Outside air kit applications
Refer to separate instruction sheet supplied with
AF/AFG outside air kit for installation. This optional
kit allows combustion air to be piped directly to the
burner (Beckett part number 51747).

Clearances to burner and appliance

Provide space around burner and appliance for
easy service and maintenance.
Check minimum clearances against those shown
by the appliance manufacturer and by applicable
building codes.
Combustion chamber — Burner retrofi t-
ting
Verify that the appliance combustion chamber pro-
vides at least the minimum dimensions given in
Table 3.
Protect Steel Combustion
WARNING
!
Chamber From Burnout
Failure to comply could result in damage to the
heating equipment and result in fi re or asphyxi-
ation hazards.
When retrofi tting appliances that have unlined
stainless steel combustion chambers, protect the
chamber by lining the inside surfaces with a ce-
ramic fi ber blanket, such as a wet-pac or other
suitable refractory material.
Some steel chambers may not require liners be-
cause the appliance was designed and tested
for use with fl ame retention burners. Refer to the
manufacturer's instructions.
Table 3. Chamber Dimensions
Chamber Dimensions (inches)
Firing
Round
Rectangular
Rate
I.D.
Width
(GPH)
0.50
8
7
0.75
9
8
1.00
10
9
1.25
11
10
1.50
12
11
2.00
14
12
2.50
16
13
3.00
18
14
Page 6
Height
Floor to
nozzle
Length
8
12
5-6
9
12
5-6
10
12.5
5-6
11
12.5
5-6
12
13
6-7
15
13.5
6-7
17
14
7-8
18
15
7-8

Prepare the Burner

Low Firing Rate Baffl e
The AFG Low Firing Rate Baffl e (LFRB) reduces
the air fl ow and pressure. The LFRB is sometimes
used for fi ring rates under 1.00 gph as listed in
Table 4. Refer to the appliance manufacturer's in-
structions. Do not omit the LFRB when specifi ed.
Omitting the baffl e when specifi ed or installing the
baffl e when not specifi ed could result in impaired
burner performance.
Table 4. AFG Reduced Firing Rates
LFRB)
Burner head type
F0
F3 or L1
F4 or F6
V1

Burner fuel unit

Verify that the burner fuel unit is compatible with
the oil supply system. For more details, refer to
"Connect fuel lines" later in this manual.

Nozzle and Pump Pressure

WARNING
Correct Nozzle and Flow
!
Rate Required
Incorrect nozzles and fl ow rates
could result in impaired combus-
tion, under-fi ring, over-fi ring, soot-
ing, puff-back of hot gases, smoke
and potential fi re or asphyxiation hazards.
Use only nozzles having the brand, fl ow rate (gph), spray
angle and pattern specifi ed by the appliance manufac-
turer.
Follow the appliance manufacturer's specifi cations for the
required pump outlet pressure for the nozzle, since this
affects the fl ow rate.
Nozzle manufacturers calibrate nozzle fl ow rates
at 100 psig.
When pump pressures are higher than 100 psig,
the actual nozzle fl ow rate will be greater than the
gph stamped on the nozzle body. (Example: A
1.00 gph nozzle at 140 psig = 1.18 gph)
Securely tighten the nozzle (90 torque inch pounds). For
typical nozzle fl ow rates at various pressures refer to Ta-
ble 5.
(with
Low Firing Rate Baffl e installed
up to 0.65 gph
up to 0.85 gph
up to 0.90 gph
up to 1.00 gph
RWB 6104 BAFG R02