Chimney Installation - Napoleon NZ25 Installation And Operation Instructions Manual

Solid fuel burning - zero clearance hi-tech listed fireplace
Table of Contents

Advertisement

8

CHIMNEY INSTALLATION

This fireplace was tested to CAN/ULC S610-M87 Zero Clearance Fireplace Safety Test Standard. In accordance with this
standard, the unit may be connected to any accepted chimney listed to ULC S-629. The following 7" factory-built chimney
systems may be used:
MANUFACTURER
OLIVER MACLEOD
SECURITY
ICC
ENERGY VENT
GSW
SELKIRK METALBESTOS
Installation of all types of factory-built chimney systems is to be in accordance with the chimney manufacturers installa-
tion instructions. An appropriate chimney manufacturers anchor base plate is required in order to initiate the twist lock
mechanism. Air cooled chimney systems are not recommended in colder climates.
FIGURE 8 - STRAIGHT UP
No Off-Set. Minimum overall chim-
ney height is 15 feet.
WS-415-71 / 09.07.00
LISTED TO ULC S610-M87: : : : :
MODEL #
HT 6103(
HT3103)
FORMERLY
ASHT
EXCEL 2100-2
HT5103
FC
SSPLUS
FIGURE 9 - 2 ELBOWS
Single off-set with two 15°, 30° or
45° elbows. Minimum overall
chimney height is 15 feet.
MAXIMUM # OF OFFSETS
(30
MAX.)
(45
MAX.)
o
o
4 - 45
4 - 30
O
O
4 - 45
4 - 30
O
O
4 - 45
4 - 30
O
O
4 - 45
4 - 30
O
O
2 - 45
& 2-15
4 - 30
O
O
O
2 - 45
2 - 30
O
O
FIGURE 10 - 4 ELBOWS
Double off-set with four 15°, 30° or
45° elbows. Minimum overall chim-
ney height is 15 feet.