Page 1
Installation & Servicing Instructions Baxi Bermuda BBU 15 HE Condensing Back Boiler Unit These Instructions must be read in conjunction with those for the separate Valor Dimension electric firefront. They include the Benchmark Commissioning Checklist and should be left with the user for safe keeping.
Page 2
Natural Gas Baxi Bermuda BBU 15 HE G.C.No. 44 075 09 For use with the following electric firefronts: Valor Dimension Classica Brass, Pewter or Black BBU Firefront Valor Dimension Dream Gold, Chrome or Black BBU Firefront Valor Dimension Innova BBU Firefront...
Competent Person's Self Certification Scheme Install and Commission this appliance to manufacturer's instructions Complete the Benchmark Checklist If you notify via the ‘Gas Safe Register’, the register will issue the Building Regulations certificate on members’ behalf Scheme Members only Call ‘Gas Safe Register’ on: 0800 408 5577 or log onto: www.GasSafeRegister.co.uk...
Page 4
You can check your engineer is registered by telephoning 0800 408 5500 or online at www.GasSafeRegister.co.uk The boiler meets the requirements of Statutory Instrument “ The Boiler (Efficiency) Regulations 1993 N 3083” and is deemed to meet the requirements of Directive...
Page 5
Where possible transport the boiler using a sack truck or other suitable trolley. Always grip the boiler firmly, and before lifting feel where the weight is concentrated to establish the centre of gravity, repositioning yourself as necessary. See the ‘Installation’ section of these instructions for recommended lift points.
IMPORTANT: To commission the boiler it is is necessary to remove the Boiler Control from the firefront packaging and connect it to the boiler at the upper right hand side (item 6).
Page 9
Flue Kit (10m & 12.5m) (Fig. 3a) Terminal Cap Flue Duct Adaptor Air Cowl Air Duct Collar Air Duct Clamp Closure Plate Boiler Adaptor 60mm Ø Seal Collar Securing Screws x 4 100mm Ø Seal 60mm Ø Flue Duct 100mm Ø Air Duct ‘C’ Clip...
The static head must not exceed 30m of water. The static head must not be less than 1m of water. The boiler must not be used with a direct cylinder. Drain cocks should be fitted to all system low points.
Page 12
›25°C) an external bypass must be fitted . 6. The bypass must be of the automatic pressure operated type. Storage Systems 1. For information regarding the use of a Bermuda BBU 15 HE boiler with a storage system, contact the appropriate storage system manufacturer.
Page 13
It shall be positioned in the flow pipe either horizontally or vertically upwards and close to the boiler. No shut off valves are to be placed between the boiler and the safety valve. The valve should be installed with a...
Page 14
Where a vessel of the calculated size is not available, the next available larger size should be used. The boiler flow temperature is controlled at approx. 75°C. The vessel size can now be determined from the information in table 1 where V = System volume in litres.
Page 16
2. Only one of the two available MULTIIFIT vertical concentric Flexi Flue kits approved for use with the boiler can be used (10m kit 720101701 or 12.5m kit 720102001). Any proprietary flue systems, terminals, adaptors etc. MUST NOT BE USED.
Page 18
BS 6798 & Part H1 of the Building Regulations give further guidance. 2. If any further drain pipe is required (additional to that supplied with the boiler), it should be run in a proprietary material e.g. PVC, PVC-U, ABS, PVC-C or PP. John Guest ‘Speedfit’ components are recommended.
Page 19
2. If the boiler reset rocker switch has been operated the pump will run also for 2 seconds. 3. When the level of condensate in the sump is sufficient to activate the discharge float switch the pump will run for 7 seconds, during which time about 0.6 litres of condensate will...
Page 22
60mm flue duct. 16. In a similar way to fitting the boiler adaptor fit the air duct clamp to the air duct. This will prevent the duct falling back into the chimney (Fig. 27).
