even if factory set, verify that the "Z" dimension has not been
changed.
• Turn off power to the burner.
• Disconnect the oil connector tube from the nozzle line.
• See Figure 4. Loosen the splined nut from the nozzle line. Loosen the
hex head screw securing the escutcheon plate to the burner housing.
• Loosen the acorn nut. Move the head adjusting plate until the "0" lines
up with the reference indicator on the housing, and retighten the hex
head screw. Place the end of a ruler at the leading edge of the head and,
using a straight edge across the end of the tube, measure the distance
to the end of the air tube. Or use a Beckett T500 gauge. Slide the nozzle
line forward or back until this dimension is 1
the acorn nut.
• Tighten the hex head screw to secure the escutcheon plate to the burner
chassis. Then tighten the splined nut and attach the oil connector tube.
cutcheon plate has not been moved. You will need to reset the "Z" dimen-
sion if you replace the air tube or nozzle line assembly.
" for V1 heads. Tighten
7

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Afg

Table of Contents