Installing - Robertshaw 9420 User Manual

Digital non-programmable thermostat
Hide thumbs Also See for 9420:
Table of Contents

Advertisement

Recycling Thermostat
If this thermostat is replacing a thermostat that contains mercury
in a sealed tube, do not place your old thermostat in the garbage.
Contact your local waste management authority for instructions
regarding proper disposal of the thermostat. If you have any ques-
tions, call Robertshaw technical support at 1-800-445-8299.
Step 2: Installing Model 9420 Thermostat
NOTE: FOR NEW INSTALLATIONS, MOUNT THERMOSTAT ON
1. Turn power off to the heating and cooling systems.
2. Place EMER-HEAT-OFF-COOL in OFF position (Figure 2).
3. Place
4. Remove the cover using a coin or screwdriver (Figure 3). Set aside.
INSIDE WALL, FIVE FEET ABOVE THE FLOOR. DO NOT
INSTALL BEHIND A DOOR, IN A CORNER, NEAR AIR
VENTS, IN DIRECT SUNLIGHT, OR NEAR ANY HEAT OR
STEAM GENERATING FIXTURES. INSTALLATION AT THESE
LOCATIONS WILL AFFECT THERMOSTAT OPERATION.
-ON-AUTO switch into AUTO position (Figure 2).
Figure 2
Figure 3
3
Maple Chase Company
www.maplechase.com
TM
Tech Service: 1-800-445-8299
M-F 7:30 a.m. - 5:30 p.m. CST
MADE IN MEXICO
SETTING OR CHANGING THE SETPOINT TEMPERATURE:
1. Press
or
button. Display will show SET and the current
temperature setpoint.
2. Press
or
button to adjust temperature setpoint.
3. After completing the change, the display will return to the current
room temperature after a few seconds.
CHANGING THE TEMPERATURE DIFFERENTIAL,
DEAD BAND, AND RESIDUAL COOL:
The temperature differentials are factory set at 1˚F and 2˚F for
1
ST
and 2
ND
stages respectively. The dead band for Auto-
changeover is set at 3˚F. To change settings:
1. Press the
and
buttons at the same time and hold for 1
second. Display will indicate: DIFFERENTIAL 1
ST
.
2. Press either the
or
button to adjust the 1st stage differ-
ential between 0.5˚F – 3˚F (0.5˚C - 1.5˚C).
3. Either wait five seconds or press the
button. The display
will indicate: DIFFERENTIAL 2
ND
.
4. Press either the
or
button to adjust 2nd stage differen-
tial between 1˚F – 6˚F (1˚C - 3˚C).
5. Either wait five seconds or press the
button. The display
will indicate: DEADBAND.
6. Press either the
or
button to adjust the dead band
between 3˚F – 6˚F (1.5˚C - 3˚C).
7. Either wait five seconds or press the
button. The fan
icon and ON will be displayed.
8. Press either the
or
button to adjust the Residual Cool
fan delay between 0, 30, 60, or 90 seconds.
9. The display will return to the current room temperature after
a few seconds.
120-1523