Page 23
60mm lip seal into the first groove (Fig. 30). The flue duct adaptor can now be fitted in the same manner as the boiler adaptor (Fig. 31). 18. Fit the terminal cap over the flue duct adaptor and air cowl.
Page 24
Carrying & lifting equipment should be used as required, e.g. when installing on another floor. 1. Lift the boiler from the packing base and place into the opening. 2. Align the boiler centrally as far back in the opening as possible, and ensure the distance between each side and the opening is equal.
7. Ensure all external controls e.g. room stat, timer etc. are calling for heat and turn on the mains electrical supply. Turn the rocker switch at the top right of the boiler to ON. The fan and condensate pump will run briefly.
Page 26
IMPORTANT: The loose boiler serial number label supplied in the boiler kit must be applied to an area of the spacer frame that is visible to the end user e.g. lower right hand side.
BS 7967, Parts 1 to 4. Check the Combustion Performance 5. Set the boiler to operate at maximum rate as described in Section 11.1.2 to 11.1.6. 6. Remove the threaded plug from the sampling point, insert the analyser probe and obtain the CO/CO be less than 0.004.
Page 28
Annual Servicing - Inspection 1. Ensure that the boiler is cool. 2. Ensure that the gas supply to the boiler is isolated. 3. Operate the Reset switch (Fig. 41) to activate the condensate pump and then repeat. This will empty most of the condensate from the sump.9.
Fig. 48 10.0 Changing Components 10.1 Changing Components 1. To change any components on the back boiler it is necessary to remove the firefront. 2. Refer to the Installer Guide that accompanies the firefront for details of removal. 3. Ensure that the boiler is cool and that the electrical and gas supplies are isolated.
Page 30
5. Undo the combustion panel securing nuts and remove the special spring washers. Remove the complete fan & panel assembly from the boiler. Check the condition of the insulation piece. 6. Undo and remove the nuts and washers securing the fan to the gas/air inlet.
Page 31
Gas/Air adjustment screw until it is flush with the valve body, then turn the screw 4 full turns clockwise (Fig. 51). If the boiler will not light, or the correct CO contact the ‘heateam’...
- see Section 9.1 1. The combustion (CO boiler for several minutes. To do this it is necessary to set the boiler to ‘Calibration Mode’. 2. Ensure that all external controls are calling for heat. The actual current boiler temperature is shown on the display.
To perform a Service Reset it is necessary to have access to the boiler. By pressing the Reset rocker switch on the right of the boiler case for a minimum of 5 seconds when error codes are displayed it is possible to reset the boiler once the fault has been rectified.
Page 35
Refer to Section 16.0 “Illustrated Wiring Diagram” for position of terminals and components Central Heating - Follow operational sequence Turn on Power Supply Display Illuminates Error 110 flashing Error 131 flashing Error 20 or 28 flashing Error 158 flashing Turn Central Heating thermostat to Maximum.
Fault Finding Solutions Sections Is there 230V at: Main terminals L and N Main terminal fuse PCB - X1 connector terminals 1,2 Check all system wiring and pump Service Reset Condensate Pump does not run PCB - X3 connector terminals 5 & 6 for at least 2 seconds Condensate Pump terminals for at least 2 seconds...
This Commissioning Checklist is to be completed in full by the competent person who commissioned the boiler as a means of demonstrating compliance with the appropriate Building Regulations and then handed to the customer to keep for future reference. Failure to install and commission this equipment to the manufacturer’s instructions may invalidate the warranty but does not affect statutory rights.
SERVICE RECORD It is recommended that your heating system is serviced regularly and that the appropriate Service Record is completed. Service Provider Before completing the appropriate Service Record below, please ensure you have carried out the service as described in the manufacturer’s instructions.
If you would like heateam to carry this out please call on 0844 871 1525. Our promise to you If you experience a fault with your new boiler, we aim to provide a safe and high quality repair service supported by our dedicated national network of highly skilled engineers.