COF 199 COF 245 COF 315 COF 385 COF 455 COF 700 United Kingdom & Ireland OIL AND GAS FIRED WATER HEATER Installatie-, Gebruikers- en Servicehandleiding Installation, User and Service Manual Installations-, Benutzer- und Wartungsanleitung Manuel d’installation, Mode d’emploi, Manual d’entretien Manual de Instalación, Usuario y Servicio...
Page 2
An accredited installer must install the heater and commission it according to the locally valid requirements. The heater may only be installed in an area that meets the required ventilation regulations. A.O. SMITH CANNOT ACCEPT ANY RESPONSIBILITY FOR GUARANTEE, SERVICE AND/OR PRODUCT LIABILITY IN THE EVENT OF UNAUTHORIZED CHANGES, PRODUCT MODIFICATIONS OR REPAIRS.
Conditions for installation and use ....................24 Exclusions ...........................24 Range of guarantee ........................24 Claims ............................24 No other guarantee or warranty either expressed or implied is made on behalf of A.O. Smith Water Products Company................24 Appendix ..........................25 Electrical diagram cof ........................25...
GENERAL 1.1.1 Packaging material The packaging protects the device against Description of the heater transportation damage. The selected packaging material is environmentally friendly, recyclable Construction of the heater is in accordance with the and can be disposed of in a relatively easy and European standards for gas-fired water heaters for environmentally friendly way.
Technical safety equipment The overheating cut-out interrupts the current supply to the burner, as a result of which the gas valves of the gas block will close. 1.2.1 Control box The control thermostat can be set between 40°C The temperature control for the water heater is and 80°C by means of the temperature control knob.
The water heaters have been examined and tested with the following front-mounted burners from Riello: GAS-FIRED BURNER OIL-FIRED BURNER HEATER MODEL TYPE MODEL TYPE COF 199 BS 2 912 T1 RG 2 377 T1 COF 245 BS 2 912 T1 RG 2...
1.3.3 Technical data The data below only apply to front-mounted burners from Riello Oil: fuel oil, max. viscosity at 20°C: 6 mm DESCRIPTION unit COF 199 COF 245 COF 315 COF 385 COF 455 COF 700 NATURAL GAS (G20 - 20 mbar):...
Page 10
DESCRIPTION unit OIL DATA Burner model RG 2 RG 2 RG 3 RG 3 RG 3 RG 3 Burner type 377 T1 377 T1 393 T1 393 T1 393 T1 396 T1 1.25 X 1.5 X 1.75 X 2.25 X 2.75 X 2.0 X Nozzle (Delavan)
Pressure difference for switching off [mbar] UNIT GAS G20 GAS G25 GAS G30 GAS G31 COF 199 COF 245 COF 315 COF 385 COF 455 COF 700 The values above are recommended settings and have been determined under laboratory conditions.
Switching point gas-pressure switch [mbar] UNIT GAS G20 GAS G25 GAS G30 GAS G31 COF 199 COF 245 COF 315 COF 385 COF 455 COF 700 The values above are recommended settings and have been determined under laboratory conditions.
GAS G20 GAS G25 GAS G30 GAS G31 GAS G20 GAS G25 GAS G30 GAS G31 COF 199 COF 199 COF 245 COF 245 COF 315 COF 315 COF 385 COF 385 COF 455 COF 455 COF 700...
GAS G20 GAS G20 GAS G25 GAS G25 GAS G30 GAS G30 GAS G31 GAS G31 COF 199 COF 199 COF 199 COF 245 COF 245 COF 245 COF 315 COF 315 COF 315 COF 385 COF 385...
2. FOR THE INSTALLER 2.1.2 Water connections A.O. Smith water heaters are suitable for connection to If possible, use a trolley or fork-lift truck to transport the vented, unvented and pumped pressurised systems. In heater. The heater must be vertical at all times during each case appropriate valves and fittings should be used transportation.
2.1.2.1 Vented systems If the water heater is to be connected to a cold feed tank or cistern the hot water supply pipe must include an open vent which discharges over the cold feed cistern. The cold feed cistern must have an actual capacity of greater volume than the hourly recovery rate of the water heater(s) which it supplies.The minimum actual capacity is 50 gallons or 227 litres (see figure 3).
2.1.2.2 Unvented systems To install an A.O. Smith water heater on an unvented cold water supply system a kit of valves and fittings listed by the water research centre and complying with part G3 of the current building regulations and BS 7206 should be used.
Page 18
A.O. Smith water heaters are tested to a maximum pressure of 12 bar and a maximum working pressure of 8 bar. Dead legs on a hot water installation are undesireable. Where possible they should be avoided. Where the inclusion on the system of a dead leg is unavoidable the following restrictions should be applied: For pipes not exceeding 19 mm.
(see figure 9: Electrical 2.1.4 Flue gas exhaust diagram). For the COF 199 and 700 the adapter ring supplied must be fitted prior to connecting the flue gas exhaust. For the other models (COF 245, 315, 385, 455 and 700) the flue Commissioning gas exhaust can be connected direct to the water heater.
control again as soon as the high-limit thermostat is To inspect the tank: deactivated. 1. Close the cold-water inlet tap; If the overheating cut-out is activated, it must be reset 2. Empty the heater completely by opening the drain manually after the water has cooled down. Upon valve;...
Descaling Calcium deposition depends on the type of water and the demand. In addition, calcium deposition increases at high water temperatures. A temperature setting of 60°C is recommended, which will keep calcium deposition to a minimum. Access covers are located on the right and left sides for inspecting and descaling the tank.
3. Close all the hot-water taps. The heater is now under pressure. Maintenance should be carried out at least once a year in accordance with the recommendations of A.O. Smith. Failure to carry out adequate maintenance may render 3.1.3 Commissioning 1.
4. WHAT TO DO IN CASE OF FAILURE General If faults occur, check the following points: • Overheat thermostat The water heaters are equipped with an overheating cut-out, which, in the case of a too high water temperature, interrupts the current supply to the burner, as a result of which the gas valves in the gas block are closed and the gas supply is cut off.
F.O.B. ba- workmanship, the warrantor will exchange such part or sis. A.O. Smith accepts no responsibility for carriage, la- component. bour or other installation costs.
6. Appendix: 6.1 Electrical diagram cof 230V AC 50Hz IMD-0010 IMD-0010 Figure 9: Electrical diagram cof = brown H1 = Running time counter = blue SB = Fault alarm = yellow/green = black Note: If, in the case of a Riello front-mounted burner, a running time counter (H1) is connected by means of a cable = Earth longer than 3 m, a 47 nF capacitor must be fitted bet-...
Page 28
Instalador Ditta Installatrice Twój Instalator Eγκαταστάτη Σας Nederland United Kingdom A.O. Smith Water Products Company B.V. A.O. Smith Water Heaters Postbus 70 Unit B8 Armstrong Mall, Southwood Business Park, 5500 AB VELDHOVEN Farnborough, Hampshire, GU14 0NR 0800 - AOSMITH (2676484) 0870 - AOSMITH (267 6484) info@aosmith.nl...