Error Code Table - Panasonic CS-HE9DKE Service Manual

Panasonic air conditioner user manual
Hide thumbs Also See for CS-HE9DKE:
Table of Contents

Advertisement

13.2.1.2. Error Code Table

Diagnosis
Abnormality / Protection control
display
H11
Indoor / outdoor abnormal
communication
H14
Indoor intake air temperature sensor
abnormality
H15
Outdoor compressor temperature sensor
abnormality
H16
Outdoor Current Transformer open
circuit
H19
Indoor fan motor mechanism lock
H23
Indoor heat exchanger temperature
sensor abnormality
H26
Ionizer abnormality
H27
Outdoor air temperature sensor
abnormality
H28
Outdoor heat exchanger temperature
sensor abnormality
H33
Indoor/Outdoor wrong connection
H97
Outdoor Fan Motor lock abnormality
H98
Indoor high pressure protection
H99
Indoor heat exchanger anti-freezing
protection
F11
Cooling / Heating cycle changeover
abnormality
F91
Refrigeration cycle abnormality
F93
Outdoor compressor abnormal revolution
F95
Cool high pressure protection
F96
IPM (power transistor) overheating
protection
F97
Outdoor compressor overheating
protection
F98
Total running current protection
F99
Outdoor Direct Current (DC) peak
detection
Note:
"O" - Frequency measured and fan speed fixed.
The memory data of error code is erased when the power supply is cut off, or press the Auto Switch until "beep" sound heard
following by pressing the "RESET" button at remote controller.
Although operation forced to stop when abnormality detected, emergency operation is possible for certain errors (refer to Error
Codes Table) by using remote controller or Auto Switch at indoor unit. However, the remote controller signal receiving sound is
changed from one "beep" to four "beep" sounds.
Abnormality
Emergency
Judgement
operation
> 1 min after starting
Indoor fan operation
operation
only
Continue for 5 sec.
Continue for 5 sec.
(Cooling only)
Continue for 5 sec.
Continue for 5 sec.
4 times occurrence
within 30 minutes
2 times occurrence
within 20 minutes
4 times occurrence
within 20 minutes
4 times occurrence
within 20 minutes
4 times occurrence
within 10 minutes
3 times occurrence
within 20 minutes
7 times occurrence
continuously
71
CS-HE9DKE CU-HE9DKE / CS-HE12DKE CU-HE12DKE
Primary location to verify
Internal / external cable
connections
Indoor / Outdoor PCB
Intake air temperature sensor
(defective or disconnected)
Compressor temperature sensor
(defective or disconnected)
Outdoor PCB
IPM (Power transistor) module
Indoor PCB
Fan motor
O
Heat exchanger temperature
sensor (defective or disconnected)
Indoor PCB
Ionizer
O
Outdoor temperature sensor
(defective or disconnected)
O
Outdoor heat exchanger
temperature sensor (defective or
disconnected)
Indoor/Outdoor supply voltage
Outdoor PCB
Outdoor Fan Motor
Air filter dirty
Air circulation short circuit
Insufficient refrigerant
Air filter dirty
4-way valve
V-coil
No refrigerant
(3-way valve is closed)
Outdoor compressor
Outdoor refrigerant circuit
Excess refrigerant
Improper heat radiation
IPM (Power transistor)
Insufficient refrigerant
Compressor
Excess refrigerant
Improper heat radiation
Outdoor PCB
IPM (Power transistor)
Compressor