10-8. Power Required To Start Motor
Single-Phase Induction Motor Starting Requirements
Motor Start
Code
KVA/HP
kVA/HP x HP x 1000
EXAMPLE: Calculate the starting amperage required for a 230 V, 1/4
HP motor with a motor start code of M.
Volts = 230
11.2 x 1/4 x 1000
230
10-9. How Much Power Can Generator Supply?
OM-4411 Page 44
4
AC MOTOR
1
VOLTS
230
3
CODE
M
HP
1/4
G
H
J
K
6.3
7.1
8.0
9.0
= STARTING AMPERAGE
VOLTS
HP = 1/4
Using Table, Code M results in kVA/HP = 11.2
= 12.2 A
Starting the motor requires 12.2 amperes.
1
2
2
AMPS
2.5
Hz
60
PHASE
1
L
M
N
P
10.0
11.2
12.5
14.0
1
Motor Start Code
2
Running Amperage
3
Motor HP
4
Motor Voltage
To find starting amperage:
Step 1: Find code and use table to
find kVA/HP. If code is not listed,
multiply running amperage by six to
find starting amperage.
Step 2: Find Motor HP and Volts.
Step 3: Determine starting amper-
age (see example).
Welding generator amperage out-
put must be at least twice the
motor's running amperage.
S-0624
1
Limit Load To 90% Of
Generator Output
Always start non-resistive (motor)
loads in order from largest to small-
est, and add resistive loads last.
2
5 Second Rule
If motor does not start within 5
seconds, turn off power to prevent
motor damage. Motor requires
more power than generator can
supply.
Ref. ST-800 396-A / S-0625