The TH149 thermostat is used for the following systems:
Heat pump (1H1C and 2H1C)
HVAC (1H1C)
The thermostat incorporates the following functions:
System mode selection: heat, cool, auxiliary heat and off
Fan mode selection: automatic or on (continuous)
Emergency heat and fault LEDs
Activation indicators (heat, cool, and auxiliary heat)
Temperature display in °C or °F
Backlit display
Programmable heating and cooling cycle lengths
Keypad lock
Emergency heat
indicator
Setpoint
indicator
Temperature
display
Cooling is On
Heating is On
Temperature adjustment buttons
* Auxiliary heat is available only for 2H1C systems.
Installation
Note:
The installation must be performed by a qualified electrician.
2.1 Removing the Old Thermostat
IN ORDER TO AVOID ANY RISK OF ELECTRIC SHOCK, CUT POWER TO
THE HEATING SYSTEM.
Remove the old thermostat to access the wires.
Identify and label each wire (with the corresponding letter on the old ther-
mostat terminals) and remove them from the terminals.
If necessary, strip the end of each wire (maximum of 6 mm).
If necessary, wrap the wires around a pencil to pre-
vent them from falling into the wall cavity.
If the opening in the wall is too big, insulate it using
a non-flammable material to avoid air draughts
behind the thermostat.
2.2 Installing the Back Plate
Note: For a new installation, choose a location approximately 1.5 m (5 feet)
above the floor and on an inside wall. Avoid draughty areas (top of staircase,
air outlet, etc.) or dead air spots (behind doors). Do not install the thermostat
on a wall concealing air ducts nor expose it to direct sunlight.
TH149
TH149
Electronic Thermostat
for Heat Pump and HVAC Systems
Installation and User Guide
Fault
indicator
Fan mode
selector
Auxiliary heat
is On *
System mode
selector
Loosen the locking screw (the screw cannot be com-
pletely removed).
Detach the front module from the back plate by pulling
the bottom part.
1.
If necessary, bore the mounting holes
and insert anchors.
Pass the wires through the opening of
the back plate and fix the plate to the
wall using the screws provided.
2.3 Connecting the Thermostat
The connection of the new thermostat should be similar to that of the old ther-
mostat; however, it can vary depending on the installation.
R; C
Power; 24 VAC
W
Heater. This connection is not required for HP-1H1C.
Y
Compressor
G
Fan
Reversing valve (see section 2.4). This connection is not required
O/B
for HVAC-1H1C.
L
Fault
2.
2.4 Jumper settings
The jumpers (JP1 and JP2), on the back of the front module, are used to con-
figure the thermostat according to your system type:
Jumper
Parameter
JP1
System
Reversing
JP2
valve
2.5 Completing the Installation
Reinstall the front module onto the back plate and tighten the locking
screw.
Place the system mode selector switch to OFF.
Note:
Leave the switch to OFF until you have verified that the thermostat is
properly configured (see section 3).
Apply power back to the system.
Ensure that the thermostat is configured according to your system type
(see section 3).
Settings
• Heat pump (HP position - default)
• HVAC (CN position)
• Activated in cool mode (O position - default)
• Activated in heat mode (B position)
400-149-000-B
10/5/05
1/2

Advertisement

loading

Summary of Contents for Aube Technologies TH149

  • Page 1 Heat Pump and HVAC Systems Installation and User Guide Introduction The TH149 thermostat is used for the following systems: • Heat pump (1H1C and 2H1C) • HVAC (1H1C) The thermostat incorporates the following functions: • System mode selection: heat, cool, auxiliary heat and off •...
  • Page 2: Configuration Menu

    • When the setpoint is not attained after a 15-minute delay following the compressor activation. After the delay, the auxiliary heating is used along with the compressor. • When the thermostat is placed in emergency heating (E.H.). In this mode, only the auxiliary heat is used. 4.2 Fan Mode Use the fan mode selector switch to place the fan in automatic mode (AUTO) or continuous mode (ON).