Honeywell T7560A Installation Instructions Manual
Honeywell T7560A Installation Instructions Manual

Honeywell T7560A Installation Instructions Manual

Digital wall module

Advertisement

Quick Links

CAUTION: This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in
accordance with the Installation Instructions, may cause interference with radio communication. It has been tested and
found to comply with the limits for a Class A computing device pursuant to Subpart J of Part 15 of FCC Rules, which are
designed to provide reasonable protection against such interference when operated in a commercial environment.
Operation of this equipment in a residential area is likely to cause interference, in which case, users at their own expense
will be required to take whatever measures may be required to correct the interference. Any unauthorized modification of
this equipment may result in the revocation of the owner's authority to continue its operation.
BEFORE INSTALLATION
All wiring must comply with local electrical codes and
ordinances or as specified on installation wiring diagrams.
Digital Wall Module (DWM) wiring can be sized from 16 to 22
2
AWG (1.5 to 0.34 mm
), depending on the application. The
maximum length of wire from a device to a wall module is
164 ft (50 m). Twisted pair wire is recommended for wire runs
longer than 100 ft (30.5 m).
CAUTION
EMI Noise Introduction.
Risk of erratic system operation.
Keep wiring at least one ft (305 mm) away from large
inductive loads such as motors, line starters, lighting
ballasts and large power distribution panels. During
installations, try to avoid areas of high EMI noise.
Run wall module wiring separately from 50 Vac or
greater power wiring.
Table 1. Types of DWM.
1
Sensor
Setpoint
T7560A
Tmp
Tmp/Hum
T7560B
T7560C
Tmp/Hum
1
Tmp = Temperature sensor; Hum = Humidity sensor
Table 2. Controller SW requirements for powering via
terminal 5 and new LCD signaling.
Fan Coil Unit
Hydronic
W7752
1.00.04
NOTE: A software module (ModAL module GNRSC02A) is
available to adapt the wall module to the respective
Excel 20, 50, 80, 100, 500, 600 controller, making
any further configuring obsolete. Contact your local
Honeywell distributor for further details.
® U.S. Registered Trademark
Copyright © 2003 Honeywell Inc. • All Rights Reserved
T7560A,B,C Digital Wall Module
Bypass
Override
wheel
button
wheel
button
-
-
Chilled Ceiling
W7762
W7763
1.00.03
1.00.03
DWM DISASSEMBLY
The T7560A,B,C comes packed with a subbase that mounts
separately for ease of installation. The cover is fixed by a
latch on the underside of the unit. Remove the cover as
shown in Fig. 1 (T7560A,B) or Fig. 2 (T7560C):
1. Insert the tip of an awl or a similar narrow, pointed
object into the small hole in the latch (T7560A,B) or
simply depress the latch by hand (T7560C).
2. Pry off the cover.
Fan
button
button
Fig. 1. DWM disassembly (T7560A,B)
-
INSTALLATION INSTRUCTIONS
Fig. 2. DWM disassembly (T7560C)
EN1B-0146GE51 R0303
95-7620-4

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell T7560A

  • Page 1 1. Insert the tip of an awl or a similar narrow, pointed 164 ft (50 m). Twisted pair wire is recommended for wire runs object into the small hole in the latch (T7560A,B) or longer than 100 ft (30.5 m).
  • Page 2: Installation

    18...30 Vdc; I < 5 mA Controllers with the following output ratings can be connected to terminal 5 Fig. 3. Mounting of DWM (T7560A,B shown) (ratings are met by all Excel 10 controllers): • 5 V with 389 ohms See Fig. 6 for T7560A,B,C mounting dimensions.
  • Page 3 (see table 2). An Excel 500 with 6V/8V/10V signaling from the controller is used. The T7560A is then powered by terminal 5. When all wiring is complete, attach the cover of the DWM as is shown in Fig. 5.
  • Page 4: Normal Operating Mode

    T7560A,B,C DIGITAL WALL MODULES CONFIGURATION (T7560A,B) After installation, the T7560A,B DWM must be configured in P1 Setpoint Type Setting order to perform as desired. This is done by using the Scale Type Setting buttons and the setpoint wheel (see Fig. 7).
  • Page 5: Configuration Items In Software Version 2.10 And Above

    T7560A,B,C DIGITAL WALL MODULES Configuration Items in Software Version 2.10 and Above P6 Device type This item configures different devices. IMPORTANT: Stay on P6:1 and do not change to other configurations. P7 Temperature offset • Temperature offset; values of 0 through 99 are valid.
  • Page 6 T7560A,B,C DIGITAL WALL MODULES ACCESSORIES T7460LONJACK The T7460LONJACK allows to easily access L ® ORKS via the wall module. L ® will be connected to the 2 ORKS LON® terminals. Via the 3.5 mm jack plug, a PC connection can be established.
  • Page 7 T7560A,B,C DIGITAL WALL MODULES 95-7620-4 EN1B-0146GE51 R0303...
  • Page 8 T7560A,B,C DIGITAL WALL MODULES Honeywell Automation and Control Solutions Honeywell AG Böblinger Straße 17 D-71101 Schönaich Phone: (49) 7031 63701 Fax: (49) 7031 637493 http://europe.hbc.honeywell.com Subject to change without notice. Printed in Germany Manufacturing location certified to EN1B-0146GE51 R0303 95-7620-4...